F150-3 Vision Sensor Setup Manual: SECTION 6 Troubleshooting

Pages 70 to 73 of 96, from F150-3 Vision Sensor Setup Manual

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron F150 and Omron F150-S1A

Page 70

Z141-E1-03.book Page 55 Monday, July 24, 2006 5:16 PM

SECTION 6 Troubleshooting This section lists the errors that may occur, along with their probable causes and countermeasure.

6-1

Connection Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

56

6-2

Errors during Menu Operation . . . . . . . . . . . . . . . . . . . .

56

6-3

Terminal Block Errors. . . . . . . . . . . . . . . . . . . . . . . . . . .

56

6-4

RS-232C Communications Errors. . . . . . . . . . . . . . . . . .

57

6-5

Two-camera Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

57

6-6

LED Indicators (for F150-C10E-3-DRT) . . . . . . . . . . . .

58

55

Page 71

Z141-E1-03.book Page 56 Monday, July 24, 2006 5:16 PM

Section 6-1

Connection Errors

6-1

Connection Errors Problem

Probable cause

The POWER indicator is not lit.

The Power Supply is not connected properly.

The Monitor is blank.

The power to the Monitor is not ON.

The supply voltage is not 24 VDC +10%/–15%. The Monitor Cable is not connected properly. The Monitor is malfunctioning. The power supply capacity is insufficient for the Monitor.

Cannot make key inputs from the Console.

The Console Cable is not correctly connected.

Camera images do not appear on the screen (for Cameras with Light Source).

The Camera Cable is not correctly connected. The lighting cable is not properly connected to the Camera.

The lens cap has not been removed. Camera images do not appear on the screen (when a The Camera Cable is not properly connected. normal CCTV lens and lightThe lens diaphragm is opened or closed too far. ing is used). The shutter speed is not suitable. The lighting method is not suitable. The indicators do not turn ON The lighting cable is not correctly connected to the Camera. (for Cameras with Light Source). There is no power supply to the F150. The DIP switches on Intelligent Light Sources are not set correctly. When using the Two-camera Unit, set the Intelligent Light Source connected to Camera 0 to 0, and set the Intelligent Light Source connected to Camera 1 to 1. The Monitor image is not clear.

There is electrical noise entering from the power supply or cables. The Monitor Cable is not correctly connected.

6-2

Errors during Menu Operation Problem

Probable cause

The measurement results are not displayed on the Monitor.

The F150 is not in Monitor or Run mode.

6-3

Terminal Block Errors Problem

Trigger signals (input signals) are not received.

Probable cause The cables are not correctly wired. The signal line is disconnected. The F150 is not in Monitor or Run mode.

56

Page 72

Z141-E1-03.book Page 57 Monday, July 24, 2006 5:16 PM

Section 6-4

RS-232C Communications Errors Problem Signals cannot be output externally.

Probable cause The trigger signal has not been input. The cables are not correctly wired. The signal line is disconnected. The F150 is not in Run mode.

6-4

RS-232C Communications Errors Problem

No communications are possible.

Probable cause The cables are not correctly wired. The communications specifications do not match those of the external device. The communications mode was not selected under System/Communications settings. Select Normal, Host link, or Menu operations under RS-232C/Operating mode.

The Unit operates well initially, but after a while there is no response from the F150.

The reception buffer on the external device (e.g., computer) is full. Check that settings allow the data to be properly received.

Cannot perform menu operations via RS-232C.

The communications mode was not selected as System/Communications settings/Menu operations.

6-5

Two-camera Unit Problem

The LED indicator is not lit.

Probable cause The power supply is not connected correctly. The supply voltage has dropped below the specified level (24 VDC +10%/–15%). The Two-camera Unit is not connected to the F150.

57

Page 73

Z141-E1-03.book Page 58 Monday, July 24, 2006 5:16 PM

LED Indicators (for F150-C10E-3-DRT)

6-6

Section 6-6

LED Indicators (for F150-C10E-3-DRT)

Indicator Status

Condition

Countermeasure

MS

NS

Lit green

Lit green

Remote I/O communications in progress.

Communications are operating normally.

OFF

Node number duplication check in progress.

Check for the following problems and restart the F150.

Flashing green

Waiting for connection to be established by Master.

• Are the baud rate settings the same on the Master and F150? • Are the cable lengths (trunk and branch lines) within specifications? • Are any cables loose or broken? • Is there a terminator on each end of the trunk line? • Is there excessive noise in the network?

Lit red

Node number duplication

Change the node number settings to eliminate the duplication and then restart the entire CompoBus/D network.

Bus off occurred. (Communications stopped due to excessive data errors.)

Check for the following problems and restart the F150. • Are the baud rate settings the same on the Master and F150? • Are the cable lengths (trunk and branch lines) within specifications? • Are any cables loose or broken? • Is there a terminator on each end of the trunk line? • Is there excessive noise in the network?

Flashing red

Communications timeout occurred.

Lit red

OFF

Watchdog timer error occurred in the F150.

The F150 is faulty. Replace the F150.

Flashing red

OFF

Incorrect setting on the DIP switch or elsewhere.

Check the switch settings and restart the F150.