Engineering Data ■ Derating Curve 10-/25-/50-/100-/150-W Model Open-frame type

Covered-type

Standard Installation Forced air-cooling (1 m3/min)

Natural air-cooling

Load (%)

Load (%)

Forced air-cooling (1 m3/min)

Natural air-cooling

Note: The derating curve shown is for standard installation. The derating curve depends on the mounting direction of the Power Supply. Ambient temperature (°C)

Ambient temperature (°C)

300-W Model 120

Parallel Operation Forced air-cooling (1 m3/min) (Standard mounting)

100

Load (%)

Load (%)

Single Operation

Standard mounting

120 20 mm min.

Natural air-cooling (Standard mounting) Forced air-cooling (1 m3/min) (Side mounting) Natural cooling (Side mounting)

20 mm min.

Forced air-cooling (1 m3/min) (Standard mounting)

100

Natural air-cooling (Standard mounting) Forced air-cooling (1 m3/min) (Side mounting)

20 mm min.

20 mm min.

Natural cooling (Side mounting)

Ambient temperature (°C)

Ambient temperature (°C)

600-W Model

Parallel Operation

120 100

Standard Mounting

120

20 mm min.

100

20 mm min.

Ambient temperature (°C)

20 mm min.

20 mm min.

Power Supplies

Load (%)

Load (%)

Single Operation

Ambient temperature (°C)

Note: Provide a minimum clearance of 20 mm between the Power Supplies.

Switching Power Supply S82J

L-89

Page 12

100 (5, 24 V)-W Models

The Power Supply is provided with an overload protection function that protects the load and the power supply from possible damage by overcurrent. When the output current rises above 105% to 160% of the rated output current, the protection function is triggered, decreasing the output voltage. When the output current falls within the rated range, the overload protection function is automatically cleared.

The Power Supply is provided with an overvoltage protection function that protects the load and the Power Supply from possible damage by overvoltage. When the output voltage rises above a set value (120% of the rated output voltage), the protection function is triggered, shutting off the output voltage. If this occurs, reset the Power Supply by turning it off for 1 minutes min. and then turning it on again.

10- to 100 (24 V)-W Models

100 (5, 12, 15 V)-W, 150-W, and 300-W Models

Intermittent operation

Output voltage (V)

10- to 300-W Models

Output voltage (V)

■ Overvoltage Protection

Output voltage (V)

■ Overload Protection

Rated output voltage

0

50

100

Output current (%)

Overvoltage protection operating

Variable range

Rated value Output current (%)

Note: 1. If the S82J is connected to a load with a built-in DC-DC converter, the overload protection function may be triggered at startup, and consequently the S82J may not operate. 2. Do not continue using the S82J with the output terminals short-circuited or the overcurrent condition continued, otherwise the internal elements of the S82J may be damaged or broken. 3. In actual operation, the output voltage may not fall to 0 V when the overload protection function is triggered. Even with short-circuits on the load side, the drop in voltage will vary depending on factors such as the impedance in the load line. 4. The overload protection function is activated at 105% of the rated output current for 300-W models.

600-W Models If an excessive current flows for 5 s or more, the output will be turned off and simultaneously protection-ON alarm indicator will be lit. To reset the S82J, turn off the input voltage, leave the S82J for at least three minutes, and then apply the input voltage again. Note: Do not continue using the S82J with the output terminals shortcircuited or the overcurrent condition continued, otherwise the internal elements of the S82J may be damaged or broken.

300- and 600-W Models If a voltage that is 120% of the rated output voltage or above is output, the output voltage will be turned off and simultaneously protection-ON alarm indicator will be lit. To reset the S82J, turn off the input voltage, leave the S82J for at least three minutes if it is a 600-W model or at least 90 seconds if it is a 300-W model, and then apply the input voltage again.

■ Overheat Protection Function 600-W Model Only If the internal temperature of the S82J rises excessively as a result of fan failure or any other reason, the overheat protection circuit will be triggered to protect the internal elements of the S82J and simultaneously a protection-ON alarm indicator will be lit. To reset the S82J, turn off the input voltage, leave the S82J for at least three minutes, and then apply the input voltage again.

■ Inrush Current, Startup Time, Hold Time Input ON AC input voltage

Input OFF

Inrush current on input application AC input current 96.5%

90% Output voltage

L-90

Switching Power Supply S82J

Startup time

Hold time (20 ms min.)

Page 13

Dimensions Note: All units are in millimeters unless otherwise indicated. Open-frame type and covered type have the same dimensions.

■ Front-mounting Bracket Type 12 max.

S82J-010@@@ (10 W)

90±1

Mounting Holes (Surface Screw Mounting)

3.5

Side Mounting 65±0.5

97±1 Two, M3

5 65±0.5

5

82±0.5

6.5

Two, 3.5 dia. 3.5 dia. 78±0.5

M3.5 terminal screw

82±0.5 3.5

28

17.5 50±0.5

15

Bottom Mounting

35±1

Two, M3

Two, M3 For track mounting bracket (4 mm deep max.) 78±0.5

124±1

12 max.

S82J-025@@@ (25 W)

Mounting Holes (Surface Screw Mounting)

3.5

Side Mounting 65±0.5

97±1

Two, M3

6 5

116±0.5

6.5

Two, 3.5 dia. 3.5 dia. 112±0.5

M3.5 terminal screw

116±0.5 3.5

Bottom Mounting 28

17.5 21.5

83±0.5

65±0.5

Two, M3

40±1

Two, M3 For track mounting bracket (4 mm deep max.)

112±0.5

S82J-050@@@ (50 W) 12 max.

161±1

Mounting Holes 3.5

Side Mounting Two, M3 65±0.5

97±1 65±0.5

7 5

153±0.5

153±0.5

Two, 3.5 dia.

M3.5 terminal screw

3.5 dia.

20

10 22

127±0.5

Bottom Mounting

3.5 20±0.5 28

40±1

Three, M3 For track mounting bracket (4 mm deep max.)

Power Supplies

150.5±0.5

6.5

Two, M3

150.5±0.5

Switching Power Supply S82J

L-91

Page 14

12 max.

S82J-10024@ (100 W, 24-V Output)

170±1

Mounting Holes 4.5

Side Mounting Two, M3 97±1 65±0.5 65±0.5

162±0.5 162±0.5

5

M3.5 terminal screw

7

4.5 dia. Three, M4 6.5 4.5 dia.

Bottom Mounting

160±0.5

Two, M3

4.5 25±0.5

27.5

50±1 28±0.5

15 15

S82J-100@@@ (100 W, 5-/12-/15-V Output) S82J-15024@ (150 W)

160±0.5

100±0.5 198 (see note) 188 4 max.

Mounting Holes (Surface Screw Mounting) Side Mounting

4.5 8.1

89±0.5

Two, M4

97

9.5 82±0.8 M4 x 8

7±0.3 4.5 dia.

3±0.25

180±0.5

180±0.5

Mounting holes (on both sides) 178±0.5

4.5 dia.

3±0.25

Note: Top terminal and connector models are 188 mm wide.

Bottom Mounting Two, M4

4.5

27.5±0.3

Three, M4 (6 mm max. deep)

S82J-30024@ (300 W) Nine, M4 terminal screws 4 max.

(19)

100±0.5

25±0.5 50 35±0.5 15

178±0.5

55±0.3

Eight, M4 holes (depth: 8 max. on both sides)

Mounting Holes (Surface Screw Mounting) Side Mounting Side Four, 4.5 dia.

50±0.5

Four, M4 holes (depth: 8 max.) 150±0.5

Bottom Mounting Four, 4.5 dia.

100±0.5

150±0.5

L-92

Switching Power Supply S82J

Page 15

S82J-60024@ (600 W) Eight, M4 holes (depth: 8 max. on both sides)

Mounting Holes (Surface Screw Mounting) Side Mounting Four, 4.5 dia.

50±0.5

Four, M4 holes (depth: 8 max. on one side) Four, M4 holes (depth: 8 max.)

150±0.5

Bottom Mounting

Nine, M4 terminal screws

Four, 4.5 dia.

100±0.5

150±0.5

Dimensions with Mounting Bracket (Provided) 10-/25-/50-/100 (24 V)-W Models Mounting Holes 11

1.5

Using the Mounting Bracket Attach the mounting bracket to the panel and loosely tighten the two screws. Insert the projected parts of the bracket (b) to the square holes of the power supply (a). Then securely tighten the screws.

4.6 15±0.2

9

60

Two, 3.5 dia.

74

Two, M3

60

Note: The mounting screws are order separately.

4.6 11 5

20 20

31.5 4.7

(b)

15 t=1.0

(a)

20.5

Power supply unit

Mounting bracket

(b)

(a)

100- (5, 12, 15 V) and 150-W Models

Mounting with Brackets

Mounting bracket

6.5 11

Power Supplies

5 dia.

120 max. 110±0.5

23.5

1.5 30±0.5

Two, 5 dia.

38 t=0.8

Note: The brackets are for front-mounting.

Switching Power Supply S82J

L-93

Page 16

300-W Models

10 dia.

Two, 5 dia.

Note: To provide ventilation space, the body will shift forward by 21.6 mm from the mounting surface. t= 1.6

600-W Models

Note: To provide ventilation space, the body will shift forward by 23.6 mm from the mounting surface.

L-94

Switching Power Supply S82J

Page 17

■ DIN Track Mounting Bracket Type S82J-010@@@D (10 W)

7 max.

12 max.

9 max. when slided out

S82J-025@@@D (25 W)

7 max.

12 max.

9 max. when slided out

S82J-050@@@D (50 W)

7 max.

12 max.

9 max. when slided out

7 max.

12 max.

9 max. when slided out

Power Supplies

S82J-10024@D (100 W, 24-V Output)

Switching Power Supply S82J

L-95

Page 18

S82J-100@@@D (100 W, 5-/12-/15-V Output) S82J-15024@D (150 W) 7 max. 4 max.

9 max. when slided out

■ DIN Track Mounting Bracket (Order Separately) Can be used with 10-W to 150-W Front-mounting Bracket models. If DIN track mounting is necessary, use a DIN Track Mounting Bracket. Refer to the S82Y DIN Track Mounting Bracket datasheet for details.

■ Front-mounting Bracket for S82J-10024@ Power Supply (Order Separately) Product Front-mounting Bracket

Model number

Dimensions

S82Y-J10F

Mounting hole dimensions Three, 4.5-dia. holes

40

Three, M4

50

50

180

Note: These Front-mounting Brackets cannot be used with S82J 100-W (5, 12, or 15-V) or 150-W models.

Switching Power Supply S82J

20

15 t = 1.6

L-96

(Unit: mm)

15

Page 19

Precautions Mounting

100 (5, 12, 15 V)/150-/300-/600-W Models

To improve and maintain the reliability of the Power Supply over a long period of time, adequate consideration must be given to heat radiation.

(A) Side mounting (except for 300- and 600-W models)

The Power Supply is designed to radiate heat by means of natural air-flow. Therefore, mount the Power Supply so that air flow takes place around the Power Supply.

(C) Bottom mounting (secured with screws from the back of the Switching Power Supply)

(B) Bottom mounting (secured with screws from the inside of the Switching Power Supply) (except for 300- and 600-W models)

When mounting the Power Supply, mounting it to a metal plate is recommended. When mounting two or more Power Supplies side-by-side, allow at least 20 mm spacing between them, as shown in the following illustration.

(B)

Forced air-cooling is recommended.

(A)

Air (C)

20 mm min.

Metal plate

(D) Front mounting Front mounting is possible with the mounting brackets provided. Refer to Dimensions.

Mounting Methods The following mounting methods are available.

10-/25-/50-/100 (24 V)-W Models (A) Side mounting (B) Bottom mounting (C) Front mounting (see Accessories) Mounting brackets (provided) Metal plate

(B)

Power Supplies

(A)

Switching Power Supply S82J

L-97

Page 20

Generating Output Voltage (±) An output of ± can be generated by using two Power Supplies as shown below, because the Power Supply produces a floating output.

INPUT

+V

+V

−V

Load

+V

Load

Parallel Operation Only 300- and 600-W models can be in parallel operation. Do not operate any other models in parallel. The output of the models in parallel operation is a maximum of 80% of the rated output.

0V

INPUT

−V

With the S82J-050@@@@ or S82J-10024@@, if the load is shorted a reverse voltage may result in the Power Supply causing deterioration and damage. It is recommended that diodes are connected as shown in the previous diagram (D1, D2).

−V

If operation amplifiers as loads are connected in series, connect a diode between the positive and negative output terminals of each Switching Power Supplies as shown in the illustration below. Without these diodes, the Power Supply may not start when power is turned on, possibly damaging internal circuits over a period of time. Use Schottky barrier diodes with a low forward voltage (VF). Other types of diodes will not be effective. Guidelines for the dielectric strength and current of the diodes are as follows:

Set the parallel operation selector to PARALLEL if the Units are in parallel operation and make sure that the thickness and the length of all wires connected to the load are the same to ensure that the wires will have no voltage drop differences.

Fan Replacement The service life of the fan is approximately 50,000 hours (at 25°C). The service life varies, however, depending on the ambient temperature or other surrounding environmental conditions such as dust. As a preventive maintenance measure, replace the fan within two years if it is used at an ambient temperature of 40°C. Fans are available as replacements.

Dielectric strength: At least twice the rated output voltage of the Power Supply Forward current: At least twice the rated output current No diodes are required for models that allow series operation. +V INPUT

D1

Load

−V

Load Load

+V D2

INPUT −V

Model: S82Y-JFAN

Series Operation Only models with power ratings of 50/100/150/300/600 W allow series operation. As shown in the following diagram, the output voltage from each Switching Power Supply can be added. +V

Fan Set: Fan (above), four M4 x 35 sems screws, instruction sheet, and packing case Replace the fan as shown in the following illustration.

D1

INPUT −V Load +V INPUT

−V D2

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. M047-E1-07

L-98

In the interest of product improvement, specifications are subject to change without notice.

Switching Power Supply S82J