For the Omron G72C-OD16 and Omron G72C-ID16

Page 1

9

SYSMAC Transistor Remote Module

G72C

Terminal Block and Transmission Capability in One Module 1 Two-conductor cable communications available using Omron Wired Remote I/O Master Modules (C200H-RM201 and C500-RM201)

1 Can share transmission lines with G72C-V Remote Terminal Blocks

1 187.5 kbps communication speed with maximum 200 m transmission distance

1 Isolated transmission lines ensure

èò excellent noise immunity

1 Easily mounts to DIN rail track or with screws for panel mounting

Ordering Information Classification For input

Internal I/O circuit common NPN (+ common) PNP (-- common)

For output

I/O points 16 points per module

Rated voltage 24 VDC

Part number G72C-ID16 DC24V G72C-ID16-1 DC24V

NPN (-- common)

G72C-OD16 DC24V

PNP (-- common)

G72C-OD16-1 DC24V

Specifications 3 RATINGS G72C-ID16-1 Input Rated input voltage

24 VDC

Input current

9.7 mA/point

ON delay time

1.5 ms max.

OFF delay time

1.5 ms max.

Number of circuits

16 points (8 points/common)

ON voltage

15 VDC max.

OFF voltage

5.6 VDC max.

Insulation method

Photocoupler

Input indication

LEDs (green)

Page 2

G72C

G72C G72C-OD16-1 Output Rated input voltage

24 VDC

Rated output current

0.3 A/point

Residual voltage

1.2 V max.

Leakage current

100 µA max.

Number of circuits

16 points (8 points/common)

Insulation method

Photocoupler

Input indication

LEDs (green)

3 CHARACTERISTICS Communication system

Two-conductor, half duplex

Synchronization method

Asynchronous

Transmission speed (baud rate)

187.5 kbps (transmission time: 2 ms max. per G72C)

Transmission distance

200 m (total length)

Transmission path

Two-conductor cable (VCTF 0.75 x DPDT recommended)

Interface

RS-485

Operating voltage range

24 VDC +10%/ --15%

Current consumption (See Note)

24 VDC: 200 mA max.

RUN output

SPST-NO contact output (closed during operation) Contact capacity: 100,000 operations at 2 A, 250 VAC (cosφ = 1)

Diagnostics

Transmission error check (BCC plus inverted two-transmission verification check), CPU error monitor 20 MΩ min. at 250 VDC

Insulation resistance Dielectric strength

2,000 VAC, 50/60 Hz for 1 min between RUN output circuit and other terminals 500 VAC, 50/60 Hz for 1 min for other terminals

Noise immunity

Noise level: 1.5 kV; pulse width: 100 ns to 1 Ps

Vibration resistance

10 to 55 Hz, 0.75--mm double amplitude for 2 hrs each in X, Y, and Z directions (both mounted and not mounted to DIN track)

Shock resistance Ambient temperature

50G, 3 times each in X, Y, and Z directions Operating: 0°C to 55°C (32°F to 131°F) Storage: --20°C to 65°C (--4°F to 149°F)

Ambient humidity

Operating: 35% to 85%

Mounting strength

No damage when 5 kgf (4.9 N) pull load was applied for 1 s in all directions (except for 1 kgf (0.9 N) in direction of rail)

Terminal strength

No abnormality when 5 kgf (4.9 N) pull load was applied for 1 s in all directions

Weight

Approx. 380 g

Approvals

UL recognized, File No. E41515; CSA certified, File No. LD31928 for G72C-ID16, G72C-OD16

Note: Consumption when all 16 points are ON. Excludes external current for Remote Input Terminal and external load current for Remote Output Terminal. Maximum current consumption for both input and output when all points are OFF will be 40 mA at 24 VDC.

2

Page 3

G72C

G72C

Nomenclature Transmission Power Path Terminals Terminals Indicates Remote Terminal for input. (Out indicates Remote Terminal for output.) Label

Indicators Power & Transmission Error

I/O LEDs I/O Terminals

RUN Output

Indicates negative side terminal Rail Hook

3 INDICATOR OPERATION POWER T/R ERR

Display

Meaning

Lit

Lit when power is supplied and the unit is operating.

Not lit

Not lit when power supply is abnormal.

Flashing

Flashes during normal data transmission.

Lit

Lit during standby and transmission error.

Not lit

Not lit during CPU (watchdog timer) error.

3

Page 4

G72C

G72C

Operation 3 SETTING Output HOLD/STOP Mode

Word Settings

Terminator Setting

OFF

ON

Not terminator (termination resistance OFF)

Terminator (termination resistance ON)

The terminator setting also sets the termination resistance. Be sure to set only one terminator per Remote I/O Master Unit and be sure it is the Unit farthest from the Master (Factory-set to OFF.) Set word numbers in order backwards from 31. (Factory set to 31.)

Output HOLD/STOP Mode (for Remote Output Interface only) Pin 6 HOLD

STOP

OUT channel status is held during a slave transmission error.

All OUT channel bits go OFF for a slave transmission error. (See Note)

Note: A slave transmission error results if no data or abnormal data is sent from the Master Unit. (Factory-set to STOP mode.)

Word Settings Word

Pin 1

2

3

4

5

0

OFF

OFF

OFF

OFF

OFF

1

ON

OFF

OFF

OFF

OFF

2

OFF

ON

OFF

OFF

OFF

3

ON

ON

OFF

OFF

OFF

. . .

. . .

. . .

. . .

. . .

. . .

28

OFF

OFF

ON

ON

ON

29

ON

OFF

ON

ON

ON

30

OFF

ON

ON

ON

ON

31

ON

ON

ON

ON

ON

4

Page 5

G72C

G72C 3 SYSTEM CONFIGURATION CPU Rack

Two-conductor cable

Wired Remote I/O Master Module (C500-RM201 or C200H-RM201) Two-conductor cable

G71 Remote Interface

G7TC I/O Block

G72C Remote Terminal

Dimensions Unit: mm (inch) 182 (7.17) max. 170±0.2

Two, 5 dia. holes (for M4 screws)

85 (3.35) max. 75±0.2

35.3±0.2 M3.5

8

10

35 max. 45 (1.77) max.

5

Page 6

G72C

G72C

Installation 3 INTERNAL CIRCUITS G72C-ID16 for Input

G72C-OD16 for Output Relay contacts

A B

Relay contacts A B

A0

B0 (+)

A0 B1 (--) Photocoupler B2 (+)

--1 Fuse +2

B0 (+) 4.3 kΩ

A1

DC/DC converter

B3 (--)

--3

G72C-ID16-1 for Input

Internal circuit

+0

Photocoupler RUN output

Power supply Transmission path

Internal circuit

Power supply Transmission path

Photocoupler

RUN output

+0

B1 (--) Photocoupler B2 (+) 4.3 kΩ

--1 A1 Fuse +2

DC/DC converter

B3 (--)

--3

G72C-OD16-1 for Output A B PHC

A B B0 (+) A0

B1 (--) B2 (+) PHC

--1

A1

+2

B3 (--)

DC/DC converter

--3

Internal circuit

+0

A0 Power supply Transmission path

Internal circuit

Power supply Transmission path

PHC

B0 (+)

+0

B1 (--)

PHC

B2 (+)

--1 A1 +2

DC/DC converter

B3 (--)

--3

3 TERMINAL ARRANGEMENT Transmission path +

--

0

1

Power supply +

A

A0 B

Black marks

6

A1 B0

A2 B1

A3 B2

A4 B3

A5 B4

A6 A7 A8 B5

-2

3

A9 A10 A11 A12 A13 A14 A15

B6 B7 B8

B9 B10 B11 B12 B13 B14 B15

Note: Positive power terminal no. 2 at the upper-right part is internally connected to the B0, B2, B4, B6, B8, B10, B12, and B14 I/O terminals at the lower part, and negative power terminal no. 3 at the upper-right part is internally connected to the B1, B3, B5, B7, B9, B11, B13, and B15 I/O terminals at the lower part and have black marks.

Page 7

G72C

G72C 3 CONNECTION WITH I/O DEVICES (Repeater terminal block for sensor/load power wiring is not required.)

Proximity sensor Photoelectric sensor

For Input

A0

A1

+ B0

Sensor 1

Sensor 2

Sensor 1

B1

Black

White

B2

-- A2 +

IN

A0

B2

A1

+ B0

Sensor 2

Sensor 1

--

A2

+

B1

IN

B2

White

IN

Red White Black

B1

+

Red White Black

B0

A2

B;acl

--

Black

A1

Two-wire Connection G72C-ID16-1

Black

+

White

A0

Two-wire Connection G72C-ID16

White

Three-wire Connection

Sensor 2

For Output G72C-OD16 A0

+ B0

L1

A1

G72C-OD16-1 -B1

L2

A2

+

OUT

A0

+ B0

B2

L1

A1

-B1

A2

+

OUT

B2

L2

7

Page 8

G72C

G72C

Precautions 3 PROPER APPLICATION Each node can consist of either a G72C Remote Terminal or a G71 Remote Interface and G7TC I/O Block pair. Each Remote I/O Subsystem connected to a Master Module can contain up to 32 nodes. Never connect or disconnect a G71 Remote Interface without first turning off the power. Failure to turn off the power can result in operational errors.

Be sure to supply the correct power to each Remote Module and combine only compatible units. I/O specifications are provided in the following. Proper combinations can be checked with label colors. The G71 Remote Output Interface corresponds to NPN (-- common). Use the NPN-output G7TC Models (+ common) when connecting. Always confirm that all G71 and G72C Units have been turned on before turning providing power to the Master.

All Remote Modules are available as 24 VDC Input or 24 VDC Output models. G71 Remote Interface Item

Model

Label color

G7TC I/O Block Model

G72C Remote Terminal

Label display (color)

Model

Label color

Input

G71-IC16

Red

G7TC-IA16 G7TC-ID16

IA16 (red)

G72C-ID16

Red

Output

G71-OD16

Yellow

G7TC-OC16 G7TC-OC08

OS16/OS08 (yellow)

G72C-OD16

Yellow

Note: Do not connect a G71 Remote Interface to a G7TC-OC16-1 I/O Block, which is a PNP model (-- common); they are incompatible.

Connections Correct Example

Incorrect Example 1

Incorrect Example 2

Always wire in order from the Master, connecting positive to positive and negative to negative, without branching.

The wiring below is incorrect because positive has been connected to negative.

The wiring below is incorrect because a branch has been created.

Remote I/O Master C500-RM201 C200H-RM201

8

G71 Remote Interface G72C Remote Terminal

G71 Remote Interface G72C Remote Terminal

Remote I/O Master C500-RM201 C200H-RM201

G71 Remote Interface G72C Remote Terminal

Remote I/O Master C500-RM201 C200H-RM201

G71 Remote Interface G72C Remote Terminal

G71 Remote Interface G72C Remote Terminal

Page 9

G72C

G72C

NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.

9

OMRON ELECTRONICS, INC.

OMRON CANADA, INC.

One East Commerce Drive Schaumburg, IL 60173

885 Milner Avenue Scarborough, Ontario M1B 5V8

1-800-55-OMRON

416-286-6465

Cat. No. GC RIO-1

04/00

Specifications subject to change without notice.