Page 1
Common Memory Module
(M/N 57C413B) (M/N 57C423)
Industrial
CONTROLS
Instruction Manual J-3636-2 eS ELECTRIC#al
Page 2
The information in this user's manual is subject to change without notice. DANGER ONLY QUALIFIED ELECTRICAL PERSONNEL FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THIS EQUIPMENT AND THE HAZARDS INVOLVED SHOULD INSTALL, ADJUST, OPERATE, AND/OR SERVICE THIS EQUIPMENT. READ AND UNDERSTAND THIS MANUAL IN ITS ENTIRETY BEFORE PROCEEDING. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.
WARNING INSERTING OR REMOVING A MODULE MAY RESULT IN UNEXPECTED MACHINE MOTION. POWER TO THE MACHINE SHOULD BE TURNED OFF BEFORE INSERTING OR REMOVING THE MODULE. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT IN BODILY INJURY.
WARNING THIS MODULE CONTAINS STATIC-SENSITIVE COMPONENTS. DO NOT TOUCH THE CONNECTORS ON THE BACK OF THE MODULE. WHEN NOT IN USE, THE MODULE SHOULD BE STORED IN AN ANTI-STATIC BAG. THE PLASTIC COVER SHOULD NOT BE REMOVED. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN DAMAGE TO OR DESTRUCTION OF THE EQUIPMENT.
ReSourcet and AutoMaxt are trademarks of Reliance Electric Company or its subsidiaries. Reliancer is a registered trademark of Reliance Electric Company or its subsidiaries.
Page 3
Table of Contents 1.0
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2.0
Mechanical/Electrical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.1 Mechanical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.1.1 Checking the Status of the On-Board Battery . . . . . . . . . . 2-1 2.2 Electrical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
3.0
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.1 Initial Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.2 Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 3.3 On-Board Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
4.0
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 4.1 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 4.1.1 Variable Control and Access . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 4.1.2 Variable Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 4.1.3 Configuration Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 4.2 Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 4.2.1 Rack Slot Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3 4.2.2 Remote Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
5.0
Diagnostics and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5.1 The WATCHDOG" LED is Off . . . . . . . . . . . . . . . . . . . . . 5-1 5.2 The LED is Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5.3 Incorrect Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5.4 Bus Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
I
Page 4
Appendices Appendix A Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 Appendix B Module Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1 Appendix C Configuring the Common Memory Module in DCS 5000 or AutoMax V 2.1 or Earlier Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1 Appendix D Summary of Common Memory Module Features . . . . . . . . . . . . . . . . D-1 Appendix E How Removing/Replacing the Common Memory Module Affects Tasks and Variables in a DCS 5000 Rack . . . . . . . . . . . . . . . . E-1 Appendix F How Removing/Replacing the Common Memory Module Affects Tasks and Variables in an AutoMax Rack . . . . . . . . . . . . . . . . F-1
II
Page 5
Figure 2.1 Figure 3.1
List
- Module Faceplate of Figures
- Rack Slot Numbers .......... 0.00 cc cece cece eee eens
Page 6
afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd
Page 7
1.0 INTRODUCTION The products described in this instruction manual are manufactured or distributed by Reliance Electric Industrial Company. The Common Memory module (57C413B and 57C423) is required in slot 0 of a DCS 5000/AutoMax rack that contains more than one Processor module. The Common Memory module stores the configuration data that must be shared among Processors, such as definitions of physical I/O. This frees Processor module memory for application tasks. The Common Memory module also arbitrates the Processors' access to the bus. The Common Memory module may also be placed in slot 0 of a single-Processor rack. As in the case above, the configuration data which normally resides on the Processor module in a single-Processor rack is stored on the Common Memory module. When the Common Memory module is placed in any even slot other than 0, it is used for userĆdefinable data storage only. This mode is useful if you need to control explicitly the physical allocation of memory, e.g., to define consecutive registers for shaft register instructions. Note, however, that it is not possible to define arrays in this mode. The module incorporates bus arbitration logic, a system watchdog for multiĆprocessing, and batteryĆbacked RAM for data storage. When used in slot 0, M/N 57C413B has 128K bytes (64K registers) of memory; M/N 57C423 has 256K bytes (128K registers) of memory. Both versions of the module make available 128K bytes only when used in any even slot other than 0. An onĆboard lithium battery and a superĆcapacitor protect the Common Memory module from power failures. Note that the battery backup is designed to maintain the contents of RAM only. It is not a source of uninterruptible power. Should the rack lose power, the onĆboard battery can maintain the contents of RAM for a minimum of 600 days. This manual describes the functions and specifications of the module. It also includes a detailed overview of installation and servicing procedures, as well as examples of programming methods. Unless specifically noted otherwise, the information in this manual describes both the M/N 57C413B and M/N 57C423 Common Memory modules. Related publications that may be of interest: D J-3630
ReSource AutoMax PROGRAMMING EXECUTIVE INSTRUCTION MANUAL VERSION 1.0
D J-3649
AutoMax CONFIGURATION TASK MANUAL
D J-3650
AutoMax PROCESSOR MODULE INSTRUCTION MANUAL
D J-3675
AutoMax ENHANCED BASIC LANGUAGE INSTRUCTION MANUAL
D J-3676
AutoMax CONTROL BLOCK LANGUAGE INSTRUCTION MANUAL
D J-3677
AutoMax LADDER LOGIC LANGUAGE INSTRUCTION MANUAL
1-1
Page 8
D J-3684
ReSource AutoMax PROGRAMMING EXECUTIVE INSTRUCTION MANUAL VERSION 2.0
D J-3750
ReSource AutoMax PROGRAMMING EXECUTIVE INSTRUCTION MANUAL VERSION 3.0
D IEEE 518 GUIDE FOR THE INSTALLATION OF ELECTRICAL EQUIPMENT TO MINIMIZE ELECTRICAL NOISE INPUTS TO CONTROLLERS FROM EXTERNAL SOURCES
1-2
Page 9
2.0 MECHANICAL/ELECTRICAL DESCRIPTION The following is a description of the faceplate LEDs and the basic circuit functions on the module.
2.1
Mechanical Description The Common Memory module is a printed circuit board assembly that plugs into the backplane of the DCS 5000/AutoMax rack. The module consists of a printed circuit board, a faceplate, and a protective enclosure. The faceplate contains tabs at the top and bottom to simplify removing the module from the rack. On the back of the module are two edge connectors that attach to the system backplane. Module dimensions are listed in Appendix A. See figure 2.1 for module faceplates. The faceplate contains two green status lights. The upper status light, labeled indicates whether the onĆboard battery is providing sufficient voltage to retain the contents of RAM (ON) or should be replaced (OFF). See section 3.3 for directions on replacing the battery and Appendix A for battery specifications. The lower status light, labeled WATCHDOG", is lit only when the module is in slot 0, the module has passed its powerĆup diagnostics, and the bus arbitration clock is present on the backplane. If the status light is off, it indicates the module is not operational, either because it is malfunctioning or because it is located in a slot other than 0 and is providing data storage only.
2.1.1
Checking the Status of the On-Board Battery The status of the Common Memory module onĆboard battery can be checked in the following ways: If the Common Memory module is in slot 0: D the OK" LED on the faceplate will be ON to indicate the battery is providing sufficient voltage to maintain the contents of RAM memory and OFF if the battery should be replaced. D the Info/Log Processor Information Display from the ON LINE menu of the AutoMax Programming Executive will show the battery status. If the Common Memory module is not in slot 0 (i.e., it is in any other evenĆnumbered slot and is being used for data storage only), the battery status is indicated only by the status of the LED on the module faceplate.
2-1
Page 10
COMMON MEMORY MODULE 57C413B
COMMON MEMORY MODULE 57C423
BAT.OK
BAT.OK
Figure 2.1 Ć Module Faceplate
2-2