What is in it
Schmersal operating instructions for the SRB 301LC/B and SRB 301LC/B-R safety-monitoring modules, DIN rail relay modules that evaluate guard switches, magnetic safety sensors, emergency stop devices and AOPDs. They cover safety notes, ordering code, purpose, full technical data, safety classification, mounting and dimensions, electrical connection, LED functions, functional testing and maintenance, disposal, wiring examples for start, sensor and actuator configurations, and the EU declaration of conformity.
Its parts
- About this document
- Product description
- Mounting
- Electrical connection
- Operating principle and settings
- Set-up and maintenance
- Disassembly and disposal
- Appendix
- EU Declaration of conformity
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Schmersal operating instructions for the SRB 301LC/B and SRB 301LC/B-R safety-monitoring modules, which evaluate emergency stop, guard door, magnetic safety switch and light curtain circuits. It gives technical data, mounting, LED functions, testing and maintenance, and wiring examples for start, sensor and actuator configurations.
- What it is
- A safety-monitoring module fitted in control cabinets, for position switches, magnetic safety sensors, emergency stops and AOPDs p. 2
- Safety contacts
- 3 (13-14, 23-24, 33-34): max. 250 V, 6 A ohmic; min. 10 V / 10 mA p. 2
- Auxiliary contact
- 1 (41-42): 24 VDC / 2 A p. 2
- Operating voltage
- 24 VDC –15% / +20% (residual ripple max. 10%) or 24 VAC –15% / +10%, 50 / 60 Hz p. 2
- Fuses
- Internal glass fuse T 1.0 A (5 x 20 mm) for the operating voltage; safety contacts 6 A slow blow; auxiliary contacts 2 A slow blow recommended p. 2
- Size and weight
- 100 x 22.5 x 121 mm (H/W/D), 230 g p. 2, 3
- Mounting
- Snaps onto standard DIN rail to EN 60715 p. 2, 3
- LEDs
- K1 and K2 channel status, UB operating voltage, Ui internal operating voltage (off when the fuse has tripped) p. 3
- Magnetic sensors
- BNS 33-02z-2187, BNS 33-02zG-2187, BNS 260-02z, BNS 260-02zG, BNS 260-02-01z, BNS 260-02-01zG p. 5
- Safety classification
- The manual states control category 4, PL e to ISO 13849-1, SIL 3 to IEC 61508-2 and SILCL 3 to IEC 62061 p. 2
What this manual walks you through
- Mounting the module on a DIN rail and removing it p. 3, 4
- Functional testing before set-up p. 3
- Regular maintenance checks p. 3
- Wiring an external reset button or automatic start p. 4
- Wiring single- and dual-channel emergency stop circuits p. 4
- Wiring guard door monitoring circuits p. 4
- Connecting magnetic safety switches p. 4, 5
- Connecting light curtains and other AOPDs with p-type outputs p. 5
- Wiring contactors on the outputs with a feedback circuit p. 5
Good to know
- Automatic start is not admitted without an additional measure, because a person could step behind the guard. p. 4
- The signalling outputs must not be used in safety circuits. p. 3
- Electrical connection only by authorised personnel with the module de-energised. p. 3
- Sensors with LEDs in the control circuit need tighter supply tolerances: 24 VDC –5 %/+ 20 % or 24 VAC –5 %/+ 10 %. p. 5
Questions this manual answers
How do I wire a reset button to the SRB 301LC/B?
The external reset button goes in series in the feedback circuit; the module starts when the button is pressed, not when it is released. p. 4
Which magnetic safety switches work with the SRB 301LC/B?
Switches meeting EN 60947-5-3 with at least 240 mW, 24 VDC and 10 mA switching, for example the BNS 33-02z-2187 or BNS 260-02z. p. 5
What do the UB and Ui LEDs on the SRB 301LC/B mean?
UB is on when operating voltage is present on A1-A2; Ui is on when that voltage is present and the fuse has not been triggered. p. 3