The text of a spec sheet · part 1 of 2
Switch mode Power Supply S82J, pages 1 to 10
Pages 1 to 10 of 20
The original document is the PDF (378 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron S82J-02505 and Omron S82J-10024
Page 1
Switch mode Power Supply
S82J Compact and Economical Switch mode Power Supplies with Capacities Up to 600 W DIN Track Mounting Bracket Type Now Available • Power range from 10 W up to 600 W. • Output Voltages: 5 V, 12 V, 15 V, or 24 V. • Mounting bracket provided for mounting to control panels. • Maintenance-free up to 300 W due to natural ventilation. • Protection-ON alarm indicator shows valuable protection functions in action (300-/600-W models). • Conforms to EMC standards: EN50081-2 and EN50082-2. • With an external filter, achieves conformance to EN50081-1 for universal usage on EMI (300-/600-W models). • Finger protection terminal block to meet VDE0106/P100 • Class 2 approved 10-W, 25-W (except for 5-V output), and 50-W (only for 24-V output) models. • UL508 approved. All models can be used at full load in UL508A industrial control panel applications. • Approved by UL/CSA standards, EN60950, and EN50178 (VDE0160). • Six-language instruction manual provided. (English, French, German, Italian, Spanish, and Japanese)
S82J
Covered Type
Open-frame Type
<10 W to 150 W> • 100 to 240-VAC input • 100 or 200 VAC (selected automatically) (100-W 5-/12-/15-V output, 150-W models)
<10 W to 150 W> • 100 to 240-VAC input • 100 or 200 VAC (selected automatically) (100-W 5-/12-/15-V output, 150-W models)
Enclosure Type
<300/600 W> • 100 or 200 VAC (selectable)
Model Number Structure ■ Model Number Legend S82J 2
3
4
1. Power Ratings 010: 10 W 025: 25 W 050: 50 W 100: 100 W 150: 150 W 300: 300 W 600: 600 W 4. Mounting Bracket None: Front-mounting Bracket Type D: DIN Track Mounting Bracket Type
2. Output Voltage 05: 5V 12: 12 V 15: 15 V 24: 24 V
3. Configuration A: Open-frame type, front terminals B: Open-frame type, top terminals C: Open-frame type, connector D: Covered type, front terminals E: Covered type, top terminals F: Covered type, connector N: Without Mounting Bracket None: Enclosure type, front terminals with Mounting Bracket
Switch mode Power Supply S82J
Power Supplies
1
L-79
Page 2
Ordering Information ■ Front-mounting Bracket Type Configuration
Input Voltage
Power ratings
Open-frame type 100 to 240 VAC 10 W
Front terminals
Top terminals
Connector
2A
S82J-01005A
---
---
12 V
1A
S82J-01012A
---
---
15 V
0.7 A
S82J-01015A
---
---
24 V
0.5 A
S82J-01024A
---
---
5V
5A
S82J-02505A
---
---
12 V
2.1 A
S82J-02512A
---
---
15 V
1.7 A
S82J-02515A
---
---
24 V
1.1 A
S82J-02524A
---
---
5V
10 A
S82J-05005A
---
---
12 V
4.2 A
S82J-05012A
---
---
24 V
2.1 A
S82J-05024A
---
---
100 or 200 VAC 100 W (selected automatically)
5V
20 A
S82J-10005A
S82J-10005B
S82J-10005C
12 V
8.5 A
S82J-10012A
S82J-10012B
S82J-10012C
15 V
7A
S82J-10015A
S82J-10015B
S82J-10015C
100 to 240 VAC
24 V
4.5 A
S82J-10024A
---
---
100 or 200 VAC 150 W (selected automatically)
24 V
6.5 A
S82J-15024A
S82J-15024B
S82J-15024C
100 to 240 VAC 10 W
5V
2A
S82J-01005D
---
---
12 V
1A
S82J-01012D
---
---
15 V
0.7 A
S82J-01015D
---
---
24 V
0.5 A
S82J-01024D
---
---
5V
5A
S82J-02505D
---
---
12 V
2.1 A
S82J-02512D
---
---
15 V
1.7 A
S82J-02515D
---
---
24 V
1.1 A
S82J-02524D
---
---
5V
10 A
S82J-05005D
---
---
12 V
4.2 A
S82J-05012D
---
---
24 V
2.1 A
S82J-05024D
---
---
100 or 200 VAC 100 W (selected automatically)
5V
20 A
S82J-10005D
S82J-10005E
S82J-10005F
12 V
8.5 A
S82J-10012D
S82J-10012E
S82J-10012F
15 V
7A
S82J-10015D
S82J-10015E
S82J-10015F
100 to 240 VAC
24 V
4.5 A
S82J-10024D
---
---
100 or 200 VAC 150 W (selected automatically)
24 V
6.5 A
S82J-15024D
S82J-15024E
S82J-15024F
100 or 200 VAC 300 W (selectable)
24 V
14 A
S82J-30024
---
---
S82J-30024N
---
---
S82J-60024
---
---
S82J-60024N
---
---
50 W
25 W
50 W
600 W
L-80
Output current
5V
25 W
Covered type
Output voltage
Switch mode Power Supply S82J
27 A
Page 3
■ DIN Track Mounting Bracket Type Input Voltage
Power ratings
Open-frame type 100 to 240 VAC 10 W
Output current
Front terminals
Top terminals
Connector
5V
2A
S82J-01005AD
---
---
12 V
1A
S82J-01012AD
---
---
15 V
0.7 A
S82J-01015AD
---
---
24 V
0.5 A
S82J-01024AD
---
---
5V
5A
S82J-02505AD
---
---
12 V
2.1 A
S82J-02512AD
---
---
15 V
1.7 A
S82J-02515AD
---
---
24 V
1.1 A
S82J-02524AD
---
---
5V
10 A
S82J-05005AD
---
---
12 V
4.2 A
S82J-05012AD
---
---
24 V
2.1 A
S82J-05024AD
---
---
100 or 200 VAC 100 W (selected automatically)
5V
20 A
S82J-10005AD
S82J-10005BD
S82J-10005CD
12 V
8.5 A
S82J-10012AD
S82J-10012BD
S82J-10012CD
15 V
7A
S82J-10015AD
S82J-10015BD
S82J-10015CD
100 to 240 VAC
24 V
4.5 A
S82J-10024AD
---
---
100 or 200 VAC 150 W (selected automatically)
24 V
6.5 A
S82J-15024AD
S82J-15024BD
S82J-15024CD
100 to 240 VAC 10 W
5V
2A
S82J-01005DD
---
---
12 V
1A
S82J-01012DD
---
---
15 V
0.7 A
S82J-01015DD
---
---
25 W
50 W
Covered type
Output voltage
24 V
0.5 A
S82J-01024DD
---
---
5V
5A
S82J-02505DD
---
---
12 V
2.1 A
S82J-02512DD
---
---
15 V
1.7 A
S82J-02515DD
---
---
24 V
1.1 A
S82J-02524DD
---
---
5V
10 A
S82J-05005DD
---
---
12 V
4.2 A
S82J-05012DD
---
---
24 V
2.1 A
S82J-05024DD
---
---
100 or 200 VAC 100 W (selected automatically)
5V
20 A
S82J-10005DD
S82J-10005ED
S82J-10005FD
12 V
8.5 A
S82J-10012DD
S82J-10012ED
S82J-10012FD
15 V
7A
S82J-10015DD
S82J-10015ED
S82J-10015FD
100 to 240 VAC
24 V
4.5 A
S82J-10024DD
---
---
100 or 200 VAC 150 W (selected automatically)
24 V
6.5 A
S82J-15024DD
S82J-15024ED
S82J-15024FD
25 W
50 W
Power Supplies
Configuration
Switch mode Power Supply S82J
L-81
Page 4
omrRONn
L-82 Switch mode Power Supply S82J
Page 5
Specifications ■ Ratings/Characteristics Item
100 to 240 VAC input 10 W
25 W
50 W
100 or 200 VAC (selected automatically) 100 W (24 V)
100 W (5, 12, 15 V)
150 W
Efficiency (typical)
67% min. (77% min. for 50-W, 24- 83% min. V models)
75% min.
Input
100 to 240 VAC (85 to 264 VAC) 110 to 170 VDC (set the terminal (L) to + side) (10 and 25 W only) (See note 1.)
100 (85 to 132) or 200 (170 to 264) VAC (selected automatically)
Voltage
300 W
600 W
82% min. 100 (85 to 132) or 200 (170 to 253) VAC (selectable)
50/60 Hz (47 to 450 Hz)
Frequency
Output (See note 3.)
100 or 200 VAC (selectable)
Current (See note 2.)
100 VAC input
0.35 A max.
0.8 A max. 1.4 A max. 2.5 A max.
2.5 A max.
3.5 A max. 8 A max.
14 A max.
200 VAC input
0.3 A max. 0.6 A max. 0.8 A max. 1.5 A max.
1.4 A max.
2.1 A max. 4 A max.
7 A max.
Leakage current (See note 2.)
100 VAC input
0.5 mA max.
200 VAC input
1 mA max.
Inrush current (25°C, cold start) (See note 2.)
100 VAC input
25 A max.
30 A max.
200 VAC input
50 A max.
60 A max.
Noise filter
Yes
Voltage adjustment range
±10% (adjustable with variable resistor (V. ADJ))
Ripple (See note 2.)
2% (p-p) max.
Input variation influence
0.4% max.
Load variation influence
0.8% max. (with rated input, 10% to 100% load)
Temperature variation influence
0.05%/°C max. (with rated input and output)
Startup time
500 ms max. (up to 90% of output voltage at rated input and output)
300 ms max. (up to 90% of output voltage at rated input and output)
Hold time (See note 2.) 20 ms min. Overload protection
105% to 160% of rated load current, inverted L drop/intermittent operation type, automatic reset
No Overvoltage protection (See note 5.)
Overheat protection
No
Protection-ON alarm indicator
No
Parallel operation
No
Series operation
No
Yes (See note 5.)
105% min. of rated load current, inverted L drop type, automatic reset (For the 600-W model, the circuit will be shut OFF when the overload exceeds 5 ±3 s. Protection-ON alarm indicator lit (See note 4.)) Yes (5-V out- No put models only) (See note 5.)
Yes, protection-ON alarm indicator lit (See note 4.)
Yes, protectionON alarm indicator lit (See note 4.) Yes (color, red) Yes, 5 units max. Yes Power Supplies
Additional function
Switching Power Supply S82J
L-83
Page 6
Item
100 to 240 VAC input 10 W
Other
25 W
50 W
100 or 200 VAC (selected automatically) 100 W (24 V)
100 W (5, 12, 15 V)
Ambient temperature
Operating: See the derating curve in the Engineering Data section. −25 to 65°C (with no condensation and icing) Storage:
Ambient humidity
Operating: 25% to 85% Storage: 25% to 90%
Dielectric strength
3.0 kVAC, 50/60 Hz for 1 min (between all inputs and all outputs)
150 W
100 or 200 VAC (selectable) 300 W
600 W
2.2 kVAC, 50/60 Hz for 1 min (between all inputs and GR terminal) 1.0 kVAC, 50/60 Hz for 1 min (between all outputs and GR terminal) Insulation resistance
100 MΩ min. (between all outputs and all inputs/GR terminals at 500 VDC)
Vibration resistance
10 to 55 Hz, 0.375-mm double amplitude for 2 h each in X, Y, and Z directions
Shock resistance
300 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Terminal screw tightening
0.74 N·m
Output indicator
Yes (green)
Electromagnetic interference (See note 2.)
Conforms to FCC Class A
EMC
Emission Enclosure: Emission AC Mains: Immunity ESD:
EMC standards
Conforms to EN50081-2 and EN50082-2
Approved standards
UL
UL508 (Listing), 1950, Class 2 (per UL1310) (See note 10.)
UL508 (Listing), 1012, 1950 (See note 8.) UL508/1012
CSA
CSA C22.2 No. 14, No. 950, Class 2 (See note 10.)
CSA C22.2 No. 14, No. 950
VDE
EN50178 (VDE0160) and EN60950 Terminal types (only terminal part): VDE0106/P100
EN55011 class A EN55011 class A EN61000-4-2: 4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference: ENV50140: 10 Vm (80 MHz to 1 GHz) (level 3) Immunity Conducted Disturbance: ENV50141: 10 V (0.5 to 80 MHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power-line (level 3) 2 kV output line (level 4)
250 g max.
Weight (See note 9.) Note: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10.
1.08 N·m
350 g max.
400 g max.
500 g max.
Conforms to EN50081-2 and EN50082-2 (See note 6.) With noise filter, confirms to EN50081-1 (See note 6 and 7.)
1,000 g max.
CSA EB1402C
2,000 g max.
2,500 g max.
DC inputs not included in safety standard approvals. At 100% load for rated input voltage (100 VAC or 200 VAC). The output specification is defined at the power supply output terminals. For resetting, turn OFF the power supply, leave for more than three minutes (90 seconds min. for the 300-W models), and then turn ON the power supply. For resetting, turn OFF the power supply, leave for more than one minute, and then turn ON the power supply. To ensure the Emission Enclosure rating ferrite ring cores (recommended model: S82Y-JC-T) should be used on all cabling. To ensure the Emission AC Mains rating for EN50081-1 (only for 200-VAC input), a noise filter (recommended models: S82Y-JF3-N for 300-W, S82Y-JF6-N for 600-W) should be used on the input lines. With UL508, 150-W connector type has “Recognized” approval. The weight indicated is the weight of the open-frame type. (Includes the covers for 300-W and 600-W models) Class 2 approved for 10-W, 25-W (except for 5-V output), and 50-W (only for 24-V output) models.
■ Reference Value Value
Definition
Reliability (MTBF)
Item
135,000 hours min.
MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates reliability of devices. Therefore, it does not necessarily represent a life of the product.
Life expectancy
10 yrs. min.
The life expectancy indicates average operating hours under the ambient temperature of 40°C and a load rate of 50%. Normally this is determined by the life expectancy of the builtin aluminum electrolytic capacitor.
L-84
Switching Power Supply S82J
Page 7
Connections ■ Block Diagrams S82J-010@@@@ (10 W) S82J-025@@@@ (25 W) Fuse*
Smoothing circuit
Rectifier
+V
AC (L)
Input
Noise Noisefilter filter
DC Output −V
AC (N)
Inrush current protection circuit
Rectifier and smoothing circuit
* Fuse capacity: 10 W, 1 A 25 W, 2 A Control circuit
Overload detection circuit
Detector Photocoupler
S82J-050@@@@ (50 W) Fuse*
AC(L) Input
+V DC Output
Noise filter
AC(N) Rectifier
Inrush current Smoothing protection circuit circuit
Rectifier and smoothing circuit
−V
* Fuse capacity: 3 A
Control circuit
Overload detection circuit
Detector Photocoupler
S82J-100@@@@ (100 W, 5-/12-/15-V Output) Fuse* +V
AC (L)
Noise Noisefilter filter
DC Output −V
AC (N)
* Fuse capacity: 5 A
100 or 200 V Rectifier and Inrush current protection circuit (selected auto- smoothing matically) circuit
Rectifier and smoothing circuit
Control circuit Detector
Overload detection circuit
Photocoupler
Power Supplies
Input
Overvoltage detector
Overvoltage protection circuit (5 V only)
Switching Power Supply S82J
L-85
Page 8
S82J-10024@@ (100 W, 24-V Output) AC(L)
Fuse (5 A)
+V
Input
DC Output
Noise filter −V
AC(N) Rectifier
Inrush current Smoothing protection circuit circuit
Rectifier and smoothing circuit
Control circuit
Overload detection circuit
Detector Photocoupler Overload detection circuit Photocoupler
S82J-15024@@ (150 W) AC (L)
Fuse (8 A)
Input
+V DC Output
Noise filter
AC (N) Inrush current protection circuit
−V
Rectifier and smoothing circuit
Rectifier
100 or 200 V (selected automatically)
Control circuit
Detector
Overcurrent detector
Photocoupler
S82J-30024@ (300 W) Rectifier and smoothing circuit
Fuse (10 A) Input
DC Output
Noise filter Inrush current protection circuit
Rectifier and smoothing circuit
100/200 V (selectable) Control circuit
Overcurrent detector
Detector Photocoupler
Overvoltage detector Photocoupler Parallel operation selector
L-86
Switching Power Supply S82J
Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC. Keep the terminals open if the input is 200 to 230 VAC.
Page 9
S82J-60024@ (600 W) Fuse 20 A
Rectifier and smoothing circuit
Input
Noise filter
DC Output Inrush current protection circuit
Rectifier and smoothing circuit
100/200 V (selectable) Fan
Control circuit
Overcurrent detector
Detector Photocoupler
Overheat detector
Overvoltage detector Photocoupler
Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC. Keep the terminals open if the input is 200 to 230 VAC.
Parallel operation selector
■ Installation 10-/25-/50-/100-/150-W Models Note: 10-/25-/50-/100 (24 V)-W models are available only as Front Terminal Models.
Front Terminals Model
Top Terminals Model
Connector Model
5
5
5
6
6
6 +V
1
+V
+V 1 −V
−V 3
GR
1
3
AC (L)
GR 3
GR
2
AC (L) NC AC (N)
AC (L) 2
2 AC (N)
−V
AC (N) 9
Types of Connector for the Connector Model (Housing and Terminal Not Included) Connector
Connector on the PCB side
Housing
Terminal
Input
Wafer (Made by Molex) 5277-04A-RE
Housing (Made by Molex) 5196-04-RE or Terminal (Made by Molex) 5194T or 5196-04 5194TL
Output
Tab header (Made by Nippon AMP) 1-178140-5
Rise housing (Made by Nippon AMP) 1-178129-6
Rise contact (Made by Nippon AMP) 1-175196-5 or 1-175218-5
Power Supplies
Note: The permissible current of the output connector is 8 A per pin.
Switching Power Supply S82J
L-87
Page 10
300-W Models 5 6 1
Side view
+V +V −V −V
AC (L) AC (N)
2 4
GR
3
7 8
600-W Models 65 7
1 −V −V +V +V
Side view
8
AC (L) AC (N) GR
1. DC Output Terminals: Connect the load lines to these terminals. 2. Input Terminals: Connect the input lines to these terminals. 4 3 2 Note: A fuse is inserted into the AC (L) side. 3. Ground Terminal (GR): Connect a ground line to this terminal. 4. Input Voltage Selector Terminals: Short-circuit the terminals if the input is 100 to 120 VAC and open the terminals if the input is 200 to 230 VAC 5. Output Indicator (DC ON): Lights while a Direct Current (DC) output is ON. 6. Output Voltage Adjuster (V.ADJ): It is possible to increase or decrease the output voltage by 10%. 7. Protection-ON Alarm Indicator: The red indicator will be lit if the overvoltage (for a 300-/600-W model) or overheat protection (for a 600-W model) circuit is triggered. This indicator will also be lit when overcurrent (for a 600-W model) is detected. 8. Parallel/Single Operation Selector: Set the selector to PARALLEL if the Units are in parallel operation. 9. NC Terminals: Leave unconnected.
L-88
Switching Power Supply S82J