Manual · Pilz
PZA Operating instructions
Manual12 pagesPDF 589 KB
Multilingual operating instructions for the Pilz PZA 3/30/300/600 delay-on energisation timer relay used in safety circuits.
Covers · 1 model
The models it covers
Summary
What is in it
Pilz operating instructions, in German, English, French, Spanish, Italian and Dutch, for the PZA 3/30/300/600 timer relay, a delay-on energisation unit for delayed unlocking of guards, used with PNOZ safety relays and PST safety gate monitors. They cover safety regulations, authorized applications, the unit description and function, installation, operation, an application example with a PNOZ 6, faults, technical data, relay service life and dimensions.
From the manual
Key facts from this manual
Each line names its page in the PDF.
Operating instructions 18 219-05 for the Pilz PZA 3/30/300/600 delay-on energisation timer relay, printed in several languages. They cover intended use, how the timer works, installation and start-up, a connection example with a PNOZ 6, fault behavior and the technical data.
- What it is
- Delay-on energisation timer relay in a P-97 housing, in several AC versions and one DC version p. 1
- Outputs
- One safety contact (N/O) 17-18 and two auxiliary contacts (N/C) 25-26 and 35-36, positive-guided p. 1, 2
- Supply voltage
- AC: 24 V, 42 V, 110 - 120 V, 230 V; DC: 24 V; tolerance -15 % ... +10 % p. 4
- Delay times
- 12 steps: PZA 3 0.3 to 3.0 s; PZA 30 3 to 30 s; PZA 300 30 to 300 s; PZA 600 60 to 600 s; repetition accuracy +/-1 % p. 4
- Power consumption
- AC: 4.5 VA; DC: 3 W p. 4
- Contact ratings
- AC1: 240 V/0.01 ... 6 A/1500 VA; DC1: 24 V/0.01 ... 6 A/150 W; AC15: 230 V/4 A; DC13: 24 V/3 A p. 4
- LEDs
- "power" lights with operating voltage; "out" lights when the delay ends and the safety contact closes p. 3
- Input circuit
- Operating voltage on terminals A1 (+) and A2 (-); applying it starts the delay p. 2
- Feedback loop
- Y1-Y2, bridged or wired to external contactors/relays; 50.0 mA p. 2, 4
- External contact fuse
- 6 A quick acting or 4 A slow acting; 24 V AC/DC: 4 A, characteristic B/C p. 4
- Mounting
- DIN rail, in a panel of at least IP 54; housing IP 40, terminals IP 20 p. 2, 4
- Wire size
- 1 flexible core 0.20 ... 4.00 mm2 (24-10 AWG); terminal screw torque 0.6 Nm p. 4
- Weight
- AC: 350 g, DC: 260 g p. 4
- Contact material
- AgSnO2 + 0.2 µm Au p. 4
What this manual walks you through
- Setting the delay and starting up the timer relay p. 2
- The operating sequence of contacts and LEDs p. 2, 3
- Connection example with a PNOZ 6 safety gate monitor p. 3
- Mounting the unit on a DIN rail p. 2
- What happens on an internal fault p. 3
- Service life of the output relays (graph) p. 5
Good to know
- Only contact 17-18 is a safety contact; 25-26 and 35-36 are auxiliary contacts, for example for monitoring. p. 2
- A fuse must be connected before the output contacts to prevent contact welding. p. 2
- Connect the unit only as in the connection example and leave unlabelled terminals unconnected. p. 3
- Output contacts with capacitive and inductive loads need adequate protection and suppression. p. 1
- The EN 954-1 category reached depends on the base unit, and the PZA may not exceed it. p. 1
Questions this manual answers
What is the difference between the PZA 3, PZA 30, PZA 300 and PZA 600?
The delay range: 0.3 to 3.0 s, 3 to 30 s, 30 to 300 s and 60 to 600 s, each in 12 steps. p. 4
What happens if the PZA timer relay has a fault?
The safety contact stays open, the auxiliary contacts stay closed and the time period defaults to infinity. p. 3
What do the power and out LEDs on the PZA show?
"power" lights when operating voltage is applied; "out" lights once the set time has elapsed and the safety contact has closed. p. 3
How do I put the PZA into operation?
Turn the rotary switch to the delay with a screwdriver, bridge Y1-Y2 or connect external contactors, then connect the operating voltage to A1 (+) and A2 (-). p. 2
Which Pilz units is the PZA used with?
Safety relays from the PNOZ range and safety gate monitors from the PST range. p. 1
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file