Page 91 read from a scan by OCR; it may hold reading errors

Applications Section 4-5

4-5 Applications

4-5-1 Heating Furnace ES 100 used: ES 100X-AAWHFE

Temp. control of air and fuel Temp. control of furnace

ES100X A AI 2)

or Furnace a

Burner

Process Requirements

1. Improve combustion efficiency by reducing the amount of air required to burn the metal in the process.

2. Ensure complete combustion of gas in furnace by controlling the ration of fuel to air.

Model Selection

1. The first ES100 is controlling the ratio of fuel to air. By having an ES100 do this using Fuzzy Logic, very tight control was obtained on the mix, allowing complete combustion of the gas used in the process.

2. The second ES100 was used to achieve tight control of the temperature of the furnace. By having an ES100 doing this, the amount of air required for complete combustion was reduced. Another benefit was less pollution created by the process.

86

Downloaded from www.Manualslib.com manuals search engine

Page 92 read from a scan by OCR; it may hold reading errors

Applications Section 4-5

4-5-2 Seat Belt Manufacturing ES 100 used: ES 100X-AAWHFE

Entrance roll (fixed speed) Exit roll

Seat-belt Lo

Motor Motor Tacho-meter Tacho-meter, >Alt¢

: ‘a A01 Alok ,

Process Requirements

Control the length of the seat belt by changing the rotation speed of the entrance and exit rolls. Model Selection

1. The ratio ability allowed the ES100 to take the uncontrolled speed of the entrance and match the exit roll speed at the appropriate ratio thereby maintaining the desired length of the seat belt.

2. The use of multiple AP registers provides for many different seat-belt lengths.

87

Downloaded from www.Manualslib.com manuals search engine

Page 93 read from a scan by OCR; it may hold reading errors

SECTION 5 Feed Forward Control

5-1 What is Feed Forward Control ... 90 5-1-1 Start-up Procedure ... 92 5-1-2 Analog Operation Assignment Table ... 92

5-2 Operation and Tuning ... 93

5-3 Autotuning ... 97 5-3-1 Fuzzy Logic Fine Tuning ... 99

5-4 Application ... 101

89

Downloaded from www.Manualslib.com manuals search engine

Page 94 read from a scan by OCR; it may hold reading errors

What is Feed Forward Control

Section 5-1

5-1

90

What is Feed Forward Control

Feed Forward control is a feature of the ES100 process controller which is used to anticipate a process and minimize its effect on the process. After the controller detects the disturbance, it adjusts its Manipulated Variable (MV) so it will be able to offset the estimated change in the process. It is able to do this by using two sensors; one placed within the process, the other to measure the value of a process ingredient before it arrives where the process is controlled.

An example of this is food sterilization by steam. The flow of food into the sterilization chamber is not continuous, and the temperature in the chamber has to be precisely controlled to avoid scalding the food or insufficiently sterilizing it. Standard Control

With standard control strategies (i.e. one feed back loop only), the process cannot be controlled accurately because of the variable flow of food into the system (Figure 1). By controlling the amount of steam pressure around the chamber, the temperature of sterilization chamber can be accurately controlled. Pe, SP aie Temperature Sensor

Disturbance

MV ' Steam -, _ - _ - _ - _~

Figure 1

Figure 2 shows an example of the process trend without feed forward control. When the flow of food into the chamber drop, the temperature increases because there is less food to absorb the heat. As a result, the temperature increase will scald the food.

Further in the time before the controller regains control of the process, all incoming food will be damaged by the excessive heat.

(Load)

Food |_-__-_-_-__-_~- = Flow

(°F)

PV ---------- ~"

Temperature of food

Load variation vs. Food temperature

Figure 2

Downloaded from www.Manualslib.com manuals search engine

Page 95 read from a scan by OCR; it may hold reading errors

What is Feed Forward Control Section 5-1

Feed Forward Control

By placing a second sensor in the path of the food (a flow sensor) the system can now anticipate the flow of food before it enters the chamber and adjust the steam pressure (Figure 3). This is known as a Feed Forward control strategy. PVVAM SP PV2/Al2 TIC] f t ' Temperature Sensor MV | Y Steam = atl (Load) Food | --_----_-- a Flow , \ t (°F) py|------------- pO Ne Temperature of food

Load variation vs. t Food temperature

Figure 3

By using the Feed Forward control method, the controller detects the reduced flow of food and can slow down the flow of steam before it scalds the food.

To set up this Feed Forward method in the ES100, the ratio of steam pressure to food flow must be determined and entered into the ES100. That ratio is know as the Feed Forward Variable (FFV).

Once this is accomplished, you will see a considerable improvement in the control performance. This is because the response of the MV to the disturbance is much quicker than with a normal single loop control strategy.

It is important to note that Feed Forward control is used in conjunction with the existing PID algorithm. It is designed as an enhancement to the PID loop.

91

Downloaded from www.Manualslib.com manuals search engine

Page 96 read from a scan by OCR; it may hold reading errors

What is Feed Forward Control Section 5-1

5-1-1 Start-up Procedure For Feed Forward control, any ES100 with two analog inputs may be used.

The following part number represents an ES100 controller with two analog inputs. ES100_ -__W_

Not used (@) i oo 8 ; ® wee ee © CT +63: @ | a S B----g eg 3 Valve C6), ---- - 8 roo 5 1 + I + \ @ | @ | 64), 9° ' A01 ©, rE) 2 4) | 6) 1 8: 4-20 MA : ; suse © i @ i RTD b Flow sensor SUB1 a) |- - - - 7 ----4 9) * +0 | 8; - - Al Al2 o@ ' 4-20 MA 4-20 mA Figure 4

Figure 4 shows a wiring diagram for the food processing example. It is shown in a Feed Forward configuration with the following requirements:

¢ PV1/Al1 = Platinum RTD (process)

¢ PV2/Al2 = Flow Sensor 4-20 mA (food flow)

¢ MV/AQ1 = Control Valve 4-20 mA (steam flow)

5-1-2 Analog Operation Assignment Table For Feed Forward Control, delete data in columns 6, 8 and 9 from your Analog operation table. Column 7 is used for Feed Forward Control, while columns 6, 8 and 9 are not (Cascade Control only). Use either the Edit menu or keyboard to delete data in columns 6, 8 and 9.

Deleting Data Using the Edit menu 1. From the main menu select the Setting <offline> icon.

2. From the Setting menu <offline>select button. The Analog operation assignment menu will appear.

3. Select and you will see the following screen (Figure 5):

Fo f Analog operation assignment ‘Or Fi :Details| | || F3: Image || F4:Edit | |Fo:0ption] | Fi6:Help || ESC: Exit ] | [ 1[ if 1f if it Edit | ESC:Cancel, [4 Display right page (CTRL+R) Display left page (CTRL+L) N1 Arg 1 Delete (CTRL+D) Ni Arg 2 Copy (CTRL+¥)|| NZ Oper Move to top (CTRL+T) [Nz arg 1 || |Move to botton (CTRL+B) NZ Arg 2 Delete all (CTRL+A) rr |¥

Figure 5

92

Downloaded from www.Manualslib.com manuals search engine

Page 97 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 5-2

4. Select the button.

5. ES/TOOLS prompts you to select a starting point to delete. Select the beginning of column 8 to the end of column 9.

6. Select button to delete data within these columns. Repeat steps 4 and 5 to delete data in column 6.

7. Select button.

Deleting Data Using the Keyboard 1. Press the <CTRL> and <D> keys at the same time.

2. ES/TOOLS prompts you to select a starting point to delete. Select the beginning of column 8 to the end of column 9.

3. To delete data within these columns, press the <ENTER> key. Your Analog Operation Table should look like Figure 6.

Fo fmalog operation assignment Zz Fi:Details|| }| F3: Image || F4:Edit | |F9:option|| F160 :Help || ESC: Exit | 5 6 7 8 9 18 assign dest |} |stp ||- poz || - - MoV END MoU END END END AP31 - AI2 - - - END END END END END END

Figure 6

5-2 Operation and Tuning

The first step in setting up a Feed Forward control application is to scale the control inputs.

Scaling the Control Inputs

In this example we will set up the controller to scale 4-20 mA signal for input Al2. The full scale of the food flow (Al2) is 0-500 kg/min. As an aid to organizing information that will be programmed into the ES100, use the table below. Input | Item Low End High End Al2 Input from Sensor 4 20 Value to be displayed on Front panel of the 0 25 ES100

Program the ES100 as follows:

1. From the ES/TOOLS menu, click on the Setting <offline> icon. 2. From the Setting menu <offline> select the button.

93

Downloaded from www.Manualslib.com manuals search engine

Page 98 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 5-2

3. Select from the Analog operation assignment menu. A pop-up menu appears (Figure 7).

Fe Analog operation assignment iO F1:Details| | || F3: Image || F4:Edit | |F9:opt ion] | F18:Help || ESC ‘Exit | 1 2 3 4 5 6

Assign dest

Set Analog Operation Details

Ni Oper ESC :Cancel

Ni arg 1

SCL (straight-line approximation)

Ni Arg 2 FNC (Cbroken - line approximation)

AP1 to AP3Z (analog operation parameters)

[Nz Oper

[Nz Arg 1

AP1 al

Figure 7

4. Select SCL (straight-line approximation) | button. The Straight-line approximation menu (Figure 8) will appear. For the food sterilization example, you must complete the table exactly as shown.

E} Straight-line approximation i | }| || || ]|F9:option] | F1a:Help || esc:Exit | Set by number key.

1 2 3 4 6.686 6.000 6.0608 6.008 6.008 6.000 6.060 6.6808 1.606 6.4006 6.060 6.868 6.568 6.008 6.060 6.660 Figure 8

Note The ES100 uses a Normalizing process to scale low end and high end values from the actual sensor input to the controller. This internal process uses 0-1 as the full scale. As a result, it is necessary to input 0 for the low end and 1 for the high end of the sensor output scales, not 4 and 20 (the actual output range).

Column 1 is used to scale Al2 for display and normalization after it (Al2) has been ratioed. To enter the values, simply click the cursor on the value in the appropriate place in the table. For this example the table should appear exactly as shown above.

Note Read the following button definitions. Low end value of the actual sensor input to the controller. Low end value to be displayed on the front panel of the ES100. High end value of the actual sensor input to the controller.

94

Downloaded from www.Manualslib.com manuals search engine

Page 99 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 5-2

High end value to be displayed on the front panel of the ES100. 5. Select to return to the Analog operation parameters menu.

Linking the Control Ratio Program to ES100 Operation

Now that the ration programming is complete. It is necessary to link it to the core program of the ES100 using the Analog operation assignment table. To do this, follow the procedures below.

1. From the Setting menu <offline>menu, select (Figure 9)., Setting Menu <Offline> ‘iO | Fi:File || || || ||F9:option| | || Esc:Exit | | Controller type [ ESi6@P-AA WHA4FE Ver. 2.x J ] | Configuration Parameters ] Parameter | Sp conditions | bper at PU error| Control parans ] | Output | | Front panel ] Power ON oper ] | Event | | ] Communications ] | | technical parans| ] TT

Program Assignment | Program | | Digital oper ] Analog oper ] [File nane |RaTIO1.ES4 || comment | | Figure 9

2. From the Analog operation assignment table, double-click on the area intersected by Assign dest and column 6. A pop-up menu appears. Scroll through the menu and double-click on FFV (Feed Forward amount).

3. Double-click on the N1 Oper/column 6 intersection. Scroll through the pop-up menu and select SCL1 (Straight-line approximation).

4. Double-click on the N1 Arg1/column 6 intersection. Double-click on Al2 (Analog Input 2).

For this example, column 6 should look exactly like the one shown in

Figure 10., Analog operation assignment ‘iO F4:Details| | || F3: Image || F4:Edit ||F9:option || F1i6:Help || ESC: Exit ] 4 5 6 ? 8 9 lassign dest ||} [eos |lstp|jrry|fpvzf|- | |-

MOV MoV SCL1i MoV END END PV AP31 AIL AlzZ - - END END END END END END piyguio iv

95

Downloaded from www.Manualslib.com manuals search engine

Page 100 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 5-2

The programming in column 6 reflects the connection of the basic Feed Forward program to the core of the ES100.

You have completed programming the ES100 to operate in a Feed Forward control mode. Now link this data into the operating program of the ES100. To do this proceed as follows.

1. Position your cursor in column 6, in line with Assign dest which is lo-cated on the left side of the Analog operation assignment menu, then click into the top of the column. A pop-up menu will appear for the Assign dest selection. In the pop-up menu, select FFV (Feed-forward amount). FFV now appears at the top of column 6. Repeat this procedure for N1 oper, N1 Arg 1, N1 Arg 2...etc.

2. Fromthe N1 Oper pop-up menu, select SCL1 (Straight Line Approximation).

3. From the column N1 Arg 1 pop-up menu, select Al2 (Analog Input 2).

You have now programmed the ES100 to accept Al2 as its Feed Forward input. The information from this input will be placed into the calculation that the ES100 will use to determine the Manipulated Variable (MV).

By programming the ES100 for Feed Forward as we have demonstrated, you have accomplished the following: ¢ Analog Input 2 signal of 4-20 mA was converted to 0-1.

¢ Use of the FFV (Feed Forward Variable) to calculate the proper output variable so that the ratio of food to steam would be consistent throughout our process.

* Scaling to SCL (Straight-line approximation, column 1), 0-500 Kg/s (N1).

The ES100 is calculating the Feed Forward variable from the food flow of 0-500 kg/s. The food flow is then used to calculate the Feed Forward Variable.

For a graphic view of the program; select [F3:image } Make sure you have column 6 highlighted. It will look like Figure 11.

Fo fAmalog operation image ‘iC | Fi:Move || || || ||F9:option] | || ESC : Exit } fmalog input Feed-forward am ali 7 qj

SCL1 FU

96

Downloaded from www.Manualslib.com manuals search engine