Page 1
Appendix B. EVM32 Installation
Connect to the 6K’s “EXPANSION I/O” connector (use the provided cable).
EVM32 Brick #1 st (1 unit in serial chain)
EVM32 Brick #2 nd (2 unit in serial chain)
2-foot (0.61 m) cable is provided with the baseboard (EVM32-BASE). SIM boards are ordered separately from the baseboard.
Baseboard (EVM32-BASE).
EVM32 Description The EVM32 is a family of I/O modules (or “bricks”) that is sold as accessories to the 6K Controllers. The purpose of the EVM32 is to provide more I/O than the 6K offers onboard. Up to eight DIN-rail mountable EVM32 bricks can be connected in a serial chain to the 6K. Each EVM32 brick can hold from 1 to 4 of these I/O SIM boards in any combination (each SIM board provides 8 I/O points, for a total of 32 I/O points per I/O brick): • Digital inputs • Digital outputs • Analog inputs Order an EVM32 brick and up to four I/O SIM boards per brick (see table below). Product (p/n)
Description
EVM32-Base............ EVM32 baseboard, extrusion with built-in DIN rail mount (includes 2-foot cable). SIM8-IN.................... SIM board with 8 digital inputs. Color code: RED. SIM8-OUT-EVM32 ... SIM board with 8 digital outputs. Color code: BLUE. SIM8-AN-IN.............. SIM board with 8 analog inputs (12-bit, ±10V inputs). Color code: GREEN. 71-016949-02........... 2-foot cable for connection to 6K or between I/O bricks (included with EVM32-BASE). 71-016949-100......... 100-foot cable for connection to 6K or between I/O bricks.
Page 2
EVM32 Specifications Parameter
Specification
Power (DC input) V+ ..................................................................... User-supplied voltage that drives output circuitry. V+ range ........................................................... 12-24VDC. V+ current ......................................................... 1.5A @ 12VDC or 0.75A @ 24VDC; plus the sum of the load current on outputs that are in sourcing mode. Environmental Operating temperature ...................................... 32 to 122°F (0 to 50°C) Storage temperature ......................................... -22 to 185°F (-30 to 85°C) Humidity ............................................................ 0 to 95% non-condensing Dimensions EMV32 module ................................................. 3.3 inches x 6.25 inches (83.82 mm x 158.75 mm) Digital Inputs Switching levels ................................................ Low ≤ 1/3 V+ voltage; High ≥ 2/3 V+ voltage. Voltage range ................................................... Voltage range = 0-24VDC. Voltage of input signals should not exceed voltage level of V+. (Input circuitry of EVM32 has diodes to protect against voltages that exceed V+, but performance may degrade.) Sinking/Sourcing ............................................... Sinking: Connect jumper for selected SIM board to position 3 (factory default). Sourcing: Connect jumper for selected SIM board to position 1. Impedance ........................................................ 6 KΩ, minimum. Requires input current (sinking or sourcing) of 0.111mA per volt of user-supplied voltage to V+ (e.g., 2.67mA if V+ = 24V). Active level ....................................................... Set by the 6K controller (INLVL command setting), default is active low, but can be set to active high. Input frequency ................................................. 50 kHz (the maximum frequency is limited practically to 500 Hz by the 2 ms update rate of the 6K controller). Status ............................................................... Check with the TIO command. Digital Outputs Sinking/Sourcing ............................................... Sinking: Connect jumper for selected SIM board to position 3 (factory default). Sourcing: Connect jumper for selected SIM board to position 1. Voltage (sinking, jumper in position 3) ........... Output voltage level is less than or equal to 0.4VDC when sinking up to 50mA. (≤ 0.4 VDC for 50 mA). Output voltage level is less than or equal to 2.5VDC when sinking up to 300mA. (≤ 2.5 VDC for 300 mA). Voltage (sourcing, jumper in position 1) ......... Output voltage level may be up to 2 volts less than the user-supplied voltage V+ when sourcing up to 50mA. Output voltage level may be up to 2.5 volts less than the user-supplied voltage V+ when sourcing up to 300mA. Current .............................................................. 300mA maximum per output; continuous duty at 50°C ambient temperature. Active level ....................................................... Set with the OUTLVL command, default is active low. Rise time, Fall time ........................................... Load dependent; typically 40ns per 1000 pF. Under-voltage protection ................................... The under-voltage lockout circuit is meant to prevent the output driver from sinking or sourcing when the user-supplied voltage at V+ drops below +5VDC. Thermal shutdown ............................................ The thermal shutdown protection is intended to protect the device from marginal environmental factors. It must not be considered short circuit protection. The thermal resistance between the FET junction and the thermal protection circuit on the SIM cards is great enough that the rapid rise in junction temperature caused by a short circuit will not transfer fast enough to protect the device from damage. Short-circuit protection ...................................... Digital outputs are NOT short-circuit protected. Status ................................................................ Check with the TIO command. Analog Inputs Input voltage range ........................................... 12-bit A/D converter, ±10VDC; unipolar/bipolar range selectable ANIRNG command. Unipolar: 0V to 10VDC, or 0V to 5V; Bipolar: -10 to +10V (factory default), or -5V to +5V. Input current (worst case load) .......................... Unipolar: 720µA @ 0V to 10VDC range; 360µA @ 0V to 5V range. Bipolar: -1200µA @ -10V and 720µA @ +10V; -600µA @ -5V and 360µA @ +5V. Input dynamic resistance .................................. Unipolar: 21KΩ; Bipolar: 16KΩ Fault tolerance .................................................. ±16.5V Sample rate ...................................................... Each input requires 2ms (e.g., 4 ms for 2 inputs, 16ms for 8 inputs); therefore, to maximize performance, you should disable unused inputs with ANIEN command. Status ................................................................ Check with the TIO command.
44
6K Hardware Installation Guide
Page 3
Installing the SIM Boards
CAUTION: Remove power to the EMV32 baseboard before installing or removing SIM boards.
SIM slot for I/O points 25-32 SIM slot for I/O points 17-24 SIM slot for I/O points 9-16 SIM slot for I/O points 1-8
SIM Board Color Codes SIM8-IN (digital inputs).......................RED SIM8-OUT-EVM32 (digital outputs) ....BLUE SIM8-AN-IN (analog inputs) ...............GREEN
Notch
Setting Jumpers (selecting sinking/sourcing) SIM4 (25-32)
SIM3 (17-24)
SIM2 (9-16)
SIM1 (1-8)
NOTE: The jumper setting affects only digital inputs (SIM8-IN) and digital outputs (SIM8-OUT-VM32).
Position 3 selects sinking (factory default setting) JU4
JU3
JU2
JU1
Position 1 selects sourcing
3 2 1
Appendix B. EVM32 Installation
45
Page 4
Electrical Connections Connection to the 6K controller and between VM32 I/O bricks
! #####&$87,21##### ! Remove power to the 6K controller and the EMV32 baseboard before connection or disconnecting the EVM32 baseboard to the 6K controller or to other EVM32 units.
If the VM32 I/O brick is disconnected (or if it loses power), the controller will perform a kill (all tasks) and set error bit #18. When the 6K controller powers up and detects an output SIM on a VM32, it will set the active level (OUTLVL command) according to the jumper setting selected. To check the status of one or more VM32 I/O bricks, use the TIO command.
Connect to the 6K’s “EXPANSION I/O” connector (use the provided cable).
EVM32 Brick #1 st (1 unit in serial chain) EVM32 Brick #2 nd (2 unit in serial chain) 2-foot (0.61 m) cable is provided with the baseboard (EVM32-BASE). Optional 100-foot cable is available.
24VDC power input Power Supply 12-24VDC 1.5A @ 12VDC or 0.75A @ 24VDC; plus the sum of the load current on outputs that are in sourcing mode. Connect to V+ V+ V+ GND V+
Connect to GND
46
6K Hardware Installation Guide
Page 5
Digital Inputs
CAUTION: Remove power to the EMV32 baseboard before connecting I/O.
External Supply (12 to 24VDC)
Sinking
+
EVM32
Electronic Device
JUMPER 3 2
V+ The output should be able to sink at least 3mA of current.
J1 GND
.
20 0 KW
1
Iso GND
Output
Input Connection
.
10 0 KW
6.81 KW
.
12 1 KW +
V+ .
1500 pF
Ground Connection Ground
Iso Ground 18.2 KW
Iso GND
30 1 KW
Iso GND
External Supply (12 to 24VDC)
Sourcing
+
EVM32
Electronic Device
JUMPER 3
V+ V1 R1
Iso GND
Output
20. 0 KW
2
J1 GND
Input Connection
Iso GND
1 18.2 KW
10. 0 KW
6.81 KW
12. 1 KW
+
Ground Connection
1500 pF
Ground
V+
Iso GND
30. 1 KW
Iso GND
Appendix B. EVM32 Installation
47
Page 6
Digital Outputs
CAUTION: Remove power to the EMV32 baseboard before connecting I/O. NOTE: Use an external diode when driving inductive loads. Connect the diode in parallel to the inductive load.
External Supply (12 to 24VDC)
Sinking
+
EVM32
J1 GND Input Iso GND
1
Electronic Device
V+
Jumper set to position 3 3
Output Connection Ground Connection
Iso GND
External Supply (12 to 24VDC)
Sourcing
+
EVM32
V+
Jumper set to position 1 3 1
6K Hardware Installation Guide
Electronic Device
J1 GND Iso GND
Iso GND
48
Output Connection
Input
Ground Connection
Ground
Page 7
Analog Inputs
EVM32 Bipolar
Analog Input Source (+/- 10V) Signal Source
Input Connection
Unipolar 5.12 KW 12.5 KW
OFF CHold
S2 1.0 MW
Ground
Voltage Reference
S1
S3
GND Connection
T/H Out
ON Track
Hold
8.67 KW Hold
Track
S4
S1 = Bipolar/Unipolar Switch S2 = Input Mux Switch S3, S4 = T/H Switch
Appendix B. EVM32 Installation
49