Common Memory Module (M/N 57C413B) (M/N 57C423)

Manual40 pagesPDF 190 KB

Instruction manual for the Reliance Electric 57C413B and 57C423 Common Memory modules used in DCS 5000 and AutoMax racks.

Download the PDF190 KB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Reliance Electric instruction manual for the Common Memory module (M/N 57C413B and 57C423) for DCS 5000 and AutoMax racks. The module stores configuration data shared among Processors, arbitrates their access to the bus and provides a system watchdog. The manual describes the faceplate LEDs and circuits, installation, module and battery replacement, configuration and rack slot restrictions, diagnostics and troubleshooting, with appendices on specifications and how removing the module affects tasks. Appendix D also summarizes the older 57C413.

Its parts

  1. Introduction
  2. Mechanical/Electrical Description
  3. Installation
  4. Programming
  5. Diagnostics and Troubleshooting

From the manual

Key facts from this manual

Each line names its page in the PDF.

Instruction manual J-3636-2 for the Reliance Electric Common Memory module, M/N 57C413B and M/N 57C423, which goes in a DCS 5000 or AutoMax rack. It covers installation, module and battery replacement, configuration, troubleshooting and technical specifications. The earlier M/N 57C413, the number the site files it under, appears only in a short feature summary as the version that needs an external battery backup.

Read for this summary: pages 1 to 4, 7 to 23, 25, 33 and 35 of 40.

What it is
Common Memory module for slot 0 of a DCS 5000/AutoMax rack: stores shared configuration data and arbitrates Processor access to the bus p. 7
Memory
57C413B: 128K bytes (64K registers) in slot 0; 57C423: 256K bytes (128K registers); both 128K bytes in other even slots p. 7
57C413 (earlier)
57C413: 128K bytes, needs external battery backup M/N 57C492 p. 33
Battery
57C413B, 57C423: on-board lithium AA, 3.6 Volts, 2.0 Ah; replace with Reliance Electric M/N 57C385 only p. 15, 25
Power
+5 volts, 1050 mA; 5.3 Watts maximum dissipation p. 25
Temperature
0 to 60°C operating, -40 to 85°C storage; 5-90% humidity non-condensing p. 25
Dimensions
11.75 in high, 1.25 in wide, 7.375 in deep p. 25
Status LEDs
Two green lights: BAT.OK and SYSTEM WATCHDOG p. 9
Bus arbitration
Slot 0 only; supports up to four Processors in slots 1-4 p. 11
Slot use
Slot 0, or even slots 2 to 14 for data storage only with the slot to its right empty p. 19
Logical slots in slot 0
57C413B: two slots of address space; 57C423: four slots p. 13
Software
57C423: Programming Executive 2.1E, and 3.1C and later only; V3.0 and later configure the module with the Rack Configurator p. 18, 33
Processor error codes
4.0 to 4.6: module failed power-up diagnostics; 31 or 51 to 58: bus error p. 21, 22

What this manual walks you through

  • Installing the module and activating its battery p. 13, 14
  • Testing a module used for data storage with the I/O MONITOR p. 14
  • Replacing the module, including an older 57C413 with external battery backup p. 14, 15
  • Replacing the on-board battery p. 15, 16
  • How common and local variables are stored and configured p. 17, 18
  • Tracking down incorrect data p. 21, 22
  • Isolating a bus error p. 22, 23
  • How replacing the module affects tasks and variables in a DCS 5000 rack p. 35

Good to know

  • The module cannot be used in a remote I/O rack. p. 19
  • In an even slot other than 0 the module gives data storage only, and arrays cannot be defined. p. 17
  • The battery keeps the RAM contents only; it is not a source of uninterruptible power. p. 7
  • Do not remove the external battery backup from racks with DCS Processor M/N 57C407, which needs it. p. 15
  • Keep the module powered for at least 8 minutes before a battery change so the super-capacitor can hold the RAM. p. 15

Questions this manual answers

What battery does the Reliance 57C413B Common Memory module use?

A 3.6 Volt lithium AA cell of 2.0 amp hours; the manual says to replace it with Reliance Electric M/N 57C385 only. p. 15, 25

What is the difference between the 57C413, 57C413B and 57C423?

The 57C413 has 128K bytes and needs external battery backup M/N 57C492. The 57C413B has 128K bytes with an on-board lithium battery; the 57C423 has 256K bytes in slot 0. p. 33

Why is the BAT.OK light off on a Common Memory module?

The battery tape may still be on, the battery may be reversed, missing or faulty, or the power supply may be malfunctioning. p. 21

Can the 57C413B be used in a remote I/O rack?

No. The manual says the module cannot be used in a remote I/O rack. p. 19

The whole text · 4 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40

The file

Revision and size

RevisionInstruction Manual J-3636-2
PublisherReliance Electric
Pages40
PDF190 KB
TextText from the PDF itself; pages 1, 5 and 40 are scans, read by OCR, which may hold reading errors.

The first pages · 3 of 40

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 40
Page 2
Page 2of 40
Page 3
Page 3of 40