The text of a manual · part 8 of 15
F150-3 Vision Sensor Setup Manual: SECTION 3 Terminal Blocks
Pages 44 to 49 of 96, from F150-3 Vision Sensor Setup Manual
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron F150 and Omron F150-S1A
Page 44
Z141-E1-03.book Page 29 Monday, July 24, 2006 5:16 PM
SECTION 3 Terminal Blocks This section describes how to connect the terminal blocks. The F150 can input measurement triggers and output measurement results through these terminal blocks. For details on setting communications specifications and I/O formats, refer to the relevant operation manuals.
3-1
Crimp Terminals and Cables . . . . . . . . . . . . . . . . . . . . . .
30
3-2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
3-3
Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31
29
Page 45
Z141-E1-03.book Page 30 Monday, July 24, 2006 5:16 PM
Section 3-1
Crimp Terminals and Cables
3-1
Crimp Terminals and Cables The terminal block uses M3 terminal screws. Use appropriate crimp terminals for M3 screws, as shown below. Tighten the screws to a torque of between 0.5 and 0.6 N⋅m. Confirm that wiring and tightening have been done properly. Use a cable length not exceeding 30 m.
!Caution Cover the terminal blocks with the Terminal Block Protection Covers after wiring. Forked
Round
6.2 mm max.
6.2 mm max.
Applicable wire size: Insulated wire of 1.31 to 1.65 mm2 (AWG16 to AWG15)
3-2
Specifications !Caution Use a DC power supply with a safe extra low-voltage circuit that prevents occurrences of high voltages in the power supplies for the terminal blocks.
Input Specifications Item Input voltage
F150-C10E-3, F150-C10E-3-DRT (NPN model) 12 to 24 VDC ±10%
ON current
5 to 15 mA
ON voltage
8.8 V max.
OFF current
0.1 mA max.
OFF voltage
4.5 V min.
ON delay
RESET input:
10 ms max.
Others:
0.5 ms max.
RESET input:
15 ms max.
Others:
0.7 ms max.
OFF delay Internal circuits
30
F150-C15E-3 (PNP model)
COM IN
Input terminal
Input terminal
COM IN
Page 46
Z141-E1-03.book Page 31 Monday, July 24, 2006 5:16 PM
Section 3-3
Terminals Output Specifications Item
F150-C10E-3, F150-C10E-3-DRT (NPN model)
Output voltage
12 to 24 VDC ±10%
Load current
45 mA max.
ON residual voltage
2 V max.
OFF leakage current
0.1 mA max.
F150-C15E-3 (PNP model)
Internal circuits Output terminal COM OUT Load Load COM OUT
Output terminal
Note If UL recognition is required, use a UL class II power supply.
3-3
Terminals The terminals on the terminal blocks are assigned as shown in the following diagrams and tables.
F150-C10E-3 F150-C15E-3 Top terminals
Bottom terminals
31
Page 47
Z141-E1-03.book Page 32 Monday, July 24, 2006 5:16 PM
Section 3-3
Terminals Top Terminals *1
✕
✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
✕ ✕
✕ ✕ ✕ ✕ ✕ ✕ ✕
Name/Application
✕ ✕ ✕
Name/Application
RUN
ERR
BUSY
GATE
OR COM OUT (*1)
For RUN, ERR, BUSY, GATE, and OR
DSA
Command inputs
Error output
NC
Not connected
RESET
Resets F150
STEP
DI 0
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
COM IN
---
Command inputs
Bottom Terminals
✕ ✕
✕ ✕
✕ ✕
✕
✕
✕ ✕ *2
32
✕ ✕
✕ ✕
✕ ✕ ✕
✕ ✕ *3
Page 48
Z141-E1-03.book Page 33 Monday, July 24, 2006 5:16 PM
Section 3-3
Terminals
Name/Application DO 1
Measurement results output
DO 3 DO 5
Name/Application DO 0 DO 2
Measurement results output
DO 4
DO 7
DO 6
NC
Not connected COM OUT (*2)
For DO 0 to DO 7
DO 9
Measurement results output
Measurement results output
DO 11
DO 8 DO 10
DO 13
DO 12
DO 15
DO 14
---
COM OUT (*3)
For DO 8 to DO 15
!Caution Do not input the RESET input immediately after turning ON the power. When using RESET input to synchronize execution timing, wait at least 1 s after turning ON the F150 power supply before turning ON the RESET terminal.
!Caution Do not reverse the connections of the signal terminals and COM terminals.
F150-C10E-3-DRT
33
Page 49
Z141-E1-03.book Page 34 Monday, July 24, 2006 5:16 PM
Section 3-3
Terminals
Name/Application
Name/Application
RUN
ERR
BUSY
GATE
OR
NC
Not connected
RESET
Resets F150
COM OUT NC
Not connected
Error output
STEP
NC
NC
NC
NC
NC
NC
NC
NC
COM IN
---
Not connected
!Caution Do not input the RESET input immediately after turning ON the power. When using RESET input to synchronize execution timing, wait at least 1 s after turning ON the F150 power supply before turning ON the RESET terminal.
!Caution Do not reverse the connections of the signal terminals and COM terminals.
34