The text of a manual · part 7 of 12
Model ES100 Process Controller ESTOOLS Software Programming Manual and Application Road Map, pages 61 to 70
Pages 61 to 70 of 114
The original document is the PDF (2.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron ES100X-AAWH01FE
Page 61
Definition of Heat/Cool Control Section 3-1
3-1-1
56
Dead Band and Overlap Bands
A dead band can be defined as a range of temperature in which there is no controlling action taken by the temperature controller.
In other words, for a predefined temperature range, neither the cooling output nor the heating output will be activated. You can modify the ES100 so that its output characteristics reflects Figure 7. An advantage of the dead band is that it helps save on energy costs.
A
Dead Band 100% v
A02 Cooling Output
| 50%
0% Figure 7 OVERLAP BAND
Greater stability and control of the process can be achieved by providing an overlapping band as shown below. In this example, the controller will be ac-tively controlling the temperature of your process at all times. This method of control will require more energy/material to control your process. Because of the overlap band control the accuracy of the controller on the process can be improved (Figure 8).
A A 100% Overlap band ov, Ao2 4 Rot Cooling | Heating Output | | ' Output > MV 0% 50% 100% Figure 8
Downloaded from www.Manualslib.com manuals search engine
Page 62
Setting Manipulated Variable for Process Operation Section 3-2
3-1-2 Start Up Procedure
Note: Heat/cool control can be performed with all standard models of the ES100 except the Valve Positioning (ES100_-RRP- - - -) models.
3-1-3 System Configuration
Alt = Chemical (O Tem erature Ao" reaction Sensor autoclave (RTD) y Heat exchanger
C ae hy Steam
Sh Cooling water © Figure 9
Figure 9 depicts how an ES100 connected in a typical heat/cool application, in this example a chemical reaction autoclave. The valves for heating and cooling are being controlled by 4-20 mA signals from the ES100. A Platinum Resistance Thermometer is being used to measure the temperature within the autoclave itself. Analog Output 1 is the heating output and Analog Output 2 is the cooling output.
After completing the basic wiring, you need to program the ES100 to operate the heat/cool process.
3-2 Setting Manipulated Variable for Process Operation
Before you can tune the controller you must first enter parameters for the operations listed. Proceed in the order of the listed operations.
* Setting the Dead Band
* Setting the Overlap Band
* Setting Cooling Coefficient
57
Downloaded from www.Manualslib.com manuals search engine
Page 63
Setting Manipulated Variable for Process Operation Section 3-2
3-2-1 Setting a Dead Band 1. From the ES/TOOLS menu, select the Setting <Offline> icon. The Setting Menu Offline appears. 2. Select the button. The Analog operation assignment menu appears. 3. From within the Analog operation assignment menu (Figure 10), select | Fi: Details |. The Set Analog Operation Details pop-up menu appears., - - - Analog operation assignment ‘C Fi:Detai Isl | || F3: Image || F4:Edit ||F9:option|| F1i8:Help || ESC: Exit | 4 5 6 7 8 3 lassign dest || A03 STP FFV PU2 - - MoU Nov SCL1i Mov END END PY AP31 AIL al2 - - END END FNC1 END END END - - Ni - - - Figure 10
4. From the Set Analog Operation Details pop-up menu, select AP1 to AP32 (Analog Operation Parameters) in Figure 11., fAmalog operation assignment | F1:Details| | || F3:Inage || F4:Edit ||F9:option]| Fi@:Help || esc:Exit ] 1 2 3 4 5 6
Assign dest
Set Analog Operation Details i - N14 Oper i=
N14 Arg 1 kc (straight-line approximation)
N14 Arg 2
FNC (broken-line approximation) ~~ |], §..
[Nas Oper AP1 to AP32 (analog operation parameters)
[Nas Arg 1
N1S Arg 2
|
Figure 11
58
Downloaded from www.Manualslib.com manuals search engine
Page 64
Setting Manipulated Variable for Process Operation Section 3-2
5.
From the Analog operation parameters menu (Figure 12), scroll down until you see Anlog oper param 32 | ang select it. Enter the deadband value as a percent of full scale. For example, if you would like a 10% dead band, key in a value of 0.100. This will make a 10% of full scale deadband in your process (Figure 13).
FA, - fmalog operation parameters Saas)
| || || || |[Fo:option|| Fia:Heip || esc:Exit |
Set by number key.
laniog oper paran 27 > 8.088 laniog oper paran 28 > 8.088 laniog oper param 29 > 6.888 lantog oper param 38 > 4.688 laniog oper param 31 > 4.568 lantog oper param 32 > 8.108
Figure 13
3-2-2 Setting an Overlap Band
To set up your controller with the overlap band simply place a ( - ) symbol in front of the percentage of overlap needed in the Analog operation parameters menu. To this follow the steps below.
1.
Downloaded from www.Manualslib.com manuals search engine
From the ES/TOOLS menu, select the Setting <Offline> icon. The Setting Menu Offline appears.
Select the button. The Analog operation assignment menu appears. From within the Analog operation assignment menu, select
| Fi: Details |. The Set Analog Operation Details pop-up menu appears.
From the Set Analog Operation Details pop-up menu, select AP1 to AP32 (Analog Operation Parameters).
From the Analog operation parameters menu, scroll down until you see |Anlog oper param 32 | ang select it. Enter the overlap band value as a negative (-) percent of full scale. For example, if you would like a 10% overlap band, key in a value of -0.100 (Figure 14).
FA, fmalog operation parameters Saas)
| || || || |[Fo:option]| F1a:Heip || esc:Exit |
Set by number key.
lan log oper param 27 > 6.000 lan log oper param 28 > 6.600 laniog oper param 29 > 6.608 lpniog oper param 34 > 6.0600 aniog oper param 31 > 6.566 laniog oper param 32 > p28 . 148 Figure 14
59
Page 65
Setting Manipulated Variable for Process Operation Section 3-2
3-2-3 Setting the Cooling Coefficient
The cooling coefficient enables the controller to compensate for differences between the heating and cooling capabilities of a system. In heat/cool control, the cooling process is controlled by changing only the proportional band. The proportional band is defined as the range of temperature values above and below the setpoint, where control action is fully ON below the band, and fully OFF above the band and proportional within the band (Figure 15).
Fully OFF} - ----------------4---
SP Proportional Fully ON F000
Figure 15
You should adjust the cooling coefficient when there is a difference between the heating and cooling characteristics of the process. If the cooler is more powerful than the heater, set the cooling coefficient to less than 1 (from 0.99 to 0.01). If the heater is more powerful than the cooler, set the cooling coefficient to greater than 1 (to a maximum of 99.99). If both are about equal, no change is necessary to the cooling coefficient.
In the ES100 the cooling coefficient is set at the factory to a default of 1. With the cooling coefficient set to 1 the proportional band of the cooling output is exactly the same value as the heating output proportional band.
1. To set the cooling coefficient, from the Setting Menu <Offline> select the button. The pop-up menu Control parameters appears (Figure 16). 2. From the Control parameters menu, select [Other items } 2 ES control parameters menu ea yl y II ||[Fa:option] | |[uscrexie |
Control parameters
PID control params } Fuzzy param ! PID set select |
Figure 16
3. From the Other items of control menu, select Cooling coefficn’t | ang key in the appropriate value for your system (Figure 17)., Other items of control CI
| || || || ||F9:option || F1i8:Help || ESC: Exit |
Set by number key.
[Coot ing coeff icn’ t S> 1.08
[on/OFF control hyst > 4.26 [“FS]
[Manua 1 reset > 56.6 [4]
[p irect“reverse > Reverse operation Figure 17
60
Downloaded from www.Manualslib.com manuals search engine
Page 66
Setting Manipulated Variable for Process Completion Section 3-3
3-3 Setting Manipulated Variable for Process Completion
Before you can tune the controller you must set it up for how you want the manipulated variable or controller output to respond when the process it is controlling has been completed or when you take the controller out of RUN mode and need to halt any control action from the controller. How you set the controller up depends on whether or not you desire no output or continued output when the process is complete.
3-3-1 Manipulated Variable When NO OUTPUT is Desired
The process for setting the manipulated variable at operation stop is different for dead band and overlap band settings. Refer to the appropriate procedure below.
When Using a Dead Band
VERSION 1 CONTROLLERS
Note: The setup for NO OUTPUT on process stop is different depending on whether you have an ES100 Version 1 (the part number of Version 1 Controllers ends with the letter “-E”) or Version 2.
Because the factory default setting for Version 1 is 0% (heating OFF; cooling ON 100%) you must change this setting to set the controller for NO OUTPUT at process stop (Figure 18).
A A 100%
A02 A01
Cooling Heating
Output | Output
> MV 0% 50% 100% Figure 18
1. From the Setting menu <Offline>select the button. The Analog operation assignment menu appears.
2. Fromthe Analog operation assignment menu, select | Fi: Details |. From the new pop-up menu, select AP1 to AP32 (analog operation parameters).
3. From the Analog operation parameters menu, scroll down to |Anlog oper param 31 | and select it. If you have not changed the default dead band value, then key in 0.500. If you have changed the default dead band value, then key in the mid-point value of the dead band expressed in terms of a percent. For example, if the mid-point of your dead band is 40%, key in 0.400.
4. Select LESC: Exit] You will be returned to the Analog operation assignment menu.
5. In the Analog operation assignment menu, scroll down so that the N11 Oper button appears at the top of the table (Figure 19).
61
Downloaded from www.Manualslib.com manuals search engine
Page 67
Setting Manipulated Variable for Process Completion Section 3-3
6. In the Analog operation assignment menu (Figure 20), you must enter the values exactly as shown in columns 1 and 2 starting at and continuing through to (shaded columns).
7. When all values have been entered, select [ESC: Exit}. Now proceed to Autotuning in this section., finalog operation assignment - FirDetails| | || Fa: nage || F4: Edit | |Fo:0pt ion] | P14: lleLp || nec rex it 1 2 a 4 oS G
Hil Oper ll END 3cLi SCLL END EHD END
Nii arg 4 b - MU MU - - - Hii arg z_ - (||| I- - - - - -
||
H1z Oper END SLL SLL END END END EE [miz are 1 lh | |- nin [iz | - - a
END SLH SLH END END END EE
- Niz N1Z - - -
- &.6 - - -
END hUL HUL END END END
- N18 M13 - - -
- N13 N13 - - -
EMD END END END END END
Figure 20
FOR VERSION 2 CONTROLLERS
Note: The setup for NO OUTPUT on process stop is different depending on whether you have an ES100 Version 1 (the part number of Version 1 Controllers ends with the letter “-E”) or Version 2.
The factory default setting for Version 2 Controllers is 50%. If you have not made any changes to the default dead band no changes are necessary. If you have changed the dead band settings, follow the steps below.
1. From the Setting menu <Offline>select the button. The Analog operation assignment menu appears.
2. Fromthe Analog operation assignment menu, select | Fi: Details |. From the new pop-up menu, select AP1 to AP32 (analog operation parameters).
3. From the Analog operation parameters menu, scroll down to
|Anlog oper param 31 | ang select it. Key in the mid-point value of your dead band expressed in terms of a percent. For example, if the mid-point of your dead band is 40%, key in 0.400.
4. Select ESC: Exit] Now proceed to Autotuning in this section.
62
Downloaded from www.Manualslib.com manuals search engine
Page 68
Setting Manipulated Variable for Process Completion Section 3-3
When Using a Overlap Band
Note:
Note:
If you have programmed an overlap band into the controller, and you want all heating and cooling action turned OFF at the completion of your process, you must make the following changes to the ES100 program.
If you want to maintain some heating or cooling action at the completion of your process, refer to Maintaining Control Action at Operation Stop later in this section.
VERSION 1 CONTROLLERS
The setup for NO OUTPUT on process stop is different depending on whether you have an ES100 Version 1 (the part number of Version 1 Controllers ends with the letter “-E”) or Version 2.
1. From the Setting menu <Offline>select the button. The Analog operation assignment menu appears.
2. From the Analog operation assignment menu, select [Fi: Details } From the new pop-up menu, select AP1 to AP32 (analog operation parameters).
3. From the Analog operation parameters menu (Figure 21), scroll down to
|Anlog oper param 31 | and select it. Key in the value -1.000., F4 f Analog operation parameters O
| || || || ||Fo:option || F186:Help || ESC: Exit |
Set by number key.
lanlog oper param 27 > 6.668 iH lanlog oper param 23 > 6.660 i lanlog oper param 29 > 6.666 i lantog oper param 38 > 6.668 BH lantog oper param 31 > -1.660 EH lantog oper param 32 > 6.600 = Figure 21
4. Select to return to the Analog operation assignment menu.
63
Downloaded from www.Manualslib.com manuals search engine
Page 69
Setting Manipulated Variable for Process Completion
Section 3-3
5. In the Analog operation assignment menu (Figure 22), you must enter the values exactly as shown in columns 1 and 2 starting at and continuing through to (shaded columns).
finalog operation assignment
“ iY
FirDetai isl |
'Exit ficion aot I] nia over [| Nii Arg 1 b mia are 2 (|
Niz Oper miz are 1__||
|| Fa: nage || F4: Edit | |Fo:0pt ion] | P14: lleLp || nec 1 2 a 4 La G FU a01 Anz ana STP - END ScLi SCLL END END END - MU MU - - - END SLL SLL END END END - N11 N12 - - - - 1.6 6.8 - - - END SLH SLH END END END - Niz N1z - - - - 4.6 6.3 - - - END fUL MUL END END END - N16 MiB - - - - Wis N13 - - - EMD END END EMD EMD END Figure 22
6. When all the values have been entered as shown select |ESC: Exit |, 7. Select Fi: Details] From the pop-up menu select SCL (straight-line approximation), Figure 23.
fAmalog operation assignment
~
|| F3:Inage || F4:Edit ||F9:option]| Fi@:Help || esc:Exit ]
Assign dest
N14 Oper
Set Analog Operation Details
N14 Arg 1 kc (straight-line approximation)
N14 Arg Z FNC (broken-line approximation)
[Nas Oper
AP1 to AP3Z (analog operation parameters)
[Nas Arg 1
N1S Arg 2
|
64
Downloaded from www.Manualslib.com manuals search engine
Figure 23
Page 70
Setting Manipulated Variable for Process Completion Section 3-3
8. Select the button (Figure 24). In column one enter the value
-0.001.
a Straight-line approximation a | || || || | |Fo:option]| F1a:He1p I ESC Exit | Set by number key.
1 2 3 4 le, 6.661 ||6.000 6.008 6.008 Output 1 4.960 46.900 6.008 4.660 4.668 6.608 6.668 6.666 Output 2 4.668 6.688 6.968 6.666 Figure 24
9. Select ESC: Exit}
You have now completed the steps necessary to configure your ES100 for NO OUTPUT at process completion. You may now proceed to Autotuning.
VERSION 2 CONTROLLERS
Note: The setup for NO OUTPUT on process stop is different depending on whether you have an ES100 Version 1 (the part number of Version 1 Controllers ends with the letter “-E”) or Version 2.
1. From the Setting menu <Offline>select the button. The Analog operation assignment menu appears.
2. From the Analog operation assignment menu, select [Fi: Details } From the new pop-up menu, select AP1 to AP32 (analog operation parameters).
3. From the Analog operation parameters menu (Figure 25), scroll down to
|Anlog oper param 31 | and select it. Key in the value -1.000., F4 f Analog operation parameters O
| || || || ||Fo:option|| F18:Help || ESC: Exit |
Set by number key.
lanlog oper param 27 > 46.668 laniog oper param 23 > 4.668 laniog oper param 29 > 46.668 lantog oper param 38 > 6.668 lantog oper param 31 > -1.660 lantog oper param 32 > 6.600 Figure 25
4. Select to return to the Analog operation assignment menu.
You have now completed the steps necessary to configure your ES100 for NO OUTPUT at process completion. You may now proceed to Autotuning.
65