Schmersal datasheet for the SRB 301LC/B-24V (article 101177962), a PROTECT SRB general purpose safety controller for emergency stop buttons, guard door monitoring, safety magnetic switches and safety light curtains. It lists ordering details, safety classification (PL, category, SIL), global properties, mechanical data, ambient conditions, electrical data, inputs and outputs, contact ratings, LED indicators, dimensions, a wiring example and the related documents.
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Schmersal datasheet for the SRB 301LC/B-24V safety control module from the PROTECT SRB series, used for emergency stop, guard door and light curtain circuits. It gives ordering details, electrical and mechanical data, timing, outputs, dimensions and a wiring example.
- What it is
- A safety control module for emergency stop buttons, guard doors, safety magnetic switches and light curtains p. 1, 4
- Article number
- 101177962 (SRB 301LC/B-24V) p. 1
- Operating voltage
- 24 VDC -15% / +20% (residual ripple max. 10%) or 24 VAC -15% / +10%, 50 / 60 Hz p. 3
- Safety contacts
- 3, STOP 0; max. 250 VAC, 6 A ohmic, min. 10 V, 10 mA; AC-15: 230 V / 6 A, DC-13: 24 V / 6 A p. 1, 3, 4
- Auxiliary contact
- 1, rated 24 VDC, 2 A p. 3, 4
- Fuses
- Safety contacts 6 A slow blow; auxiliary contacts 2 A slow blow; operating voltage 0.5 A gG D-fuse p. 3, 4
- Mounting
- Snaps onto standard DIN rail to EN 60715 p. 2
- Dimensions
- 22.5 mm wide, 100 mm high, 121 mm deep p. 4
- Ambient temperature
- −25 °C to +45 °C; storage and transport −40 °C to +85 °C p. 2, 3
- Switching delays
- ON delay ≤ 300 ms with automatic start, ≤ 20 ms with reset button; drop-out ≤ 25 ms on emergency stop p. 2
- Start modes
- Automatic or start button, with feedback circuit p. 2
- Protection class
- Enclosure IP40, terminals IP20, clearance IP54 p. 3
- LEDs
- 4: relay K1, relay K2, supply voltage, internal operating voltage Ui p. 4
- Safety classification
- The spec sheet states PL up e, control category up 4 and SIL up 3 (STOP 0) p. 1
What this sheet walks you through
- Wiring a 2-channel guard door circuit with two position switches p. 5
- Wiring a 1-channel control p. 5
- Connecting safety light grids or curtains p. 5
- Setting up automatic start p. 5
- Reading the status LEDs p. 4
Good to know
- Inductive loads such as contactors and relays must be suppressed by a suitable circuit. p. 4
- Light grids or curtains wired to S12/S22 must share the module's reference potential. p. 5
- The module detects wire breakage and earth faults but not short circuits on its monitored inputs. p. 3
Questions this sheet answers
What supply voltage does the SRB 301LC/B-24V need?
24 VDC (-15% / +20%) or 24 VAC (-15% / +10%) at 50 or 60 Hz. p. 3
How many safety contacts does the SRB 301LC/B have?
Three safety contacts (STOP 0) and one auxiliary contact. p. 1, 3
How do I wire the SRB 301LC/B for a single channel?
Connect the NC contact to S11/S12 and bridge S12/S22. p. 5
How is automatic start set on the SRB 301LC/B?
Connect the feedback circuit to terminals X1/X2; if no feedback circuit is needed, fit a bridge there. p. 5