What is Ratio Control Section 4-1

4-1 Whatis Ratio Control

Ratio control usually involves the mixture of two or more ingredients using a very specific mixture (or ratio) where the flow of one ingredient into a process is controlled based on a flow of a second, uncontrolled ingredient. The variable input is generated directly from an external input, or remote set point (RSP).

For example, in a grout color mixing application the two main ingredients, sand and dye, must be mixed in an exact ratio of 100 parts sand to 5 parts dye or a 20:1 ratio. In the example, the sand is the uncontrolled variable (RSP) and flows freely into the process. The dye in turn is delivered to the process in a 20:1 ratio based on the amount of sand entering the system (Figure 1).

Dye

Sand fo A / Hopper B

Conveyor Flow sensor Pump

Se [SF

- Weight meter / ‘ 420 e) Sp ff

In the grout example above, the input to the ES100 from the remote setpoint (Al2) is a 4-20 mA signal generated from a weight meter. To maintain tight control of the mixture to avoid over or under-dyeing, the controller’s primary input is a 4-20 mA signal from a flowmeter (Al1) in the dye injection tube. It is also the PV for the flow of the dye. The control output is directed to a dye flow control pump (AOQ1).

The system operates by taking the remote setpoint value and comparing it to a preprogrammed ratio (Figure 2). The ratioed value is then use to adjust the output to precisely control the flow of dye to maintain grout color consistency.

Flow of dye

Weight of sand

| Ratio K = Flow of dye Ratio K

Weight of sand (kg/s) Figure 2

76

Downloaded from www.Manualslib.com manuals search engine

Page 82 read from a scan by OCR; it may hold reading errors

Operation and Tuning

Section 4-3

4-2 Start-Up Procedure

4-2-1 Wiring

AO1

Al2

The ES100 selected for Ratio control applications must have an optional second input installed. The part number should look like: ES100X-_ __ W_

Awiring diagram for the grout mixing applications appears below (Figure 3). It is typical of most ratio control applications. In our example there are three connections to be made: the dye flow sensor (Al1), the sand scale (Al2), and the dye flow pump AOQ1).

5 Ove. @ :----8----@ (6) CT Input -, O go. cd Power on (5) a supply ©) ee 4 @3) : \ 1 + 1 + \ : @2) | : : = @ | Ol @ ORR @ ® os 4-20 mA @bo ore : * An Oe ae -, $ = 9 cbr eC) Tt = Figure 3

4-3 Operation and Tuning

The first step in setting up a ratio control application is to scale the control inputs. The second step is to input the desired control ratio.

Scaling the Control Inputs

In this example we will set up the controller to scale 4-20 mA signals for each input (Al, Al2). The full scale of the sand scale (Al2) is 0-500 kg/min, the full scale of the dye flow sensor (Al1) is 0-25 kg/min. As an aid to organizing information that will be programmed into the ES100, use the table below.

Input | Item Low End High End Alt Input from Sensor 4 20 Value to be displayed on Front panel of the 0 500 ES100 Al2 Input from Sensor 4 20 Value to be displayed on Front panel of the 0 25 ES100

Program the ES100 as follows:

1. From the ES/TOOLS menu, click on the Setting <offline> icon. 2. From the Setting menu <offline> select the button.

77

Downloaded from www.Manualslib.com manuals search engine

Page 83 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 4-3

3. Select from the Analog operation assignment menu. A pop-up menu appears (Figure 4).

F4 f Analog operation assignment iO

F1:Detai ls] | || F3: Image || F4:Edit | |Fo:option] | F1@:Help || ESC Exit |

2 3 4 5 6, - E -

“ 2a omn nan

Assign dest

Set Analog Operation Details sc. (straight-line approximation)

FNC (broken-line approximation)

AP1 to AP32 Canalog operation parameters)

| NZ Oper

[n2 arg 1

AP1 a]

Figure 4

4. Select SCL (straight-line approximation) | button. The Straight-line approximation menu (Figure 5) will appear. For the grout coloring example, you must complete the table exactly as shown.

Fo Straight-line approximation |

|| || || ||F9:opt ion || F1i@:Help 1 ESC : Exit ]

Set bu number key.

Input 1 -668 6.688 6.468 4.666

Output 1 4.668 4.008 4.968 4.0868

Input 2 1.608 4.825 4.868 4.088

Output 2 5.868 1.606 6.088 6.688 bE

Figure 5

Note: The ES100 uses a Normalizing process to scale low end and high end values from the actual sensor input to the controller. This internal process uses 0-1 as the full scale. As a result, it is necessary to input 0 for the low end and 1 for the high end of the sensor output scales, not 4 and 20 (the actual output range).

Columns 1 and 2 are used for scaling Al2 for display and renormalization after it (Al2) has been ratioed. To enter the values, simply click the cursor on the value in the appropriate place in the table. For this example the table should appear exactly as shown above.

Note: Read the following button definitions. Low end value of the actual sensor input to the controller.

Low end value to be displayed on the front panel of the ES100.

78

Downloaded from www.Manualslib.com manuals search engine

Page 84 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 4-3

High end value of the actual sensor input to the controller.

High end value to be displayed on the front panel of the ES100.

5. Select to return to the Analog operation parameters menu. Setting the Control Ratio

The next step in setting up a ratio control application is to input the control ratio. The mixing ratio must be predetermined by the user. In the grout coloring example, the appropriate ratio is 100 parts of sand to 5 parts dye or 20:1. Follow the steps below to program the controller with the control ratio.

1. From the Analog operation assignment menu, select FtDetails | From the pop-up menu, select AP1 to AP32 (Analog operation parameters).

2. Click on the value across from Analog oper param 1 and enter 0.050. The table should look like Figure 6., f Analog operation parameters |

| || || || ||Fo:option] | F1i@:Help || ESC : Exit ]

Set buy number key.

len log oper param 1 > 6.656 lpmlog oper param 2 > 6.668 lanlog oper param 3 > 6.668 lantog oper param 4 > 6.668 lantog oper param 5 > 6.668 laniog oper param 6 > 6.666 Figure 6

3. Select to escape back to the Analog operation assignment menu.

79

Downloaded from www.Manualslib.com manuals search engine

Page 85 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 4-3

Linking the Control Ratio Program to ES100 Operation

Now that the ration programming is complete. It is necessary to link it to the core program of the ES100 using the Analog operation assignment table. To do this, follow the procedures below.

1. From the Setting menu <offline>menu, select (Figure 7)., Setting Menu <Offline> ‘iO

[ Fi:rile || || || ||F9:option|| || esc:Exit |

| Controller type [ ES1@@P-AA WHO4FE Ver. 2.%* ] }

| Configuration Parameters |

Parameter [ sp conditions | per at PU error| | Control parans | | Output | | Front panel | | Power ON oper | [ever |i | [Communications | | ffechnical params

Program Assignment | Program | | Digital oper | | Analog oper | [File name [RATIO .ES4 ||Comment | | Figure 7

2. From the Analog operation assignment table, double-click on the area intersected by Assign dest and column 6. A pop-up menu appears. Scroll through the menu and double-click on RSP (Remote Setpoint).

3. Double-click on the N1 Oper/column 6 intersection. Scroll through the pop-up menu and select SCL1 (Straight-line approximation).

4. Double-click on the N1 Arg1/column 6 intersection. Double-click on Al2 (Analog Input 2).

5. Double-click on the N2 Oper/column 6 intersection. Select MUL (Multi-ply) from the pop-up menu.

6. Double-click on the N2 Arg 1/column 6 intersection. Select N1 (Argu-ment Result) from the pop-up menu.

7. Double-click on the N1 Arg 2/column 6 intersection. Select AP1 (Analog Parameter 1) from the pop-up menu.

8. Double-click on the N3 Oper/column 6 intersection. Select SCL2 (Straight-line approximation) from the pop-up menu.

9. Double-click on the N3 Arg 1/column 6 intersection. Select N2 (Argu-ment Result from the pop-up menu.

For this example, column 6 should look exactly like the one shown in Figure 8.

80

Downloaded from www.Manualslib.com manuals search engine

Page 86 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 4-3, Analog operation assignment O Fi:Details|| | | FI: Inage || F4: Bait ||Fo:0ption|| F1iG:llelp || Dee :Ex it a 2 a 4 La G

Assign dest | PU 401 - Att STP ENP

MOV MoV END MoV Hou SCL1

Alt MU - Pu AP31 AT2

END END END END END HAUL

- - - - - NL

- - - - - AP4 BND END END END EHD SCLZ - - - - - Nz

EN END END EMI) EMD END

<]

The programming in column 6 reflects the connection of the basic ratio program to the core of the ES100. By performing the steps above, you have accomplished the following:

* Scaling Al1 to SCL (Straight-line approximation, column 1), 0-500 Kg/s (N1). ¢ Al2 (weight of the sand) is multiplied by the ration (20:1) in AP1 (N2).

¢ In the final operand (N3) Al2 was scaled to provide a useable number for display on the front panel of the ES100. However, in order for the ES100 to use the data that Al2 provides, Al2 must be rescaled, or normalized to 0-1. This value is then transferred into the Remote Setpoint function of the ES100 (Figure 9).

Ft Analog operation image KO

| F1:Move || || || ||F9:option || || ESC :Exit |

Table No. : 6

Analog input Remote SP

AIZ 77 SCL1 x APL = - Analog operat SCL2 Ha | -Rsp <<]

Figure 9

81

Downloaded from www.Manualslib.com manuals search engine

Page 87 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 4-3

Al2 is normalized after the ratio has been applied to the input. The normalized ratio is then used as the Remote Setpoint for the ES100 so that it can mix the proper amount of dye with the sand.

You have now completed all programming for ratio control process. Proceed to Autotuning.

4-4 Autotuning Note: The ES100 must be connected.

The autotune feature uses a method of tuning similar to a limit cycle, which is described in Section 1, Cascade Control. When autotuning is activated it will be indicated by a blinking yellow LED on the front panel of the ES100.

1. From the ES/TOOLS menu, select the Check Control icon. 2. Select from the Check control menu (Figure 10). Fe Check control Z|

F1:Run qq F2:Paran | [Fa:status | ra :connanal [F9:opt ion || |{ escrexit |

68/26/94 758.48

Clear data 87:59:42

Move point Monitor rend Setting J/SP PU 74.63

Trend mode HU 190.80

Exec A.T.

PY Interval 2 Second Canc A.T

Draw mode Clear + draw

Change SP

TEEPE

6:82:08 6:46:08 4:16:08

Figure 10

3. Select from the new vertical menu on the left side of the screen (Figure 11).

hRaNVYVTS, Check control Unit No.88 lal [ Fi:run || F2:Param |[F3:status | F4:Conmanal |F9:opt ion] | |[esc:exit | 16:86:55 Monitor : Py 58.48 Hola | Py 2 Second Draw mode (Clear + draw -5e 2:62:08 0:86:08 0:10:00 Figure 11

4. Select to return to the Check control menu.

5. From the vertical menu on the left side of the screen, select [Exec AT. |

A new pop-up window will appear (Figure 12). Enter the number of the PID bank you wish to Autotune.

82

Downloaded from www.Manualslib.com manuals search engine

Page 88 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 4-3

Et Check control Unit No.a@ KM | Fi:Run || F2:Param | |F3:status | F4:Conmandl [Fo :option| | || ESC : Exit | Clear data mecca 188

Move point Monitor tr rend Setting SP Py 78

Trend mode ad 48) [PID set vo. > 2 Exec A.T. [Esc :Cance! }| ENT :OK | Interva 2 Second

Draw mode Clear + draw Change SP

OEEEEEREEE

6:62:68 4:66:68 6:16:08

Figure 12

7. Select [ENT: OK }. The controller will now autotune. Do Not interrupt or stop this process. The controller will have completed autotuning when the yellow ‘AT’ light stops blinking on the front panel of the ES100.

4-4-1 Fuzzy Logic Fine Tuning

If the performance of the controller is not satisfactory after autotuning, you may improve the performance of the ES100 by using the Fuzzy Logic Fine Tune. Follow these steps to get to the Fine Tune portion of the ES/TOOLS program.

Start controlling your process with the ES100 by placing it in the RUN mode. 1. From the ES/TOOLS menu, select the Check control icon. 2. From the Check control menu, select [Fi:Run }

3. From the vertical menu on the left side of the screen, select 1. From the ES/TOOLS Menu select the Check control icon.

83

Downloaded from www.Manualslib.com manuals search engine

Page 89 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 4-3

2. Select from the menu on the left side of the screen (Figure 13)., Check control i

Fi:Run || F2:Param | |F3:status | Fa :command] |[F9:opt ion || || esc:excit |

68/29/94 758.8 16:68:33

Clear data

Move point rend Setting

Trend mode

Exec A.T.

ypu

Interval 2 Second

Draw mode

Clear + draw

Change SP

CEEEEE REE

6:62:68 6:66:60 6:16:66

Figure 13 3. A Pop-Up window will appear to confirm the PID set that you are using.

4. Enter the appropriate PID set number and select (ENT: OK] a new pop-up window will appear Figure 14.

Clear + draw

Check control ik | Fi:Run || F2:Param | [F3:status | F4:Commana| |F9:opt ion || || esc:Exit | a ah f é - T va Clear data toe. F.T. required level setting Overshoot Moni rend Setting ISP Py me Exec A.T. | Rspons lunting 2 Se Draw ||ESC:Cance1| | ENT:0x |

Change SP

6:62:66 6:66:66 6:16:68

Figure 14

5. There are five different levels of response that you can initiate using Fuzzy Logic Fine Tuning. Each triangle represents one level of strength. The more triangles you select the greater the reaction will be from the Fine Tuning effect of Fuzzy Logic. You can select one parameter (as is shown) or a maximum of two parameters, such as Response/Hunting, or Overshoot/Hunting. Use the keyboard cursor controls to move the red

84

Downloaded from www.Manualslib.com manuals search engine

Page 90 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 4-3 inner circle around the inside of the outer circle. The arrowheads will automatically fill in based on the position of the red circle.

6. Select after you have selected the level of corrective action you require.

7. ES/TOOLS will prompt you to execute fine tuning, select LENT:OK | Repeat Fuzzy Logic Fine Tuning as necessary to achieve optimum performance.

You have now completed tuning your ES100 for Ratio Control.