For the Omron H8PS8B-F

Page 25

H8PS Clearing Settings Clearing All Programs

Clearing Individual Steps, Cams, and Banks

The all clear function can be used to delete all cam programs, the settings for advance angle compensation function, and all other settings. All settings in the Function Setting Mode will be returned to their default settings.

ON/OFF angle settings can be deleted by step, by cam, or by bank. If settings are deleted by cam, the settings for the advance angle compensation (ADV) function will not be deleted. If settings are deleted by bank, the settings for the ADV function will also be deleted. Settings in the Function Setting Mode will not be deleted.

Mode Mode

Set the mode switch to PRGM or TEST.

PRGM TEST RUN

Set the mode switch to PRGM or TEST.

PRGM TEST RUN

Initial Display Initial Display

PRG

PRG

CAM

STEP CAM

STEP

Press the CLEAR Key for 3 s min. Press the CLEAR Key. PRG

Confirm that clr flashes on the display.

Screens for Individually Clearing Items PRG

CAM

STEP

Deleting Settings by Step Press the STEP Keys to specify the step to be deleted.

Press the WRITE Key. CAM

CLEAR Key PRG

After the completion of all clear processing, the screen displays end for approximately one second and then resume the previously displayed screen. If the CLEAR Key is pressed again before pressing the WRITE Key, the settings will not be deleted and the previous display will be resumed.

STEP PRG

CAM

STEP PRG

CAM

Deleting Settings by Cams Press the CAM Keys to specify the cam to be deleted.

Deleting Settings by Banks Press the BANK Key to specify the bank to be deleted.

STEP

Press the WRITE Key. CLEAR Key. PRG

After the completion of all clear processing, the screen displays end for approximately one second and then resume the previously displayed screen. If the CLEAR Key is pressed again before pressing the WRITE Key, the settings will not be deleted and the previous display will be resumed.

25

Page 26

H8PS ■ Advanced Functions Set the advanced functions as required to perform more advanced operation. Outlines of the advanced functions are provided on the following pages. For details, refer to the Operation Manual (Cat. No. Z199).

Mode Transitions The values in parentheses are the default settings. PRGM TEST RUN

Function Setting Mode

ADV Key 3 s min. Programming Mode PRG

➾ Refer to pages 28 to 30.

Changed with the mode switch. PRGM TEST RUN

Test Mode

: No. of pulse outputs [60] ADV Key

TST

: Pulse output start angle [0°] ADV Key

Changed with the mode switch. PRGM TEST RUN

: Speed alarm upper limit [---] Run Mode

RUN

ADV Key

: Speed alarm lower limit [---] ADV Key ADV Key 5 s min.

ADV Key ON/OFF Key 1 s min.

: Step number limit [---] (See note 1.) ADV Key

: Cam protection [None] All Protection Disables all keys and switches. will light when the all protection function is enabled. ➾ Refer to page 24.

ADV Key

Switching the Angle and Speed Display

Setting the ADV Function

Main Display: Angle Sub-display: Speed ↓↑ Main Display: Speed Sub-display: Angle ➾ Refer to page 24.

Advance angle compensation (ADV) function automatically advances the ON/OFF angle of outputs in proportion to the machine (Encoder) speed.

: Bank enable/disable [Disable] ADV Key

: Bank switching method [Bank inputs] (See note 2.) ADV Key

: Bank copy (See note 2.) ADV Key

: E24 detection enable/disable [Enable] ADV Key Shaded items above are not displayed for 8-output models. Note 1: The default setting is for 10 steps for all cams. Note 2: Not displayed when F7 is disabled.

26

Page 27

H8PS Advance Angle Compensation (ADV) Function The advance angle compensation function automatically advances the ON/OFF angle of cam outputs in proportion to machine (encoder) speed. As the speed of the machine increases, the system can be affected by the delay in outputs. If the ADV function is used, the output delay caused by higher speeds is automatically compensated.

Example: Setting the ADV Value to 2° at 100 r/min for Cam 4 1. Set the mode switch to PRGM or TEST. 2. Set cam number 4 with the CAM Keys

3. Press the ADV Key to move to the ADV function setting display and confirm that “ADV” is displayed. Setting Display

As shown in the following diagram, ADV function is used to linearly compensate outputs according to the speed based on the ADV value setting for a specific speed.

TST

4. Set the speed to 100 with the ANGLE Keys and then press the WRITE Key.

ADV value

CAM

2°

. (See note.)

STEP

Amount of angle compensation TST

0

100

5. Set the ADV value to 2 with the ANGLE Keys .

Speed (r/min)

Note: The maximum amount of angle compensation is 360°. Cam program setting 100°

CAM

180°

8° advance angle compensation

STEP

At high speed (400r/min)

TST

92°

6. Press the WRITE Key to write the settings to memory.

172°

Example: ADV Value Set to 2° at 100 r/min ADV value can be set independently for cams 1 to 7 (7 total). For the ADV function, the speed and the amount of angle compensation are set. If “- - -” is displayed for any setting, the ADV function is disabled. The setting ranges are given in the following table. Encoder

Speed

ADV value

Resolution Display angle 256

256

256

360

360

---

720

---

“ - - - ”, 1 to 1,600 “ - - - ”, 1 to 1,600

“ - - - ”, 0 to 255 “ - - - ”, 0 to 359

“ - - - ”, 1 to 1,600 “ - - - ”, 1 to 800

“ - - - ”, 0 to 359 “ - - - ”, 0 to 359.5

CAM

STEP

7. Press the ADV Key after finishing setting the ADV function. The previous display in Programming or Test Mode will be resumed. Note: If the bank function is being used, set the bank number before setting the cam number.

Note: Default settings are shown in reverse type. The maximum response speed will decrease as shown in the following table when ADV values are set for 4 cams or more. Number of cams with ADV settings 0 to 3 4 to 7

Encoder resolution

Max. response speed

256/360

1,600r/min

720

800r/min

256/360

1,200r/min

720

600r/min

Note: Even if the ADV value is set to 0°, the cam must be included in the number of cams with ADV settings.

27

Page 28

H8PS Pulse Output (f1/f2)

Speed Alarm Outputs (f3/f4)

Outputs a preset number of pulses per Encoder rotation. Pulses are output at a 1:1 ON/OFF ratio and pulse output can be started from a specified angle.

Specific cam outputs can be used as Encoder speed alarm outputs. Alarms can be output for upper and lower speed limits. Speed

Operation for 9 Output Pulses and a Start Angle of 0° 1

2

3

0°

4

5

90°

6

7

Upper limit SV 8

180°

9

270°

Lower limit SV

0°

Upper Limit Alarm Output

Output start angle

Operation for 9 Output Pulses and a Start Angle of 10° 1

2

0°10°

3

4

90°

5

6

7

180°

Lower Limit Alarm Output 8

9

270°

0°

Output start angle

Number of Output Pulses (f1)

The speed alarm outputs are assigned to cam outputs as shown in the following table. The speed alarms are set to “- - -” for the default settings, i.e., the normal cam outputs are enabled. If a speed alarm is set to any value but “- - -”, the normal cam output for the corresponding cam number will be disabled.

Select the number of pulses per rotation from the following table. Encoder resolution

Settable number of pulses

256

1, 2, 3, 4, 5, 6, 9, 10, 12, 15, 18, 20, 30, 36, 45, 60 , 90

360

1, 2, 3, 4, 5, 6, 9, 10, 12, 15, 18, 20, 30, 36, 45, 60 , 90, 180

720

1, 2, 3, 4, 5, 6, 8, 9, 10, 12, 15, 18, 20, 24, 30, 36, 40, 45, 60 , 72, 90, 120, 180, 360

Upper Limit Alarm Output H8PS-8@ (8 outputs)

Cam 7

Lower Limit Alarm Output Cam 8

H8PS-16@ (16 outputs) Cam 15

Cam 16

H8PS-32@ (32 outputs) Cam 31

Cam 32

The setting ranges for the upper and lower limits speed alarm are given in the following table. Encoder resolution

Speed

Note: Default settings are shown in reverse type.

256, 360

Example: Setting 90 Pulses per Rotation

720

The number of pulses is set using the F1 menu in the Function Setting Mode.

Note: Default settings are shown in reverse type.

“ - - - ” or 0 to 1,600 r/min “ - - - ” or 0 to 800 r/min

Speed Alarm Upper Limit (f3)

Setting Display

Example: Setting the Upper Limit Set Value to 700 r/min for a 16output Model

PRG

Set the number of pulses with the ANGLE Keys and then press the WRITE Key.

The upper limit set value is set using the F3 menu in the Function Setting Mode. Upper Limit Setting Display

CAM

STEP PRG

Pulse Output Start Angle (f2)

Set the upper limit set value to 700 with the ANGLE Keys and then press the WRITE Key. (See note.)

The setting ranges are given in the following table. Encoder Resolution

Start angle

Display angle

CAM

256

256

0 to 255°

256

360

0 to 359° (See note 2.)

360

---

0 to 359°

720

---

0 to 359.5°

STEP

Note: If banks are being used, the bank number must be set.

Speed Alarm Lower Limit (f4) Example: Setting the Lower Limit Set Value to 20 r/min for a 16output Model

Note: 1. Default settings are shown in reverse type. 2. The output accuracy is 2° maximum, so not all angles can be set.

The lower limit set value is set using the F4 menu in the Function Setting Mode.

Example: Setting the Pulse Output Start Angle to 100°

Lower Limit Setting Display

The starting angle for pulse outputs is set using the F2 menu in the Function Setting Mode.

PRG

Set the upper limit set value to 20 with the ANGLE Keys and then press the WRITE Key.

Setting Display PRG

Set the pulse output start angle to 100 with the ANGLE Keys and then press the WRITE Key. CAM

CAM

STEP

Note: If banks are being used, the bank number must be set.

STEP

28

Page 29

H8PS Step Number Limit (f5)

Bank Functions (f7/f8/f9)

With the H8PS, up to 10 steps can be set to turn the output ON/OFF 10 times for each cam. The number of steps that can be set, however, can be restricted to prevent programming from being added through operating mistakes. Settings can be made for all cams at once or each cam individually. The default setting for the Step Number Limit is 10 steps for all cams.

The bank function is supported by 16-/32-output models. Banks enable changing the entire cam program at once by switching bank numbers (0 to 7).

Example: Limiting the Number of Steps to 2 for All Cams Collectively.

Cam Program (Bank No. 7)

Cam Program (Bank No. 2) Cam Program (Bank No. 1) Cam Program (Bank No. 0)

The maximum number of steps to be set is set using the F5 menu in the Function Setting Mode.

Step 0 Step 1 Control output (cam number) ON angle OFF angle ON angle OFF angle

Display for Collective Settings PRG

Set the cam number to a with the CAM Keys and set the maximum number of steps to 2 with the Angle Keys . Press the WRITE Key to write the setting to memory. STEP

CAM

Step 9 ON angle OFF angle

1

45°

90°

135°

225°

270°

315°

2

0°

90°

135°

180°

---

---

32

90°

225°

270°

285°

315°

345°

In Run Mode or Test Mode, the start input must be turned OFF and ON as shown in the following diagram in order to change banks. Control the start input when changing banks. Bank specification

Bank 0

Bank 1

Bank 2

T4

The cam number can be set to a on the setting display to set all cams at once. If the number of steps is displayed as “---” when the cam number is a, the collective settings for all cams are disabled.

Start ON input OFF

Example: Limiting the Number of Steps to 1 for Cam 3.

Operation

The maximum number of steps to be set is set using the F5 menu in the Function Setting Mode.

T2 Bank 0

Unstable region (outputs OFF)

PRG

Set the cam number to 3 with the CAM Keys and set the maximum number of steps to 1 with the Angle Keys . Press the WRITE Key to write the setting to memory. STEP

T2

T3 Bank 1

Bank 2

ON RUN output OFF

Display for Individual Settings

CAM

T1

T1: 225 ms max. T2: 400 ms max. T3: 20 ms min. T4: 20 ms min.

Bank Enable/Disable (f7) The default setting disables the bank function. To use banks, change the setting using the F7 menu in the Function Setting Mode. Setting Display PRG

Enable or disable the bank function with the ANGLE Keys .

Cam Protection (f6) Cam programs can be write-protected. Use this setting to protect the programs for only specific cam numbers. Protected cam numbers will not be displayed in Programming Mode or Test Mode. Writing or changing programs will not be possible. Protected cam numbers will also not be displayed in Run Mode and cannot be checked. The default settings are for no protection for all cams.

CAM yes no

(Enabled)

(Disabled)

STEP

Example: Protecting Cam 3 with an 8-output Model

Bank Switching Method (f8)

Cam protection is set using the F6 menu in the Function Setting Mode.

The following methods can be used to switch the bank: the bank inputs on the terminal block or the BANK Key on the front of the Cam Positioner.

Setting Display Not lit (protected) 1

CAM

2

4

5

6

7

8

PRG

Set the cam number to be protected (and not displayed) to 3 with the CAM Keys and then press the WRITE Key. The output display will go out.

STEP

29

Page 30

H8PS Bank Switching Method (f8)

Bank Copy (f9)

The following methods can be used to switch the bank: the bank inputs on the terminal block or the BANK Key on the front of the Cam Positioner. The method is set using the F8 menu in the Function Setting Mode.

Programs can be copied between banks. This function is convenient to copy a program to a different bank when only some of the ON/OFF angle settings need to be changed.

Setting

Display

Description

Bank input (IN)

in

Banks can be changed only with the bank inputs. Even if a different bank number is displayed in Programming Mode, the bank specified with the bank inputs will be used after switching to Run Mode or Test Mode.

key

Bank Key (KEY)

Banks can be changed only with the BANK Key. Bank inputs are disabled.

Note: This operation can be used only when the Bank Function (F7) has been enabled. Example: Copying the Program in Bank 2 to Bank 3 Banks are copied using the F9 menu in the Function Setting Mode. Setting Display 1. Set the number of the bank to be copied. PRG

Note: 1. Default settings are shown in reverse type. 2. This setting can be made only when the Bank Function (F7) has been enabled.

Set bank number 2 (the copy source) with the BANK Key and then press the WRITE Key.

Setting Display PRG

Use the ANGLE Keys to set the bank switching method.

in key

(IN)

(KEY)

CAM

STEP

2. Set the number of the bank to receive the copy. PRG

Set bank number 3 (the copy destination) with the BANK Key and then press the WRITE Key.

STEP

CAM

The bank inputs on the terminal block are used as shown in the following table. Bank No.

Bank input terminals 1

2

CAM

4

0

OFF

OFF

OFF

1

ON

OFF

OFF

2

OFF

ON

OFF

3

ON

ON

OFF

4

OFF

OFF

ON

6

ON

OFF

ON

6

OFF

ON

ON

7

ON

ON

ON

STEP

3. Execute the copy. PRG

Confirm that cpy is displayed and then press the WRITE Key again.

CAM

STEP

4. Copying completed. ON: Shorted to COM terminal. PRG

OFF: Open

After completion of copying end is displayed for approx. 1 s and the previous display will be resumed. CAM

STEP

E24 Detection (f10) Displaying E24 errors (Encoder disconnected) can be disabled. The setting does not normally need to be changed. When the Y92C-30 Parallel Input Adapter (order separately) is used to connect more than one H8PS to the same Encoder, an E24 error can appear even if the Encoder connection is normal. If this happens, use the E24 Detection function (F10) in the Function Setting Mode to disable E24 detection displays. Setting Enabled

Disabled

Display

Description yes

An E24 error will be displayed if the Encoder is not connected correctly in Run Mode or Test Mode.

no

Setting Display PRG

Enable or disable E24 detection with the ANGLE Keys .

CAM yes no

(Enabled)

(Disabled)

STEP

An E24 error will not be displayed even if an Encoder is not connected.

Note: Default settings are shown in reverse type.

30

Page 31

H8PS ■ Self Diagnostic Function The following displays will appear on the main display if an error occurs. If an error occurs, all outputs (including cam, pulse, and run outputs) will be turned OFF. Display

Meaning

Recovery method e00

Origin designation data error

Press the CLEAR Key for at least 3 s. All settings, including the origin designation data, will be initialized.

e11

Memory error: RAM error

Cycle the power supply.

e12

Memory error: Checksum error Press the CLEAR Key for at least 3 s. All settings, including the origin designation data, will be initialized.

e13

CPU error

Cycle the power supply.

e21

Response speed exceeded

The Encoder is rotating faster than the allowable range. Reduce the speed to within the allowable range. Then cycle the power supply or switch to Programming Mode and then to Run Mode.

e22

Encoder data error

There are surges or noise around the product or in the wiring. Check the wiring and protect the product from surges and noise. Then cycle the power supply.

e23

Encoder resolution inconsistent Set the Encoder resolution according to the specifications of the Encoder. Then cycle the power supply.

e24

Encoder disconnected

Connect the Encoder connector properly. Then, cycle the power supply or switch to Programming Mode and then to Run Mode.

Angle Data Table To assist with programming when using an Encoder with a resolution of 256/rotation, displays and settings may be done by conversion to 360 degrees by setting a pin on the DIP switch inside the front cover. The following table shows the conversions. 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0°

1°

3°

4°

6°

7°

8°

10°

11°

13°

14°

15°

17°

18°

20°

21°

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

23°

24°

25°

27°

28°

30°

31°

32°

34°

35°

37°

38°

39°

41°

42°

44°

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

45°

46°

48°

49°

51°

52°

53°

55°

56°

58°

59°

60°

62°

63°

65°

66°

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

68°

69°

70°

72°

73°

75°

76°

77°

79°

80°

82°

83°

84°

86°

87°

89°

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

90°

91°

93°

94°

96°

97°

98°

100° 101° 103° 104° 105° 107° 108° 110° 111°

80

81

82

83

84

85

86

87

88

89

90

91

92

93

94

95

113° 114° 115° 117° 118° 120° 121° 122° 124° 125° 127° 128° 129° 131° 132° 134° 96

97

98

99

100

101

102

103

104

105

106

107

108

109

110

111

135° 136° 138° 139° 141° 142° 143° 145° 146° 148° 149° 150° 152° 153° 155° 156° 112

113

114

115

116

117

118

119

120

121

122

123

124

125

126

127

158° 159° 160° 162° 163° 165° 166° 167° 169° 170° 172° 173° 174° 176° 177° 179° 128

129

130

131

132

133

134

135

136

137

138

139

140

141

142

143

180° 181° 183° 184° 186° 187° 188° 190° 191° 193° 194° 195° 197° 198° 200° 201° 144

145

146

147

148

149

150

151

152

153

154

155

156

157

158

159

203° 204° 205° 207° 208° 210° 211° 212° 214° 215° 217° 218° 219° 221° 222° 224° 160

161

162

163

164

165

166

167

168

169

170

171

172

173

174

175

225° 226° 228° 229° 231° 232° 233° 235° 236° 238° 239° 240° 242° 243° 245° 246° 176

177

178

179

180

181

182

183

184

185

186

187

188

189

190

191

256 display (Encoder output data)

248° 249° 250° 252° 253° 255° 256° 257° 259° 260° 262° 263° 264° 266° 267° 269° 192

193

194

195

196

197

198

199

200

201

202

203

204

205

206

207

270° 271° 273° 274° 276° 277° 278° 280° 281° 283° 284° 285° 287° 288° 290° 291° 208

209

210

211

212

213

214

215

216

217

218

219

220

221

222

223

293° 294° 295° 297° 298° 300° 301° 302° 304° 305° 307° 308° 309° 311° 312° 314° 224

225

226

227

228

229

230

231

232

233

234

235

236

237

238

How to Use the Table

0 0°

1 1°

239

315° 316° 318° 319° 321° 322° 323° 325° 326° 328° 329° 330° 332° 333° 335° 336° 240

241

242

243

244

245

246

247

248

249

250

251

252

253

254

255

338° 339° 340° 342° 343° 345° 346° 347° 349° 350° 352° 353° 354° 356° 357° 359°

360° display (360° converted data)

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice.

31

Page 32

Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 2015.10 In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation Industrial Automation Company http://www.ia.omron.com/

(c)Copyright OMRON Corporation 2015 All Right Reserved.