Operating instructions Safety-monitoring module
SRB 301LC/B SRB 301LC/B-R 8 Appendix 8.1 Wiring examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 8.2 Start configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 8.3 Sensor configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 8.4 Actuator configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
EN
9
Operating 1 to 6
EU Declaration of conformity
Original
1. About this document 1.1 Function This operating instructions manual provides all the information you need for the mounting, set-up and commissioning to ensure the safe operation and disassembly of the safety-monitoring module. The operating instructions must be available in a legible condition and a complete version in the vicinity of the device. 1.2 Target group: authorised qualified personnel All operations described in this operating instructions manual must be carried out by trained specialist personnel, authorised by the plant operator only. Please make sure that you have read and understood these operating instructions and that you know all applicable legislations regarding occupational safety and accident prevention prior to installation and putting the component into operation. The machine builder must carefully select the harmonised standards to be complied with as well as other technical specifications for the selection, mounting and integration of the components. 1.3 Explanation of the symbols used
Content
Information, hint, note: This symbol is used for identifying useful additional information.
1 About this document 1.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Target group: authorised qualified personnel . . . . . . . . . . . . . . . . . 1 1.3 Explanation of the symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.4 Appropriate use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.5 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.6 Warning about misuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.7 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Caution: Failure to comply with this warning notice could lead to failures or malfunctions. Warning: Failure to comply with this warning notice could lead to physical injury and/or damage to the machine. 1.4 Appropriate use The products described in these operating instructions are developed to execute safety-related functions as part of an entire plant or machine. It is the responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machine or plant.
2 Product description 2.1 Ordering code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.2 Special versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.3 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.5 Safety classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
The safety-monitoring module must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer. Detailed information regarding the range of applications can be found in the chapter "Product description". 1.5 General safety instructions The user must observe the safety instructions in this operating instructions manual, the country specific installation standards as well as all prevailing safety regulations and accident prevention rules.
x.000 / 11.2017 / v.A. - 101177974-EN / E / 2017-10-25 / AE-Nr. 7940
3 Mounting 3.1 General mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4 Electrical connection 4.1 General information for electrical connection . . . . . . . . . . . . . . . . . 3
Further technical information can be found in the Schmersal catalogues or in the online catalogue on the Internet: www.schmersal.net.
5 Operating principle and settings 5.1 LED functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 5.2 Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
The information contained in this operating instructions manual is provided without liability and is subject to technical modifications.
6 Set-up and maintenance 6.1 Functional testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 6.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
There are no residual risks, provided that the safety instructions as well as the instructions regarding mounting, commissioning, operation and maintenance are observed.
7 Disassembly and disposal 7.1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 7.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
EN
1
Page 2
Operating instructions Safety-monitoring module
SRB 301LC/B SRB 301LC/B-R
1.6 Warning about misuse
2.4 Technical data General
In case of inadequate or improper use or manipulations of the safety-monitoring module, personal hazards or damage to machinery or plant components cannot be excluded. The relevant requirements of the standards ISO 14119 and ISO 13850 must be observed.
EN 60204-1, EN 60947-5-1; ISO 13849-1, IEC 61508 Climate EN 60068-2-78 snaps onto standard DIN rail to EN 60715 Terminal EN 60947-1 Material of the Plastic, glass-fibre reinforced thermoplastic, ventilated Material of the AgSnO, self-cleaning, positive drive
230 g Start Automatic or start button Feedback circuit Pull-in delay for automatic - LC/B: 300 ms - LC/B-R: 50 ms Pull-in delay with reset 20 ms Drop-out delay in case of "emergency 25 ms Mechanical Connection Screw connection Min. cable 0.25 mm² Max. cable 2.5 mm² Connecting rigid or flexible Tightening torque for the terminals: 0.6 Nm With removable terminals Mechanical 10 million operations Electrical life: Derating curve available on request Resistance to 10 g / 11 ms Resistance to vibrations to EN 10 ... 55 Hz, amplitude 0.35 mm Ambient Ambient – 25 °C … +45 °C Storage and transport –40 °C … +85 °C Protection Enclosure: IP40 Terminals: IP20 Clearance: IP54 Air clearances and creepage distances to IEC 4 kV/2 (basic insulation) EMC rating: to EMC Directive Electrical Contact resistance in new state: max. 100 mΩ Power max. 1.7 W / 1.9 VA Rated operating voltage 24 VDC –15% / +20%, residual ripple max. 10%, 24 VAC –15% / +10% Frequency 50 / 60 Hz Fuse rating for the operating glass fuse; internal T 1.0 A (5 x 20 mm) Monitored Short-circuit recognition Wire breakage detection (Y/N): Earth leakage detection (Y/N): Number of NO Number of NC Cable 1-channel without cross-wire short detection: – 1,500 m = 1.5 mm² – 2,500 m = 2.5 mm² 2-channel without cross-wire short detection Conduction max. 40 Ω
Number of safety Number of auxiliary Number of signalling outputs: Switching capacity of the safety 13-14; 23-24; 33-34: max. 250 V, 6 A ohmic (inductive in case of appropriate protective wiring); min. 10 V / 10 mA Switching capacity of the auxiliary 41-42: 24 VDC / 2 A Fuse rating of the safety 6 A slow blow Recommended fuse for the auxiliary 2 A slow blow
1.7 Exclusion of liability We shall accept no liability for damages and malfunctions resulting from defective mounting or failure to comply with this operating instructions manual. The manufacturer shall accept no liability for damages resulting from the use of unauthorised spare parts or accessories. For safety reasons, invasive work on the device as well as arbitrary repairs, conversions and modifications to the device are strictly forbidden; the manufacturer shall accept no liability for damages resulting from such invasive work, arbitrary repairs, conversions and/or modifications to the device. The safety-monitoring module must only be used when the enclosure is closed, i.e. with the front cover fitted.
2. Product description 2.1 Ordering code This operating instructions manual applies to the following types: SRB 301LC/B SRB 301LC/B-R Only if the information described in this operating instructions manual are realised correctly, the safety function and therefore the compliance with the Machinery Directive is maintained. 2.2 Special versions For special versions, which are not listed in the order code below 2.1, these specifications apply accordingly, provided that they correspond to the standard version. 2.3 Purpose The safety-monitoring modules for integration in safety circuits are designed for fitting in control cabinets. They are used for the safe evaluation of the signals of positive break position switches or magnetic safety sensors for safety functions on sliding, hinged and removable safety guards as well as emergency stop control devices and AOPD's. The safety function is defined as the opening of the enabling circuits 13-14, 23-24 and 33-34 when the inputs S11-S12 and/or S11-S22 are opened. The safety-relevant current paths with the outputs contacts 13-14, 23-24 and 33-34 meet the following requirements under observation of a PFH value assessment (also refer to chapter 2.5 "Safety classification"): – Control category 4 - PL e to ISO 13849-1 – SIL 3 to IEC 61508-2 – 3 to IEC 62061 To determine the Performance Level (PL) to ISO 13849-1 of the entire safety function (e.g. sensor, logic, actuator), an assessment of all relevant components is required. The entire concept of the control system in which the safety component is integrated, must be validated to the relevant standards.
2
EN
Page 3
Operating instructions Safety-monitoring module
SRB 301LC/B SRB 301LC/B-R 5. Operating principle and settings
Utilisation category to IEC/EN
AC-15 / DC-13: EN 60947-5-1:2007 Dimensions H x W x 100 mm x 22.5 mm x 121 mm The data specified in this manual are applicable when the component is operated with rated operating voltage Ue ±0%. 2.5 Safety classification
Control
PFH
Service
5.1 LED functions • K1: Status channel 1 • K2: Status channel 2 • Status operating voltage (LED is on, when the operating voltage on the terminals A1-A2 is ON) • Status internal operating voltage (LED is on, when the operating voltage on the terminals A1-A2 is ON and the fuse has not been triggered).
ISO 13849-1, IEC 61508, IEC 62061 up to e up to 4 99% (high) > 65 points ≤ 2.00 × 10-8/h up to 3 20 years
Description of the terminals Voltages: Inputs:
The PFH value of 2.00 × 10-8/h applies to the combinations of contact load (current through enabling contacts) and number of switching cycles (nop/y) mentioned in the table below. At 365 operating days per year and a 24-hours operation, this results in the below-mentioned switching cycle times (tcycle) for the relay contacts. Diverging applications upon request. Contact load nop/y tcycle
20 % 40 % 60 % 80 % 100 %
525,600 210,240 75,087 30,918 12,223
1.0 min 2.5 min 7.0 min 17.0 min 43.0 min
Outputs:
Start:
3. Mounting 3.1 General mounting instructions Mounting: snaps onto standard DIN rails to EN 60715. Snap the bottom of the enclosure slightly tilted forwards in the DIN rail and push up until it latches in position. To avoid EMC disturbances, the physical ambient and operational conditions at the place where the product is installed, must meet the provisions laid down in the paragraph "Electromagnetic Compatibility (EMC)" of EN 60204-1.
A1 A2 S11-S12 S11-S22 13-14 23-24 33-34 X1-X2 41-42
33 23 13 41 X1 S12 S11 A1
33 23 13 41 X1 S12S11 A1
UB Ui SRB K1 301 K2 LC/B
UB Ui SRB K1 301 LC/B-R K2
X2 S22S21 A2 34 24 14 42
X2S22S21 A2 34 24 14 42
Fig. 1
Fig. 2
+ 24 VDC/24 VAC 0 VDC/24 VAC Input channel 1 (+) Input channel 2 (+) First safety enabling circuit Second safety enabling circuit Third safety enabling circuit Feedback circuit and external reset Auxiliary NC contact as signalling contact
5.2 Notes Signalling outputs must not be used in safety circuits.
3.2 Dimensions All measurements in mm.
6. Set-up and maintenance 6.1 Functional testing The safety function of the safety-monitoring module must be tested. The following conditions must be previously checked and met: 1. Correct fixing 2. Check the integrity of the cable entry and connections 3. C heck the safety-monitoring module's enclosure for damage 4. C heck the electrical function of the connected sensors and their influence on the safety-monitoring module and the downstream actuators
Device dimensions (H/W/D): 100 x 22.5 x 121 mm
4. Electrical connection 4.1 General information for electrical connection As far as the electrical safety is concerned, the protection against unintentional contact of the connected and therefore electrically interconnected apparatus and the insulation of the feed cables must be designed for the highest voltage, which can occur in the device.
6.2 Maintenance A regular visual inspection and functional test, including the following steps, is recommended: 1. Check the correct fixing of the safety-monitoring module 2. Check the cable for damages 3. Check electrical function
The electrical connection may only be carried out by authorised personnel in a de-energised condition. Wiring examples: see appendix
EN
3
Page 4
Operating instructions Safety-monitoring module
SRB 301LC/B SRB 301LC/B-R Automatic start (see Fig. 4) • automatic start is programmed by connecting the feedback circuit to the terminals X1-X2. If the feedback circuit is not required, establish a bridge. • Not admitted without additional measure due to the risk of gaining access by stepping behind! • the safety-monitoring modules are used with the operating mode "Automatic start", an automatic restart after a shutdown in case of emergency must be prevented by the upstream control to EN 60204-1 paragraph 9.2.5.4.2.
If a manual functional check is necessary to detect a possible accumulation of faults, then this must take place during the intervals noted as follows: •a t least every month for PL e with category 3 or category 4 (according to ISO 13849-1) or SIL 3 with HFT (hardware fault tolerance) = 1 (according to IEC 62061); •a t least every 12 months for PL d with category 3 (according to ISO 13489-1) or SIL 2 with HFT (hardware fault tolerance) = 1 (according to IEC 62061). Damaged or defective components must be replaced.
X1
X1
KB S KA X2
KB S KA X2
Fig. 3
Fig. 4
J
7. Disassembly and disposal 7.1 Disassembly The safety-monitoring module must be disassembled in a de-energised condition only. Push up the bottom of the enclosure and hang out slightly tilted forwards. 7.2 Disposal The safety-monitoring module must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations.
8.3 Sensor configuration Single-channel emergency stop circuit with command devices to ISO 13850 and EN 60947-5-5 (Fig. 5) • breakage and earth leakage in the control circuits are detected. • 1 – PL c to ISO 13849-1 possible.
8. Appendix 8.1 Wiring examples
Dual-channel emergency stop circuit with command devices to ISO 13850 and EN 60947-5-5 (Fig. 6) • breakage and earth leakage in the control circuits are detected. • shorts between the control circuits are not detected. • category 4 – PL e to ISO 13849-1 possible (with protective wiring)
Dual-channel control, shown for a guard door monitor with two position switches where one has a positive break contact; with external reset button J (Fig. 2) • outputs: 2-channel control, suitable for increase incapacity or number of contacts by means of contactors or relays with positiveguided contacts. • control system recognises wire-breakage and earth faults in the monitoring circuit. J
Single-channel guard door monitoring circuit with interlocking devices to ISO 14119 (Fig. 7) • least one contact with positive break required. • breakage and earth leakage in the control circuits are detected. • 1 – PL c to ISO 13849-1 possible.
L1
S11 S12
KB S KA
A1
A
S12 S11 S21 S22 X1 X2
S11 S11
S11 S12
S12 S22
S12 S22
A
13 23 33 41
F1
S12 S22 a) K1
KA
K2
KB
Fig. 5
Ui K1
K2
A2
KB N
Fig. 2 a) Logic S = Feedback circuit
Dual-channel control of magnetic safety switches to EN 60947-5-3 (see Fig. 9) • breakage and earth leakage in the control circuits are detected. • shorts between the control circuits are not detected. • 3 – PL e to ISO 13849-1 possible.
8.2 Start configuration External reset button (Fig. 3) • external reset button is integrated in the feedback circuit in series. • manual start or the activation of the module occurs when the button is pressed (not when it is released!).
4
Fig. 7
Dual-channel guard door monitoring circuit with interlocking device to ISO 14119 (Fig. 8) • at least one positive-break position switch • breakage and earth leakage in the control circuits are detected. • shorts between the control circuits are not detected. • category 4 – PL e to ISO 13849-1 possible (with protective wiring)
14 24 34 42 KA
Fig. 6
EN
Page 5
Operating instructions Safety-monitoring module
SRB 301LC/B SRB 301LC/B-R 8.4 Actuator configuration
The connection of magnetic safety switches to the SRB 301LC/B safety-monitoring module is only admitted when the requirements of the standard EN 60947-5-3:2005 are observed.
Single-channel control with feedback circuit (Fig. 11) • for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. •S = feedback circuit: If the feedback circuit is not required, establish a bridge.
As the technical data are regarded, the following minimum requirements must be met: – switching capacity: min. 240 mW – switching voltage: min. 24 VDC – switching current: min. 10 mA
Dual-channel control with feedback circuit (Fig. 12) • for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. •S = feedback circuit: If the feedback circuit is not required, establish a bridge.
For example, the following safety sensors meet the requirements: – BNS 33-02z-2187, BNS 33-02zG-2187 – BNS 260-02z, BNS 260-02zG – BNS 260-02-01z, BNS 260-02-01zG
L1
L1 KA
S
X1
KA
S
X2
13
X1
KB X2
13 KB KA
KA
When sensors with LED are wired in the control circuit (protective circuit), the following rated operating voltage must be observed and respected: – 24 VDC with a max. tolerance of –5 %/+ 20 % – 24 VAC with a max. tolerance of –5 %/+ 10 % Otherwise availability problems could occur, especially in series-wired sensors, where a voltage drop in the control circuit is triggered by LED's for instance.
14
14
KA
KA
N
N
Fig. 11
Fig. 12
KB
Dual-channel control of a safety-related (microprocessor-based) safety guards with p-type transistor outputs e.g. AOPD's to IEC 61496-1 (Fig. 10) • breakage and earth leakage in the control circuits are detected. • shorts between the monitoring circuits are usually detected by the safety guards. The safety-monitoring module therefore is not equipped with a cross-wire short detection. • cross-wire shorts in the control circuits are detected by the safety guard: Control category 4 – PL e to ISO 13849-1 possible.
Fig. 8
S11 S11
S11 S11
+24V +24V
S12 S22
S12 S22
S12 S22
Fig. 9
Fig. 10
EN
5
Page 6
Operating instructions Safety-monitoring module
SRB 301LC/B SRB 301LC/B-R
9. EU Declaration of conformity
EU Declaration of conformity Original
K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com
We hereby certify that the hereafter described components both in their basic design and construction conform to the applicable European Directives. SRB 301LC/B SRB301LC/B-R
Description of the component:
Safety-monitoring module for emergency stop circuits, guard door monitoring, magnetic safety switches and AOPDs
Relevant Directives:
Machinery Directive EMC-Directive RoHS-Directive
Applied standards:
EN 60947-5-1:2004 + AC:2005 + A1:2009, EN ISO 13849-1:2015, EN ISO 13849-2:2012, ISO 13850:2015, EN 61326-3-1:2008
Notified body, which approved the full quality assurance system, referred to in Appendix X, 2006/42/EC:
TÜV Rheinland Industrie Service GmbH Alboinstr. 56, 12103 Berlin ID n°: 0035
Person authorised for the compilation of the technical documentation:
Oliver Wacker Möddinghofe 30 42279 Wuppertal
Place and date of issue:
Wuppertal, 24 October 2017
SRB 301LC/B-C-EN
Name of the component:
Authorised signature Philip Schmersal Managing Director