Page 31

Appendix C (Continued) 16 Bit Register Reference Format Use the following method to reference a 16 bit register as a single precision integer. One statement is required in the configuration task for each variable. The symbolic name of each value should be as meaningful as possible: nnnnn IODEF SYMBOLIC_NAME%[ SLOT=s, REGISTER=r]

Bit Reference Format Use the following method to reference individual bits in a register. One statement is required in the configuration task for each variable. The symbolic name of each bit should be as meaningful as possible: nnnnn IODEF SYMBOLIC_NAME@[ SLOT=s, REGISTER=r, BIT=b] where: nnnnn - BASIC statement number. This number may range from 1-32767. SYMBOLIC_NAME! - A symbolic name chosen by the user and ending with (!). This indicates a double precision, or long integer data type and all references will access registers r and r+1. SYMBOLIC_NAME% - A symbolic name chosen by the user and ending with (%). This indicates a single precision integer data type and all references will access register SYMBOLIC_NAME@ - A symbolic name chosen by the user and ending with (@). This indicates a boolean data type and all references will access bit number in register SLOT - Slot number that the module is plugged into. This number may range from 2-14. If you are referencing registers on the upper half of the card, remember to use the slot number of the empty slot to the right of the module in the rack. REGISTER - Specifies the register that is being referenced. This number may range from 0-32767 for both slots. BIT - Used with boolean data types only. Specifies the bit in the register that is being referenced. This number may range from 0-15.

Examples of Configuration Statements The following statement assigns the symbolic name WINDOW! to register 2000 and 2001 on the memory module located in slot 10: 1000 IODEF WINDOW![ SLOT=10, REGISTER=2000] The following statement assigns the symbolic name POSITION% to register 250 of the input module located in slot 4: 1020 IODEF POSITION%[ SLOT=4, REGISTER=250] The following statement assigns the symbolic name LIGHT@ to bit 9 of register 10 on the input module located in slot 6: 2050 IODEF LIGHT@[ SLOT=6, REGISTER=10, BIT=9]

C-3

Page 32

afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd

Page 33

Appendix D Summary of Common Memory Module Features M/N 57C413 This module has 128K bytes of memory and requires external battery backup (M/N 57C492) to mainain the contents of memory in the event of a power failure.

M/N 57C413B This module has 128K bytes of memory and an onĆboard lithium battery to maintain the contents of memory in the event of a power failure.

M/N 57C423 This module has 256K bytes of memory available when plugged into slot 0, and 128K bytes available when plugged into any other nonĆzero slot. An onĆboard lithium battery maintains the contents of memory in the event of a power failure. This module is supported only by the following Program Executive version: 2.1E, and 3.1C and later.

D-1

Page 34

afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd

Page 35

Appendix E How Removing/Replacing The Common Memory Module Affects Tasks and Variables in a DCS 5000 Rack The following tables illustrate how removing or replacing the Common Memory module affects tasks and variables in a DCS 5000 rack. (Refer to Appendix F for information regarding the effect on tasks and variables in an AutoMax rack.) In each case, assume a BASIC task has written to variables in both the Processor (local) and the Common Memory module (common). Also assume the task was stopped before power was removed from the rack. The following information applies only if an external battery backup (57C492) is connected to the power supply. The external battery backup is required for DCS 5000 Processor memory backup. If the battery backup is not used, all tasks are deleted when power is removed from the rack.

Common Memory Module Located In Slot 0 For the following, assume the Common Memory module is in slot 0 and a Processor module is in slot 1. Status of Data Common App. Task Deleted?

App. Task Status

NonVol

Vol

Local

Replace 57C413A with Same or new 57C413A ąAt power up

YES*

N/A

N/A

N/A

N/A

Replace 57C413A with New 57C413B or 57C423 ąAt power up

NO

UNINSTALLED*

N/A

N/A

N/A

Action

Replace 57C413B or 57C423 with new or used 57C413B or 57C423 (module may contain data from another application) ąAt power up Replace battery on 57C413B or 57C423 and return same module to rack ąAt power up***

*

Error Code 13 appears on Processor LEDs**

NO

STOP

Data OK

Zero

Data OK

You must reĆload the configuration and application tasks onto the rack. This procedure is described in the Programming Executive instruction manual (J-3630).

** Select DOWNLOAD from the ON LINE menu to download the configuration and application tasks. Select ERROR CLEAR to clear the LED fault code on the Processor module. Refer to J-3630 for more information about the ON LINE menu. *** Assumes superĆcapacitor has maintained memory on the module during the time required to replace the battery.

E-1

Page 36

Appendix E (Continued) The Common Memory Module Is In Any Even Slot Other Than 0 In the following, assume the Common Memory module is in slot 2 and the single Processor module in the rack is in slot 1. Recall that in this configuration, common variables, as well as local variables, are being stored on the Processor module. Status of Data Common

Action

App. Task Deleted?

App. Task Status

NonVol

Vol

I/O

Local

Replace 57C413A with Same or new 57C413A ąAt power up

NO

STOP

Data OK

Zero

Lost (Random)

Data OK

Replace 57C413A with New 57C413B or 57C423 ąAt power up

NO

STOP

Data OK

Zero

Zero*

Data OK

Replace 57C413A with programmed 57C413B or 57C423 (module may contain data from another application) ąAt power up

NO

STOP

Data OK

Zero

Value from programmed module at same address*

Data OK

Replace 57C413B or 57C423 with New 57C413B or 57C423 ąAt power up

NO

STOP

Data OK

Zero

Zero*

Data OK

Replace 57C413B or 57C423 with proĆ grammed 57C413B or 57C423 (module may contain data from another application) ąAt power up Replace battery on 57C413B or 57C423 and return same module to rack ąAt power ***

*

Error Code 13 appears on Processor LEDs**

NO

STOP

Data OK

Zero

Data OK

Data OK

To ensure your application task does not access old or incorrect data, create a BASIC task to write zeroes to each register location before you run any other application tasks.

** Select DOWNLOAD from the ON LINE menu to download the configuration and application tasks. Select ERROR CLEAR to clear the LED fault code on the Processor module. Refer to J-3630 for more information about the ON LINE menu. *** Assumes superĆcapacitor has maintained memory on the module during the time required to replace the battery.

E-2

Page 37

Appendix F How Removing/Replacing The Common Memory Module Affects Tasks and Variables in an AutoMax Rack The following tables illustrate how removing or replacing the Common Memory module affects tasks and variables in an AutoMax rack. (Refer to Appendix E for information regarding the effect on tasks and variables in a DCS 5000 rack.) In each case, assume a BASIC task has written to variables in both the Processor (local) and the Common Memory module (common). Also assume the task was stopped before power was removed from the rack.

Common Memory Module Located In Slot 0 For the following, assume the Common Memory module is in slot 0 and a Processor module is in slot 1. Status of Data Common App. Task Deleted?

App. Task Status

NonVol

Vol

Local

Replace 57C413A with Same or new 57C413A ąAt power up

YES*

N/A

N/A

N/A

N/A

Replace 57C413A with New 57C413B or 57C423 ąAt power up

YES*

N/A

N/A

N/A

N/A

Replace 57C413B or 57C423 with new or used 57C413B or 57C423 (modĆ ule may contain data from another application) ąAt power up

YES*

N/A

N/A

N/A

N/A

Replace battery on 57C413B or 57C423 and return same module to rack ąAt power up**

NO

STOP

Data OK

Zero

Data OK

Action

*

You must reĆload the configuration and application tasks onto the rack. This procedure is described in the AutoMax Programming Executive instruction manual. Refer J-3750 if you are using AutoMax Version 3.0 or later. Refer to J-3684 if you are using AutoMax Version 2.1 or earlier.

** Assumes superĆcapacitor has maintained memory on the module during the time required to replace the battery.

F-1

Page 38

Appendix F (Continued) The Common Memory Module Is In Any Even Slot Other Than 0 In the following, assume the Common Memory module is in slot 2 and the single Processor module in the rack is in slot 1. Recall that in this configuration, common variables, as well as local variables, are being stored on the Processor module. Status of Data Common

Action

App. Task Deleted?

App. Task Status

NonVol

Vol

I/O

Local

Replace 57C413A with Same or new 57C413A ąAt power up

NO

STOP

Data OK

Zero

Lost (Random)

Data OK

Replace 57C413A with New 57C413B or 57C423 ąAt power up

NO

STOP

Data OK

Zero

Zero*

Data OK

Replace 57C413A with used 57C413B or 57C423 (module may contain data from another application) ąAt power up

NO

STOP

Data OK

Zero

Value from programmed module at same address*

Data OK

Replace 57C413B or 57C423 with New 57C413B ąAt power up

NO

STOP

Data OK

Zero

Zero*

Data OK

Replace 57C413B or 57C423 with used 57C413B or 57C423 (module may contain data from another application) ąAt power up

NO

STOP

Data OK

Zero

Replace battery on 57C413B or 57C423 and return same module to rack ąAt power up***

NO

STOP

Data OK

Zero

*

Value from used module at same address*

Data OK

Data OK

Data OK

To ensure your application task does not access old or incorrect data, create a BASIC task to write zeroes to each register location before you run any other application tasks.

** Assumes superĆcapacitor has maintained memory on the module during the time required to replace the battery.

F-2

Page 39

afadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa fdfdsfdsfdfdsfdsfsadfda sfdfaddfdd

Page 40 read from a scan by OCR; it may hold reading errors

www.rockwellautomation.com

Power, Control and Information Solutions Headquarters

Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846