Autotuning Section 5-3

5-3 Autotuning

Autotuning can be used with all Feed Forward control strategies. The autotune feature uses a method of tuning similar to a limit cycle, which is described in Section 1, Cascade Control. When autotuning is activated it will be indicated by a blinking yellow LED on the front panel of the ES100.

Note The ES100 must be connected. 1. From the ES/TOOLS menu, select the Check Control icon.

2. Select from the Check control menu (Figure 12). Et Check control ia

| F1i:Run ty F2:Paran | |F3:status | Fa :commanal |F9:0pt ion || || ESC: Exit |

08/26/94 758.8

Clear data 97:59:42

Move point Monitor rend Setting §/5P

PY 74.63

Trend mode HU 168.80

PU

Interval 2 Second

Draw mode Clear + draw Change SP o iy] 9 & 3 o a 0 > > “a, 6:62:68 4:46:68 4:18:68

Figure 12

3. Select from the new vertical menu on the left side of the screen (Figure 13)., Check control Unit No.64 ia

| F1i:Run || F2:Paran | [F3:status | F4:command] [Fa :opt ion | | |[ Esc:Exit |

87/87/95 108 16:86:55

ESC : Cancel

Sel pattern Monitor

P 1 56.88 lV 48.89

I

Reset (stop)

Hold

PU

Advance Interval 2 Second

TREC

Draw mode

Clear + draw

6:02:06 4:46:60 4:16:06

Figure 13 4. Select to return to the Check control menu.

5. From the vertical menu on the left side of the screen, select [Exec AT. |

97

Downloaded from www.Manualslib.com manuals search engine

Page 102 read from a scan by OCR; it may hold reading errors

Autotuning Section 5-3

6. Anew pop-up window will appear (Figure 14). Enter the number of the PID bank you wish to Autotune.

Draw mode

Clear + draw

Change SP

Fa Check control Unit No.6@ KM | Fi:Run | | F2:Param | [Fa:Status | Fa :Conmand| [ro :Option | | | | ESC : Exit | aia,

Monitor 7 s Py 78 MY 48] |PID set No. > 2 Exec A.T. | esc Cancel | | ENT :OK | 2 Second

6:62:68 4:66:68 6:16:08

Figure 14

7. Select [ENT: OK }. The controller will now autotune. Do Not interrupt or stop this process. The controller will have completed autotuning when the yellow ‘AT’ light stops blinking on the front panel of the ES100.

98

Downloaded from www.Manualslib.com manuals search engine

Page 103 read from a scan by OCR; it may hold reading errors

Autotuning

Section 5-3

5-3-1 Fuzzy Logic Fine Tuning

Start controlling your process with the ES100 by placing it in the RUN mode. 1. From the ES/TOOLS menu, select the Check control icon.

2. From the Check control menu, select [Fa:Run |

3. From the vertical menu on the left side of the screen, select

If the performance of the controller is not satisfactory after autotuning, you may improve the performance of the ES100 by using the Fuzzy Logic Fine Tune. Follow these steps to get to the Fine Tune portion of the ES/TOOLS program.

1. From the ES/TOOLS Menu select the Check control icon.

2. Select from the menu on the left side of the screen (Figure 15).

FI Check control ia

| Fi:Run || F2:Param | |F3:status | Fa :command] |[F9:opt ion || || esc:excit |

68/29/94 758.8 16:68:33

Move point [_fenitor rend Setting 9/SP 168.68 Py 75.84 MY 6.007

Clear data

Trend mode

Exec A.T.

ypu

Interval 2 Second

Draw mode Clear + draw Change SP

CEEEEE REE

6:62:68 6:66:60 6:16:66

Figure 15

3. A Pop-Up window will appear to confirm the PID set that you are using.

99

Downloaded from www.Manualslib.com manuals search engine

Page 104 read from a scan by OCR; it may hold reading errors

Autotuning Section 5-3

4. Enter the appropriate PID set number and select (ENT: OK] a new pop-up window will appear Figure 16.

Clear + draw Change SP, Check control ia | Fi:Run || F2:Param | [F3:status | F4:Commana| |F9:opt ion || || esc:Exit | a ah f é - T va Clear data toe. F.T. required level setting Overshoot Moni rend Setting ISP Py me Exec A.T. | Rspons lunting 2 Se Draw ||ESC:Cance1| | ENT:0x |

6:62:66 6:66:66 6:16:68

Figure 16

5. There are five different levels of response that you can initiate using Fuzzy Logic Fine Tuning. Each triangle represents one level of strength. The more triangles you select the greater the reaction will be from the Fine Tuning effect of Fuzzy Logic. You can select one parameter (as is shown) or a maximum of two parameters, such as Response/Hunting, or Overshoot/Hunting. Use the keyboard cursor controls to move the red inner circle around the inside of the outer circle. The arrowheads will automatically fill in based on the position of the red circle.

6. Select after you have selected the level of corrective action you require.

7. ES/TOOLS will prompt you to execute fine tuning, select LENT:OK | Repeat Fuzzy Logic Fine Tuning as necessary to achieve optimum performance.

You have now completed tuning your ES100 for Feed Forward control.

100

Downloaded from www.Manualslib.com manuals search engine

Page 105 read from a scan by OCR; it may hold reading errors

Application

Section 5-4

5-4 Application

The following is a typical example illustrating how ES100 is used in Feed Forward control.

Alcohol Sterilizing System

Current-to-Pressure Transducer

ES100 used: ES100X-AAWHFE

Hot water tank

Alt

NL

74 1 f 1 1 1 c | 4

Flow sensor

Process Requirements

Heater

Temperature sensor

Filler tank

Filling machine

The system is comprised of 2 separate loops. The first loop is water heated by steam, stored in a hot water tank, and sent through a “heater” to sterilize the liquor (controlled flow).

1. The process was being controlled by holding the hot water tank at a specific temperature. This did not allow for changes in the flow of the liquor. Customer wanted to control the temperature of the alcohol directly.

Process needed to be very accurate because over/under temperature could cause sterilization and/or flavor differences.

Model Selection

With Feed Forward control, the temperature of the alcohol can be directly controlled using the flow of alcohol as the Feed Forward variable. By controlling the process this way we were able to better maintain SP resulting in greater production and lower product damage.

101

Downloaded from www.Manualslib.com manuals search engine

Page 106 read from a scan by OCR; it may hold reading errors

Application Section 5-4

102

Downloaded from www.Manualslib.com manuals search engine

Page 107 read from a scan by OCR; it may hold reading errors

Appendix A Control Modes mi ON/OFF CONTROL

The output remains ON when the controlled variable (CV) is below the set point (in heating mode). When the CV reaches the set point the output turns OFF. The output will not turn on again until the CV has dropped a specified amount below the set point. The difference between the point at which the output will turn OFF and the point at which it will turn ON is called hysteresis. ON/OFF control is simple but imprecise since the CV will never stabilize.

High Hysteresis temperature | Set point > 4 Input Low Time temperature

Control ON es ee ee ee output OFF m@ PROPORTIONAL-DERIVATIVE (PD) CONTROL

In proportional action the percentage of output is based on the amount of deviation frorm set point. Anywhere below the proportional (P) band, the outputis full ON. As the Controlled Variable (CV) moves through the band, the output percentage decreases in alinear fashion until the output is totally OFF at the top end of the P band. When derivative action (D) is added, the controller has the ability to respond to a process disturbance by increasing or decreasing the output percentage based on the rate of change of the CV.

High temperature

Set point, >

Input

Low temperature

ON Control OFF output mi PROPORTIONAL-INTEGRAL-DERIVATIVE (PID) CONTROL

Choose PID control action when tight control is required. The proportional action (P) varies the output percentage based on the amount of deviation from set point. But proportional control alone can only maintain the set point if the system is designed so that the required output at set point is 50%. Since few systems meet this requirement exactly, an offset often occurs. Integral action (I) checks for this offset, and eliminates it by shifting the proportional band up or down. Derivative action (D) give the controller the ability to respond to a process disturbance by increasing or decreasing the output variable based on the rate of change of the controlled variable.

High temperature

Proportional band

Set > point Input

Low temperature, > Time

ON Control OFF output

103

Downloaded from www.Manualslib.com manuals search engine

Page 108 read from a scan by OCR; it may hold reading errors

Control Modes Appendix A

104

Downloaded from www.Manualslib.com manuals search engine

Page 109 read from a scan by OCR; it may hold reading errors

Appendix B PID Conversions

In Process Control, PID is sometimes referred to as GAIN, RESET, and RATE opposed to PROPORTIONAL BAND, INTEGRAL, and DERIVATIVE. The following conversions should be used as necessary:

100 9, =_ PROPORTIONAL BAND (%) = Gar INTEGRAL TIME (sec) = ©2 - RESET (repeats/min) 60 DERIVATIVE TIME (S80) = 5 ATE Gepeats/min

The following algorithm formula is set by ISA standards and is called Non-Interacting PID Algorithm based on the fact that the Integral and Derivative are non-interacting with each other. See equation below:

_ _- de(t) m(t) = Ke [e(t) + 7; fe(dt + Td it ] m(t) = Controller Output Ke = Gain (i.e. 100/PB)

Ti = Integral or Reset time Td = Derivative or Rate Time e(t) =Error signal

Most of OMRON’s controller E5X - - ES 100 series use a form of the equation above.

105