Manual · Reliance Electric
Common Memory Module (M/N 57C413B) (M/N 57C423)
Manual40 pagesPDF 190 KB
Instruction manual for the Reliance Electric 57C413B and 57C423 Common Memory modules used in DCS 5000 and AutoMax racks.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Reliance Electric instruction manual for the Common Memory module (M/N 57C413B and 57C423) for DCS 5000 and AutoMax racks. The module stores configuration data shared among Processors, arbitrates their access to the bus and provides a system watchdog. The manual describes the faceplate LEDs and circuits, installation, module and battery replacement, configuration and rack slot restrictions, diagnostics and troubleshooting, with appendices on specifications and how removing the module affects tasks. Appendix D also summarizes the older 57C413.
Its parts
- Introduction
- Mechanical/Electrical Description
- Installation
- Programming
- Diagnostics and Troubleshooting
From the manual
Key facts from this manual
Each line names its page in the PDF.
Instruction manual J-3636-2 for the Reliance Electric Common Memory module, M/N 57C413B and M/N 57C423, which goes in a DCS 5000 or AutoMax rack. It covers installation, module and battery replacement, configuration, troubleshooting and technical specifications. The earlier M/N 57C413, the number the site files it under, appears only in a short feature summary as the version that needs an external battery backup.
- What it is
- Common Memory module for slot 0 of a DCS 5000/AutoMax rack: stores shared configuration data and arbitrates Processor access to the bus p. 7
- Memory
- 57C413B: 128K bytes (64K registers) in slot 0; 57C423: 256K bytes (128K registers); both 128K bytes in other even slots p. 7
- 57C413 (earlier)
- 57C413: 128K bytes, needs external battery backup M/N 57C492 p. 33
- Battery
- 57C413B, 57C423: on-board lithium AA, 3.6 Volts, 2.0 Ah; replace with Reliance Electric M/N 57C385 only p. 15, 25
- Power
- +5 volts, 1050 mA; 5.3 Watts maximum dissipation p. 25
- Temperature
- 0 to 60°C operating, -40 to 85°C storage; 5-90% humidity non-condensing p. 25
- Dimensions
- 11.75 in high, 1.25 in wide, 7.375 in deep p. 25
- Status LEDs
- Two green lights: BAT.OK and SYSTEM WATCHDOG p. 9
- Bus arbitration
- Slot 0 only; supports up to four Processors in slots 1-4 p. 11
- Slot use
- Slot 0, or even slots 2 to 14 for data storage only with the slot to its right empty p. 19
- Logical slots in slot 0
- 57C413B: two slots of address space; 57C423: four slots p. 13
- Software
- 57C423: Programming Executive 2.1E, and 3.1C and later only; V3.0 and later configure the module with the Rack Configurator p. 18, 33
- Processor error codes
- 4.0 to 4.6: module failed power-up diagnostics; 31 or 51 to 58: bus error p. 21, 22
What this manual walks you through
- Installing the module and activating its battery p. 13, 14
- Testing a module used for data storage with the I/O MONITOR p. 14
- Replacing the module, including an older 57C413 with external battery backup p. 14, 15
- Replacing the on-board battery p. 15, 16
- How common and local variables are stored and configured p. 17, 18
- Tracking down incorrect data p. 21, 22
- Isolating a bus error p. 22, 23
- How replacing the module affects tasks and variables in a DCS 5000 rack p. 35
Good to know
- The module cannot be used in a remote I/O rack. p. 19
- In an even slot other than 0 the module gives data storage only, and arrays cannot be defined. p. 17
- The battery keeps the RAM contents only; it is not a source of uninterruptible power. p. 7
- Do not remove the external battery backup from racks with DCS Processor M/N 57C407, which needs it. p. 15
- Keep the module powered for at least 8 minutes before a battery change so the super-capacitor can hold the RAM. p. 15
Questions this manual answers
What battery does the Reliance 57C413B Common Memory module use?
A 3.6 Volt lithium AA cell of 2.0 amp hours; the manual says to replace it with Reliance Electric M/N 57C385 only. p. 15, 25
What is the difference between the 57C413, 57C413B and 57C423?
The 57C413 has 128K bytes and needs external battery backup M/N 57C492. The 57C413B has 128K bytes with an on-board lithium battery; the 57C423 has 256K bytes in slot 0. p. 33
Why is the BAT.OK light off on a Common Memory module?
The battery tape may still be on, the battery may be reversed, missing or faulty, or the power supply may be malfunctioning. p. 21
Can the 57C413B be used in a remote I/O rack?
No. The manual says the module cannot be used in a remote I/O rack. p. 19
The whole text · 4 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file