Page 1
9
SYSMAC Transistor Remote Module
G72C
Terminal Block and Transmission Capability in One Module 1 Two-conductor cable communications available using Omron Wired Remote I/O Master Modules (C200H-RM201 and C500-RM201)
1 Can share transmission lines with G72C-V Remote Terminal Blocks
1 187.5 kbps communication speed with maximum 200 m transmission distance
1 Isolated transmission lines ensure
èò excellent noise immunity
1 Easily mounts to DIN rail track or with screws for panel mounting
Ordering Information Classification For input
Internal I/O circuit common NPN (+ common) PNP (-- common)
For output
I/O points 16 points per module
Rated voltage 24 VDC
Part number G72C-ID16 DC24V G72C-ID16-1 DC24V
NPN (-- common)
G72C-OD16 DC24V
PNP (-- common)
G72C-OD16-1 DC24V
Specifications 3 RATINGS G72C-ID16-1 Input Rated input voltage
24 VDC
Input current
9.7 mA/point
ON delay time
1.5 ms max.
OFF delay time
1.5 ms max.
Number of circuits
16 points (8 points/common)
ON voltage
15 VDC max.
OFF voltage
5.6 VDC max.
Insulation method
Photocoupler
Input indication
LEDs (green)
Page 2
G72C
G72C G72C-OD16-1 Output Rated input voltage
24 VDC
Rated output current
0.3 A/point
Residual voltage
1.2 V max.
Leakage current
100 µA max.
Number of circuits
16 points (8 points/common)
Insulation method
Photocoupler
Input indication
LEDs (green)
3 CHARACTERISTICS Communication system
Two-conductor, half duplex
Synchronization method
Asynchronous
Transmission speed (baud rate)
187.5 kbps (transmission time: 2 ms max. per G72C)
Transmission distance
200 m (total length)
Transmission path
Two-conductor cable (VCTF 0.75 x DPDT recommended)
Interface
RS-485
Operating voltage range
24 VDC +10%/ --15%
Current consumption (See Note)
24 VDC: 200 mA max.
RUN output
SPST-NO contact output (closed during operation) Contact capacity: 100,000 operations at 2 A, 250 VAC (cosφ = 1)
Diagnostics
Transmission error check (BCC plus inverted two-transmission verification check), CPU error monitor 20 MΩ min. at 250 VDC
Insulation resistance Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between RUN output circuit and other terminals 500 VAC, 50/60 Hz for 1 min for other terminals
Noise immunity
Noise level: 1.5 kV; pulse width: 100 ns to 1 Ps
Vibration resistance
10 to 55 Hz, 0.75--mm double amplitude for 2 hrs each in X, Y, and Z directions (both mounted and not mounted to DIN track)
Shock resistance Ambient temperature
50G, 3 times each in X, Y, and Z directions Operating: 0°C to 55°C (32°F to 131°F) Storage: --20°C to 65°C (--4°F to 149°F)
Ambient humidity
Operating: 35% to 85%
Mounting strength
No damage when 5 kgf (4.9 N) pull load was applied for 1 s in all directions (except for 1 kgf (0.9 N) in direction of rail)
Terminal strength
No abnormality when 5 kgf (4.9 N) pull load was applied for 1 s in all directions
Weight
Approx. 380 g
Approvals
UL recognized, File No. E41515; CSA certified, File No. LD31928 for G72C-ID16, G72C-OD16
Note: Consumption when all 16 points are ON. Excludes external current for Remote Input Terminal and external load current for Remote Output Terminal. Maximum current consumption for both input and output when all points are OFF will be 40 mA at 24 VDC.
2
Page 3
G72C
G72C
Nomenclature Transmission Power Path Terminals Terminals Indicates Remote Terminal for input. (Out indicates Remote Terminal for output.) Label
Indicators Power & Transmission Error
I/O LEDs I/O Terminals
RUN Output
Indicates negative side terminal Rail Hook
3 INDICATOR OPERATION POWER T/R ERR
Display
Meaning
Lit
Lit when power is supplied and the unit is operating.
Not lit
Not lit when power supply is abnormal.
Flashing
Flashes during normal data transmission.
Lit
Lit during standby and transmission error.
Not lit
Not lit during CPU (watchdog timer) error.
3
Page 4
G72C
G72C
Operation 3 SETTING Output HOLD/STOP Mode
Word Settings
Terminator Setting
OFF
ON
Not terminator (termination resistance OFF)
Terminator (termination resistance ON)
The terminator setting also sets the termination resistance. Be sure to set only one terminator per Remote I/O Master Unit and be sure it is the Unit farthest from the Master (Factory-set to OFF.) Set word numbers in order backwards from 31. (Factory set to 31.)
Output HOLD/STOP Mode (for Remote Output Interface only) Pin 6 HOLD
STOP
OUT channel status is held during a slave transmission error.
All OUT channel bits go OFF for a slave transmission error. (See Note)
Note: A slave transmission error results if no data or abnormal data is sent from the Master Unit. (Factory-set to STOP mode.)
Word Settings Word
Pin 1
2
3
4
5
0
OFF
OFF
OFF
OFF
OFF
1
ON
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
. . .
. . .
. . .
. . .
. . .
. . .
28
OFF
OFF
ON
ON
ON
29
ON
OFF
ON
ON
ON
30
OFF
ON
ON
ON
ON
31
ON
ON
ON
ON
ON
4
Page 5
G72C
G72C 3 SYSTEM CONFIGURATION CPU Rack
Two-conductor cable
Wired Remote I/O Master Module (C500-RM201 or C200H-RM201) Two-conductor cable
G71 Remote Interface
G7TC I/O Block
G72C Remote Terminal
Dimensions Unit: mm (inch) 182 (7.17) max. 170±0.2
Two, 5 dia. holes (for M4 screws)
85 (3.35) max. 75±0.2
35.3±0.2 M3.5
8
10
35 max. 45 (1.77) max.
5
Page 6
G72C
G72C
Installation 3 INTERNAL CIRCUITS G72C-ID16 for Input
G72C-OD16 for Output Relay contacts
A B
Relay contacts A B
A0
B0 (+)
A0 B1 (--) Photocoupler B2 (+)
--1 Fuse +2
B0 (+) 4.3 kΩ
A1
DC/DC converter
B3 (--)
--3
G72C-ID16-1 for Input
Internal circuit
+0
Photocoupler RUN output
Power supply Transmission path
Internal circuit
Power supply Transmission path
Photocoupler
RUN output
+0
B1 (--) Photocoupler B2 (+) 4.3 kΩ
--1 A1 Fuse +2
DC/DC converter
B3 (--)
--3
G72C-OD16-1 for Output A B PHC
A B B0 (+) A0
B1 (--) B2 (+) PHC
--1
A1
+2
B3 (--)
DC/DC converter
--3
Internal circuit
+0
A0 Power supply Transmission path
Internal circuit
Power supply Transmission path
PHC
B0 (+)
+0
B1 (--)
PHC
B2 (+)
--1 A1 +2
DC/DC converter
B3 (--)
--3
3 TERMINAL ARRANGEMENT Transmission path +
--
0
1
Power supply +
A
A0 B
Black marks
6
A1 B0
A2 B1
A3 B2
A4 B3
A5 B4
A6 A7 A8 B5
-2
3
A9 A10 A11 A12 A13 A14 A15
B6 B7 B8
B9 B10 B11 B12 B13 B14 B15
Note: Positive power terminal no. 2 at the upper-right part is internally connected to the B0, B2, B4, B6, B8, B10, B12, and B14 I/O terminals at the lower part, and negative power terminal no. 3 at the upper-right part is internally connected to the B1, B3, B5, B7, B9, B11, B13, and B15 I/O terminals at the lower part and have black marks.
Page 7
G72C
G72C 3 CONNECTION WITH I/O DEVICES (Repeater terminal block for sensor/load power wiring is not required.)
Proximity sensor Photoelectric sensor
For Input
A0
A1
+ B0
Sensor 1
Sensor 2
Sensor 1
B1
Black
White
B2
-- A2 +
IN
A0
B2
A1
+ B0
Sensor 2
Sensor 1
--
A2
+
B1
IN
B2
White
IN
Red White Black
B1
+
Red White Black
B0
A2
B;acl
--
Black
A1
Two-wire Connection G72C-ID16-1
Black
+
White
A0
Two-wire Connection G72C-ID16
White
Three-wire Connection
Sensor 2
For Output G72C-OD16 A0
+ B0
L1
A1
G72C-OD16-1 -B1
L2
A2
+
OUT
A0
+ B0
B2
L1
A1
-B1
A2
+
OUT
B2
L2
7
Page 8
G72C
G72C
Precautions 3 PROPER APPLICATION Each node can consist of either a G72C Remote Terminal or a G71 Remote Interface and G7TC I/O Block pair. Each Remote I/O Subsystem connected to a Master Module can contain up to 32 nodes. Never connect or disconnect a G71 Remote Interface without first turning off the power. Failure to turn off the power can result in operational errors.
Be sure to supply the correct power to each Remote Module and combine only compatible units. I/O specifications are provided in the following. Proper combinations can be checked with label colors. The G71 Remote Output Interface corresponds to NPN (-- common). Use the NPN-output G7TC Models (+ common) when connecting. Always confirm that all G71 and G72C Units have been turned on before turning providing power to the Master.
All Remote Modules are available as 24 VDC Input or 24 VDC Output models. G71 Remote Interface Item
Model
Label color
G7TC I/O Block Model
G72C Remote Terminal
Label display (color)
Model
Label color
Input
G71-IC16
Red
G7TC-IA16 G7TC-ID16
IA16 (red)
G72C-ID16
Red
Output
G71-OD16
Yellow
G7TC-OC16 G7TC-OC08
OS16/OS08 (yellow)
G72C-OD16
Yellow
Note: Do not connect a G71 Remote Interface to a G7TC-OC16-1 I/O Block, which is a PNP model (-- common); they are incompatible.
Connections Correct Example
Incorrect Example 1
Incorrect Example 2
Always wire in order from the Master, connecting positive to positive and negative to negative, without branching.
The wiring below is incorrect because positive has been connected to negative.
The wiring below is incorrect because a branch has been created.
Remote I/O Master C500-RM201 C200H-RM201
8
G71 Remote Interface G72C Remote Terminal
G71 Remote Interface G72C Remote Terminal
Remote I/O Master C500-RM201 C200H-RM201
G71 Remote Interface G72C Remote Terminal
Remote I/O Master C500-RM201 C200H-RM201
G71 Remote Interface G72C Remote Terminal
G71 Remote Interface G72C Remote Terminal
Page 9
G72C
G72C
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
9
OMRON ELECTRONICS, INC.
OMRON CANADA, INC.
One East Commerce Drive Schaumburg, IL 60173
885 Milner Avenue Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GC RIO-1
04/00
Specifications subject to change without notice.