Page 1
E-STOP relays, safety gate monitors Up to PL e of EN ISO 13849-1 PNOZ X8P ` Safety gates ` Light beam devices
Unit features ` Positive-guided relay outputs: – 3 safety contacts (N/O), instantaneous – 2 auxiliary contacts (N/C), instantaneous ` 2 semiconductor outputs ` Connection options for: – E-STOP pushbutton – Safety gate limit switch – Reset button – Light barriers ` LED indicator for: – Switch status channel 1/2 – Supply voltage ` Semiconductor outputs signal: – Switch status channel 1/2 – Supply voltage is present ` Plug-in connection terminals (either spring-loaded terminal or screw terminal) ` See order reference for unit types Gertemerkmale
Gertebild
Safety relay for monitoring E-STOP pushbuttons and safety gates. ][Bildunterschrift
Approvals
PNOZ X8P ‹
Safety features The relay meets the following safety requirements: ` The circuit is redundant with built-in self-monitoring. ` The safety function remains effective in the case of a component failure. ` The correct opening and closing of the safety function relays is tested automatically in each on-off cycle. ` The tranformer is short circuitproof. An electronic fuse is used on a DC supply. ][Sicherheitseigenschaften Schaltgerät_allgemeiner Teil
Sicherheitseigenschaften Zusatz - AC/DC-Gerte_PNOZ
Unit description
‹
The safety relay meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with ` E-STOP pushbuttons Bestimmung/Gertebeschreibung NOT-AUS, Schutzt, Lichtschr_PNOZ
‹
Zulassungen
Block diagram idl tb a h s k c lo B
A1 A2
~ =
S11 S12 S21 S22 S52 S33 S34 S37
Input
Input
Reset/ Start
13 23 33 41 51 51
K1
Power Feedback
K2 0 V 24 V
Y1 Y2 Y30 Y31 Y32 Y35
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
14 24 34 42 52 52
NSG-D-2-142-2009-09
Page 2
E-STOP relays, safety gate monitors Up to PL e of EN ISO 13849-1 PNOZ X8P Function description ` Single-channel operation: no redundancy in the input circuit, earth faults in the reset and input circuit are detected. ` Dual-channel operation without detection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input circuit, – short circuits in the input circuit and, with a monitored reset, in the reset circuit too. ][Funktionen_einkanalig
][Funktionen_zweikanalig_ohne_quer
` Dual-channel operation with detection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input circuit, – short circuits in the input circuit and, with a monitored reset, in the reset circuit too, – shorts between contacts in the input circuit. ` Automatic start: Unit is active once the input circuit has been closed. ][Funktionen_autoStart
][Funktionen_manuStart
` Manual reset: Unit is active once the input circuit is closed and then the reset circuit is closed. ` Monitored reset: Unit is active once – the input circuit is closed and then the reset circuit is closed and opened again. – the reset circuit is closed and then opened again once the input circuit is closed. ` Increase in the number of available instantaneous safety contacts by connecting contact expansion modules or external contactors. ][Funktionen_berStart_allg
][Funktionen_Kontaktvervielfachung
][Funktionen_zweikanalig_mit_quer_ber
Timing diagram H C N U R s x 1 b n o u _ rm g a itd e ][Z
1
2 a b
3 a b
POWER Reset/Start Input Output safe Output aux. Out semi RUN Out semi CH t1 t2 t1 t1 t2 t2 t1 t2 t1 t1 t2 t2 t3
Key ` Power: Supply voltage ` Reset/Start: Reset circuit S33-S34, Y1-S37 ` Input: Input circuits S21-22, S11S12, S52 ` Output safe: Safety contacts 13-14, 23-24, 33-34 ` Output aux: Auxiliary contacts 4142, 51-52
` Out semi RUN: Semiconductor output supply voltage Y35 ` Out semi CH: Semiconductor output switch status Y32 ` c: Automatic reset ` d: Manual reset ` e: Monitored reset ` a: Input circuit closes before reset circuit
` b: Reset circuit closes before input circuit ` t1: Switch-on delay ` t2: Delay-on de-energisation ` t3: Recovery time
` Calculation of the max. cabling runs lmax in the input circuit:
` Sufficient fuse protection must be provided on all output contacts with capacitive and inductive loads.
Wiring Please note: ` Information given in the “Technical details” must be followed. ` Outputs 13-14, 23-24, 33-34 are safety contacts, outputs 41-42, 5152 are auxiliary contacts (e.g. for display). ` To prevent contact welding, a fuse should be connected before the output contacts (see technical details). ][Verdrahtung_Si_Hi_unverz
Imax =
Rlmax Rl / km
Rlmax = max. overall cable resistance (see technical details) Rl /km = cable resistance/km ` Use copper wire that can withstand 60/75 °C.
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-142-2009-09
-2
Page 3
E-STOP relays, safety gate monitors Up to PL e of EN ISO 13849-1 PNOZ X8P Preparing for operation
Betriebsbereitschaft herstellen
` Supply voltage Supply voltage
AC
DC A1 A2
L1 N
A1
L+
PE
A2
L-
` Input circuit Input circuit E-STOP without detection of shorts across contacts
Single-channel
Dual-channel S11
S1
S11
S21
S12
S21
S22
S52
S22
E-STOP with detection of shorts across contacts
S12 S52
S11
Safety gate without detection of shorts across contacts S11
S11
S21
S52
S22 S12
S1
S11
S21
S12
S22
S21
S52
S22
S1
S1
S1
S2
S12 S52
Safety gate with detection of shorts across contacts
S11
S11 S12
S52
S21
S1
S2
S22
Light beam device with detection of shorts across contacts via ESPE
24 V DC S21 S22
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S12 S52
GND
NSG-D-2-142-2009-09
Page 4
E-STOP relays, safety gate monitors Up to PL e of EN ISO 13849-1 PNOZ X8P ` Reset circuit Reset circuit
E-STOP/safety gate wiring (single-channel and dual-channel without shorts across contacts)
Automatic reset
E-STOP/safety gate wiring (dual-channel with shorts across contacts)
S33
S12
S34
S34
Manual reset
S3
S3
S33
S12
S34
S34
Monitored reset
S3
S3
S33 S34
S12 S34
Y1
Y1
S37
S37
` Feedback circuit Feedback circuit Contacts from external contactors
Automatic reset
Monitored reset Y1 Y2
13 (23, 33) 14 (24, 34)
K5
Y1 Y2
K6 K5
L1 N
K6
13 (23, 33) 14 (24, 34)
K5
K6 K5
L1 N
K6
` Semiconductor output
Y31
24 V DC
Y32 Y35
SPS Input
Y30
0V
SPS Input
` Key S1
E-STOP pushbutton
S3
Reset button Switch operated Gate open Gate closed
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-142-2009-09
-4
Page 5
E-STOP relays, safety gate monitors Up to PL e of EN ISO 13849-1 PNOZ X8P Terminal configuration u g b n m le K
A1 S33 S34 S52 S11 13 23 33 P3 S11 S12 S12 S21 S22 41 51 51 P4 13 23 33 41 51 PNOZ X8P POWER 14 24 34 42 52
CH.1 IN
CH. 1
CH.2 IN
CH. 2
95157
START
P3 42 52 52 Y30 Y31 Y32 Y35 P4 A2 Y1 Y2 Y1 S37 14 24 34
` The safety relay should be installed in a control cabinet with a protection type of at least IP54. ` Use the notch on the rear of the unit to attach it to a DIN rail. ` Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing element (e.g. retaining bracket or an end angle). Montage_PNOZ_X
Dimensions * with spring-loaded terminals Abmessungen
121 (4.76")
Installation
94 (3.70") * 101 (3.98")
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
45 (1.77")
NSG-D-2-142-2009-09
Page 6
E-STOP relays, safety gate monitors Up to PL e of EN ISO 13849-1 PNOZ X8P Notice This data sheet is only intended for use during configuration. For installation and operation, please refer to the operating instructions supplied with the unit.
Service life graph
][WICHTIG_PDB_alt v rk u a d s n b e L
Nennbetriebstrom (A) Nominal operating current (A) Courant coupé (A)
10 AC15: 230 V DC1: 24 V DC13: 24 V 1
0.1
10
100
AC1: 230 V
1000 Schaltspielzahl x 103 Cycles x 103 Nombre de manœuvres x 103
10000
][Technische Daten PNOZ
Technical details Electrical data Supply voltage Supply voltage UB AC Supply voltage UB DC Voltage tolerance Power consumption at UB AC Power consumption at UB DC Frequency range AC Residual ripple DC Voltage and current at Input circuit DC: 24.0 V
Reset circuit DC: 24.0 V
Feedback loop DC: 24.0 V
Number of output contacts Safety contacts (S) instantaneous: Auxiliary contacts (N/C): Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V Safety contacts: DC1 at 24 V Auxiliary contacts: AC1 at 240 V Auxiliary contacts: DC1 at 24 V Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V Safety contacts: DC13 at 24 V (6 cycles/min) Auxiliary contacts: AC15 at 230 V Auxiliary contacts: DC13 at 24 V (6 cycles/min)
24 V, 110 V, 115 V, 120 V, 230 V 24 V -15 %/+10 % 6.5 VA Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 2.5 W Order no.: 777760, 787760 50 - 60 Hz 160 % 40.0 mA Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 45.0 mA Order no.: 777760, 787760 50.0 mA Order no.: 777760, 787760 60.0 mA Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 50.0 mA Order no.: 777760, 787760 60.0 mA Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 3 2 Imin: 0.01 A , Imax: 8.0 A Pmax: 2000 VA Imin: 0.01 A , Imax: 8.0 A Pmax: 200 W Imin: 0.01 A , Imax: 8.0 A Pmax: 2000 VA Imin: 0.01 A , Imax: 8.0 A Pmax: 200 W Imax: 5.0 A Imax: 7.0 A Imax: 5.0 A Imax: 7.0 A
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-142-2009-09
-6
Page 7
E-STOP relays, safety gate monitors Up to PL e of EN ISO 13849-1 PNOZ X8P Electrical data Contact material External contact fuse protection (IK = 1 kA) to EN 60947-5-1 Blow-out fuse, quick Safety contacts: Auxiliary contacts: Blow-out fuse, slow Safety contacts: Auxiliary contacts: Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: Auxiliary contacts: Semiconductor outputs (short circuit proof) External supply voltage Voltage tolerance Max. overall cable resistance Rlmax input circuits, reset circuits single-channel at UB DC single-channel at UB AC dual-channel without detect. of shorts across contacts at UB DC dual-channel without detect. of shorts across contacts at UB AC dual-channel with detect. of shorts across contacts at UB DC dual-channel with detect. of shorts across contacts at UB AC Safety-related characteristic data PL in accordance with EN ISO 13849-1 Category in accordance with EN 954-1 SIL CL in accordance with EN IEC 62061 PFH in accordance with EN IEC 62061 SIL in accordance with IEC 61511 PFD in accordance with IEC 61511 tM in years Times Switch-on delay with automatic reset typ.
with automatic reset max.
with automatic reset after power on typ.
with automatic reset after power on max.
with manual reset typ. with manual reset max. on monitored reset with rising edge typ. on monitored reset with rising edge max.
AgSnO2 + 0.2 µm Au
10 A 10 A 6A 6A 6A 6A 24.0 V DC,50 mA 24.0 V DC -20 %/+20 %
100 Ohm Order no.: 777760, 787760 100 Ohm Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 200 Ohm Order no.: 777760, 787760 200 Ohm Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 16 Ohm Order no.: 777760, 787760 28 Ohm Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 PL e (Cat. 4) Cat. 4 SIL CL 3 2.31E-09 SIL 3 2.03E-06 20
160 ms Order no.: 777760, 787760 175 ms Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 200 ms Order no.: 777760, 787760 220 ms Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 185 ms Order no.: 777760, 787760 200 ms Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 220 ms Order no.: 777760, 787760 250 ms Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 190 ms 250 ms 130 ms 180 ms
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-142-2009-09
Page 8
E-STOP relays, safety gate monitors Up to PL e of EN ISO 13849-1 PNOZ X8P Times Delay-on de-energisation with E-STOP typ. with E-STOP max. with power failure typ.
with power failure max.
Recovery time at max. switching frequency 1/s after E-STOP after power failure
Min. start pulse duration with a monitored reset with rising edge Simultaneity, channel 1 and 2 Supply interruption before de-energisation Environmental data EMC Vibration to EN 60068-2-6 Frequency Amplitude Climatic suitability Airgap creepage in accordance with EN 60947-1 Pollution degree Overvoltage category Rated insulation voltage Rated impulse withstand voltage Ambient temperature Storage temperature Protection type Mounting (e.g. cabinet) Housing Terminals Mechanical data Housing material Housing Front Cross section of external conductors with screw terminals 1 core flexible 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve without crimp connectors or with TWIN crimp connectors Torque setting with screw terminals Cross section of external conductors with spring-loaded terminals: Flexible with/without crimp connectors Spring-loaded terminals: Terminal points per connection Stripping length
15 ms 30 ms 100 ms Order no.: 777760, 787760 160 ms Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 150 ms Order no.: 777760, 787760 220 ms Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 50 ms 180 ms Order no.: 777760, 787760 250 ms Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 30 ms 150 ms 35 ms EN 60947-5-1, EN 61000-6-2 10 - 55 Hz 0.35 mm EN 60068-2-78 2 III 250 V 4.0 kV -10 - 55 °C -40 - 85 °C IP54 IP40 IP20
PPO UL 94 V0 ABS UL 94 V0 0.25 - 2.50 mm² , 24 - 12 AWG Order no.: 777760, 777764, 777765, 777766, 777768, 777770 0.25 - 1.00 mm² , 24 - 16 AWG Order no.: 777760, 777764, 777765, 777766, 777768, 777770 0.20 - 1.50 mm² , 24 - 16 AWG Order no.: 777760, 777764, 777765, 777766, 777768, 777770 0.50 Nm Order no.: 777760, 777764, 777765, 777766, 777768, 777770 0.20 - 1.50 mm² , 24 - 16 AWG Order no.: 787760, 787764, 787765, 787766, 787768, 787770 2 Order no.: 787760, 787764, 787765, 787766, 787768, 787770 8 mm Order no.: 787760, 787764, 787765, 787766, 787768, 787770
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-142-2009-09
-8
Page 9
E-STOP relays, safety gate monitors Up to PL e of EN ISO 13849-1 PNOZ X8P Mechanical data Dimensions Height
101.0 mm Order no.: 787760, 787764, 787765, 787766, 787768, 787770 94.0 mm Order no.: 777760, 777764, 777765, 777766, 777768, 777770 45.0 mm 121.0 mm 310 g Order no.: 787760 320 g Order no.: 777760 410 g Order no.: 787764, 787765, 787766, 787768, 787770 420 g Order no.: 777764, 777765, 777766, 777768, 777770
Width Depth Weight
Technische Daten_Satz Normen
The standards current on 2006-06 apply. ][Dauerstrom_ACDC
Conventional thermal current Number of contacts 1
Ith (A) at UB DC 8.00 A Order no.: 777760, 787760
2
8.00 A Order no.: 777760, 787760
3
7.00 A Order no.: 777760, 787760
Ith (A) at UB AC 8.00 A Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 7.30 A Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770 6.00 A Order no.: 777764, 777765, 777766, 777768, 777770, 787764, 787765, 787766, 787768, 787770
Bestelldaten
Order reference Type PNOZ X8P C PNOZ X8P PNOZ X8P C PNOZ X8P PNOZ X8P C PNOZ X8P PNOZ X8P C PNOZ X8P PNOZ X8P C PNOZ X8P PNOZ X8P C PNOZ X8P
Features 24 VDC 24 VDC 110 VAC 110 VAC 115 VAC 115 VAC 120 VAC 120 VAC 230 VAC 230 VAC 24 VAC 24 VAC
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Terminals Spring-loaded terminals Screw terminals Spring-loaded terminals Screw terminals Spring-loaded terminals Screw terminals Spring-loaded terminals Screw terminals Spring-loaded terminals Screw terminals Spring-loaded terminals Screw terminals
Order no. 787 760 777 760 787 764 777 764 787 765 777 765 787 766 777 766 787 768 777 768 787 770 777 770
NSG-D-2-142-2009-09