Page 62
Z141-E1-03.book Page 47 Monday, July 24, 2006 5:16 PM
Section 5-4
Connector Pin Allocation
5-4
Connector Pin Allocation
Shield
Name
Function
Color
V–
Power supply line (–)
CAN L
Communications data (Low)
Black Blue
Shield
Shield
---
CAN H
Communications data (High)
White
V+
Power supply line (+)
Red
Refer to the CompoBus/D (DeviceNet) Operation Manual for details on assembling a communications cable.
Note
1.
Turn OFF the power supply before connecting or disconnecting the cable. Peripheral devices may be damaged if the cable is connected or disconnected with the power ON.
2.
Securely tighten the connector screws.
47
Page 63
Z141-E1-03.book Page 48 Monday, July 24, 2006 5:16 PM
Section 5-5
LED Indicators
5-5
LED Indicators The status of CompoBus/D communications is indicated by the MS and NS indicators.
MS (Module Status) Indicator The MS indicator shows the status of node (F150) itself. The indicator will be lit green when the F150 is operating normally.
NS (Network Status) Indicator The NS indicator shows the status of network. The indicator will be lit green when the network is operating normally. Note The MS and NS indicators are lit in green or red. The status of these indicators (lit, flashing, or not lit) can be used to determine what error has occurred.
→ p. 58
5-6
Multi-vendor Applications Use the Vision Sensor’s specifications as well as the Device Protocol and Object Mounting information shown in the following tables when the F150-C10E-3-DRT is connected to another company’s Master.
Device Protocol General data Compatible DeviceNet Specifications Vendor name
OMRON Corporation, vendor ID = 47
Device type
Generic, protocol number = 0
Product code Network current consumption Physical conformance Connector type data Physical insulation
205 55 mA max. Open plug Yes
Supported indicators
Module, Network
MAC ID setting
DIP switch
Default MAC ID
0
Baud rate setting
DIP switch
Supported baud rates
125K bps, 250K bps, and 500K bps
Communicati Predefined Master/Slave connecons data tion set
48
Volume I - Release 2.0 Volume II - Release 2.0
Group 2 only server
Dynamic connection support (UCMM)
No
Explicit message fragmentation support
Yes
Page 64
Z141-E1-03.book Page 49 Monday, July 24, 2006 5:16 PM
Section 5-6
Multi-vendor Applications
Object Mounting Identity Object (0x01) Object class
Attribute
Not supported
Service
Not supported
Item Object instance
ID content
Attribute
Get (read)
Set (write)
1 Vendor
Yes
No
47
2 Product type
Yes
No
0
3 Product code
Yes
No
205
4 Revision
Yes
No
2.1
5 Status (bits supported)
Yes
No
Bit 0 and bit 10
6 Serial number
Yes
No
Unique for each Unit
7 Product name
Yes
No
F150-C10E-3
8 State
No
No
---
Item
DeviceNet service
Service
Object instance
Value
Parameter option
05 Reset
No
0E Get_Attribute_Single
No
Message Router Object (0x02) Object class Object instance
Attribute
Not supported
Service
Not supported
Attribute
Not supported
Service
Not supported
Vendor specification addition
No
DeviceNet Object (0x03) Item Object instance
Attribute
Item Object class
Service
ID content 1 Revision
Get (read)
Set (write)
Yes
No
02 (hexadecimal)
DeviceNet service 0E Get Attribute Single
Value
Parameter option No
49
Page 65
Z141-E1-03.book Page 50 Monday, July 24, 2006 5:16 PM
Section 5-6
Multi-vendor Applications Item Object instance
ID content
Attribute
Get (read)
Set (write)
1 MAC ID
Yes
No
2 Baud rate
Yes
No
---
3 BOI
Yes
No
00 (hexadecimal)
Yes
No
---
5 Allocation information
Yes
No
---
6 MAC ID switch changed
No
No
---
7 Baud rate switch changed
No
No
---
8 MAC ID switch value
No
No
---
9 Baud rate switch value
No
No
---
DeviceNet service
Service
---
4 Bus Off counter
Item Object instance
Value
Parameter option
0E Get_Attribute_Single
No
4B Allocate_Master/ Slave_Connection_Set
No
4C Release_Master/ Slave_Connection_Set
No
Assembly Object (0x04) Object class
Item
Attribute
Not supported
Service
Not supported
Section
Object instance 1
Information
Instance type
Item Object Attribute instance 1
Item Object instance 1
50
Service
Max. number of instances
Static I/O
1
Content
Get (read)
Set (write)
Value
1 Number of Members in List No
No
2 Members List
No
No
---
3 Data
Yes
Yes
---
DeviceNet service
---
Parameter option
0E Get_Attribute_Single
No
10 Set_Attribute_Single
No
Page 66
Z141-E1-03.book Page 51 Monday, July 24, 2006 5:16 PM
Section 5-6
Multi-vendor Applications Connection Object (0x05) Object class
Attribute
Not supported
Service
Not supported
Max. number of active connections
1
Item
Section
Object instance 1
Information
Max. number of instances
Instance type
Explicit Message
Production trigger
Cyclic
---
Transport type
Server
---
Transport class
3
---
Item Attribute Object instance 1
ID content
1
Get (read)
Set (write)
Value
1 State
Yes
No
---
2 Instance type
Yes
No
00 (hexadecimal)
3 Transport class trigger
Yes
No
83 (hexadecimal)
4 Produced connection ID
Yes
No
---
5 Consumed connection ID
Yes
No
---
6 Initial comm. characteristics
Yes
No
21 (hexadecimal)
7 Produced connection size
Yes
No
FE00 (hexadecimal)
8 Consumed connection size
Yes
No
FE00 (hexadecimal)
9 Expected packet rate
Yes
Yes
---
12 Watchdog time-out action
Yes
No
One of 01, 03
13 Produced connection path length
Yes
No
0000
14 Produced connection path
Yes
No
---
15 Consumed connection path length
Yes
No
0000
16 Consumed connection path
Yes
No
---
17 Production inhibit time
Yes
No
---
51
Page 67
Z141-E1-03.book Page 52 Monday, July 24, 2006 5:16 PM
Section 5-6
Multi-vendor Applications Item Object instance 1
DeviceNet service
Service
Item Object instance 2
52
No
0E Get_Attribute_Single
No
10 Set_Attribute_Single
No
Section Instance type
Information Polled I/O
Max. number of instances 1
Production trigger Cyclic
---
Transport type
Server
---
Transport class
2
---
Item Object instance 2
Parameter option
05 Reset
ID content
Attribute 1 State
Get Set (read) (write) Yes
No
Value ---
2 Instance type
Yes
No
01 (hexadecimal)
3 Transport class trigger
Yes
No
82 (hexadecimal)
4 Produced connection ID
Yes
No
---
5 Consumed connection ID
Yes
No
---
6 Initial comm. character- Yes istics
No
01 (hexadecimal)
7 Produced connection size
Yes
No
See note 1.
8 Consumed connection size
Yes
No
See note 2.
9 Expected packet rate
Yes
Yes
---
12 Watchdog time-out action
Yes
No
00
13 Produced connection path length
Yes
No
14 Produced connection path
Yes
0000 (no inputs) 0600 (with inputs)
No
No data (no inputs) 20_04_24_01_ 30_03 (with inputs)
15 Consumed connection Yes path length
No
16 Consumed connection Yes path
No
17 Production inhibit time Yes
No
0000 (no outputs) 0600 (with outputs) No data (no outputs) 20_04_24_01_ 30_03 (with outputs) 00
Page 68
Z141-E1-03.book Page 53 Monday, July 24, 2006 5:16 PM
Section 5-6
Multi-vendor Applications Note
1.
Indicates the number of input bytes used by the Slave. The leftmost and rightmost bytes are reversed. (For example, the produced connection size = 4000 when 64 bytes are used.)
2.
Indicates the number of output bytes used by the Slave. The leftmost and rightmost bytes are reversed. (For example, the consumed connection size = 4000 when 64 bytes are used.)
Item Object instance 2
DeviceNet service
Service
05 Reset
Parameter option No
0E Get_Attribute_Single
No
10 Set_Attribute_Single
No
Item
Section
Object instance 3
Instance type
Bit strobed I/O
Information
1
Max. number of instances
Production trigger
Cyclic
---
Transport type
Server
---
Transport class
2
---
53
Page 69
Z141-E1-03.book Page 54 Monday, July 24, 2006 5:16 PM
Section 5-6
Multi-vendor Applications
Item Object instance 3
ID content
Get (read)
Set (write)
Yes
No
---
2 Instance type
Yes
No
01 (hexadecimal)
3 Transport class trigger
Yes
No
82 (hexadecimal)
Attribute 1 State
Value
4 Produced connection ID
Yes
No
---
5 Consumed connection ID
Yes
No
---
6 Initial comm. characteristics
Yes
No
02 (hexadecimal)
7 Produced connection size
Yes
No
See note.
8 Consumed connection size
Yes
No
0800 (hexadecimal)
9 Expected packet rate
Yes
Yes
---
12 Watchdog time-out action
Yes
No
00
13 Produced connection path length
Yes
No
0600
14 Produced connection path
Yes
No
20_04_24_01_ 30_03
15 Consumed connection path length
Yes
No
0000
16 Consumed connection path
Yes
No
No data
17 Production inhibit time
Yes
No
00
Note Indicates the number of input bytes used by the Slave. The leftmost and rightmost bytes are reversed. (For example, the produced connection size = 0800 when 8 bytes are used.) With the bit-strobed interface, the maximum produced connection size is 8 bytes. A produced connection size of 8 bytes (0800) will be used if a higher value has been set for the number of input bytes with the user MPU; the set value will be used if it is 8 bytes or less.
Item Object instance 3
54
Service
DeviceNet service 05 Reset
Parameter option No
0E Get_Attribute_Single
No
10 Set_Attribute_Single
No