Page 1

03.10.2018 18:21:13h

Datasheet - SRB 301LC/B-24V Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB 301LC/B

• Fit for signal evaluation of outputs of safety magnetic switches (to this end, integrated current and voltage limiters) • Suitable for signal processing of potential-free outputs, e.g. emergency stop command devices, position switches and solenoid interlocks • Suitable for signal processing of outputs connected to potentials (AOPDs), e.g. safety light grids/curtains • 3 safety contacts, STOP 0 • 1 Signalling output

(Minor differences between the printed image and the original product may exist!)

Ordering details Product type description

SRB 301LC/B-24V

Article number

101177962

EAN Code

4250116201686 eCl@ss

27-37-19-01

Approval Approval USA/CAN EAC

Classification Standards

EN ISO 13849-1, IEC 61508, EN 60947-5-1

PL up e (STOP 0)

Control category up 4 (STOP 0)

DC

99% (STOP 0)

CCF

> 65 points

PFH value

≤ 2,0 x 10-8/h (STOP 0)

SIL up 3 (STOP 0)

Mission time

20 Years

- notice

The PFH value is applicable for the combinations listed in the table for

Page 2

contact load (K) (current through enabling paths) and switching cycle number (n-op/y). In case of 365 operating days per year and a 24-hour operation, this results in the specified switching cycle times (t-cycle) for the relay contacts. Diverging applications on request.

Global Properties Permanent light

SRB 301LC/B

Standards

IEC/EN 60204-1, EN 60947-5-1, EN ISO 13849-1, IEC 61508

Compliance with the Directives (Y/N)

Yes

Climatic stress

EN 60068-2-78

Mounting snaps onto standard DIN rail to EN 60715

Terminal designations

IEC/EN 60947-1

Materials - Material of the housings

Plastic, glass-fibre reinforced thermoplastic, ventilated

- Material of the contacts

AgSn0, self-cleaning, positive action

Weight

230

Start conditions

Automatic or Start button

Start input (Y/N)

Yes

Feedback circuit (Y/N)

Yes

Start-up test (Y/N)

No

Automatic reset function (Y/N)

Yes

Reset with edge detection (Y/N)

No

Pull-in delay - ON delay with automatic start

≤ 300 ms

- ON delay with reset button

≤ 20 ms

Drop-out delay - Drop-out delay in case of emergency stop

≤ 25 ms

Mechanical data Connection type

Screw connection

Cable section - Min. Cable section

0,25

- Max. Cable section

2.5

Pre-wired cable rigid or flexible

Tightening torque for the terminals

0,6

Detachable terminals (Y/N)

No

Mechanical life

10.000.000 operations

Electrical lifetime

Derating curve available on request restistance to shock

30 g / 11 ms

Resistance to vibration To EN 60068-2-6

10…55 HZ, Amplitude 0,35 mm, ± 15 %

Ambient conditions Ambient temperature - Min. environmental temperature

−25 °C

- Max. environmental temperature

+45 °C

Storage and transport temperature - Min. Storage and transport temperature

−40 °C

Page 3

- Max. Storage and transport temperature

+85 °C

Protection class - Protection class-Enclosure

IP40

- Protection class-Terminals

IP20

- Protection class-Clearance

IP54

Air clearances and creepage distances To IEC/EN 60664-1 - Rated impulse withstand voltage Uimp

4 kV

- Overvoltage category

II To VDE 0110

- Degree of pollution

2 To VDE 0110

Electromagnetic compatibility (EMC) EMC rating conforming to EMC Directive

Electrical data Rated DC voltage for controls - Max. rated DC voltage for controls

20.4

- Max. rated DC voltage for controls

28.8

Rated AC voltage for controls, 50 Hz - Min. rated AC voltage for controls, 50 Hz

20.4

- Max. rated AC voltage for controls, 50 Hz

26.4

Rated AC voltage for controls, 60 Hz - Min. rated AC voltage for controls, 60 Hz

20.4

- Max. rated AC voltage for controls, 60 Hz

26.4

Contact resistance max. 100 mΩ

Power consumption max. 1.7 W; 1.9 VA

Type of actuation

AC/DC

Switch frequency max. 5 HZ

Rated operating voltage Ue

24 VDC −15% / +20%, residual ripple max. 10% 24 VAC −15% / +10%

Operating current Ie

0,08 A

Frequency range

50 / 60 HZ

Electronic protection (Y/N)

No

Fuse rating for the operating voltage

0,5 A gG D-fuse

Inputs Monitored inputs - Short-circuit recognition (Y/N)

No

- Wire breakage detection (Y/N)

Yes

- Earth connection detection (Y/N)

Yes

Number of shutters

0 piece

Number of openers

2 piece

Cable length

1500 m with 1.5 mm²; 2500 m with 2.5 mm²

Conduction resistance max. 40 Ω

Outputs Stop category

0

Number of safety contacts

3 piece

Number of auxiliary contacts

1 piece

Number of signalling outputs

0 piece

Page 4

Switching capacity - Switching capacity of the safety contacts max. 250 VAC, 6 A ohmic (inductive in case of appropriate protective wiring) min. 10 V, 10 mA

- Switching capacity of the auxiliary contacts

24 VDC, 2 A

Fuse rating - Protection of the safety contacts

6 A slow blow

- Fuse rating for the auxiliary contacts

2 A slow blow

Utilisation category To EN 60947-5-1

AC-15: 230 V / 6 A DC-13: 24 V / 6 A

Number of undelayed semi-conductor outputs with signaling function

0 piece

Number of undelayed outputs with signaling function (with contact)

1 piece

Number of delayed semi-conductor outputs with signaling function.

0 piece

Number of delayed outputs with signalling function (with contact).

0 piece

Number of secure undelayed semi-conductor outputs with signaling function

0 piece

Number of secure, undelayed outputs with signaling function, with contact.

3 piece

Number of secure, delayed semi-conductor outputs with signaling function

0 piece

Number of secure, delayed outputs with signaling function (with contact). 0 piece

LED switching conditions display LED switching conditions display (Y/N)

Yes

Number of LED´s

4

LED switching conditions display - The integrated LEDs indicate the following operating states. - Position relay K1 - Position relay K2 - Supply voltage - Internal operating voltage Ui

Miscellaneous data Applications Emergency-Stop button Guard system Pull-wire emergency stop switches Safety light curtain Safety sensor

Dimensions Dimensions - Width

22.5 mm

- Height

100 mm

- Depth

121 mm notice Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.

Page 5

notice - Wiring example Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R); cross-wire monitoring and feedback circuit (H2) The control system recognises wire-breakage and earth faults in the monitoring circuit. Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. For 1-channel control, connect NC contact to S11/S12 and bridge S12/S22 Connect potential p-type outputs of safety light grids/curtains to S12/S22. The devices must have the same reference potential. Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals X1/X2. If the feedback circuit is not required, establish a bridge The wiring diagram is shown with guard doors closed and in de-energised condition.

Documents Operating instructions and Declaration of conformity (es) 292 kB, 06.06.2018 Code: mrl_srb_301lc_b_es Operating instructions and Declaration of conformity (nl) 291 kB, 13.07.2018 Code: mrl_srb_301lc_b_nl Operating instructions and Declaration of conformity (pt) 298 kB, 17.08.2018 Code: mrl_srb_301lc_b_pt Operating instructions and Declaration of conformity (fr) 345 kB, 29.06.2018 Code: mrl_srb_301lc_b_fr Operating instructions and Declaration of conformity (de) 272 kB, 18.05.2018 Code: mrl_srb_301lc_b_de Operating instructions and Declaration of conformity (da) 319 kB, 29.08.2013 Code: mrl_srb_301lc_b_da Operating instructions and Declaration of conformity (pl) 301 kB, 06.09.2018 Code: mrl_srb_301lc_b_pl Operating instructions and Declaration of conformity (it) 295 kB, 22.01.2018 Code: mrl_srb_301lc_b_it Operating instructions and Declaration of conformity (en) 293 kB, 18.05.2018 Code: mrl_srb_301lc_b_en Operating instructions and Declaration of conformity (jp) 337 kB, 03.01.2014 Code: mrl_srb_301lc_b_jp Wiring example (99) 15 kB, 06.08.2009 Code: ksrb3l23 Wiring example (99) 20 kB, 22.08.2008 Code: ksrb3l11 CCC certification (cn) 296 kB, 16.01.2017 Code: q_srbp02 CCC certification (en) 314 kB, 16.01.2017 Code: q_srbp01

Page 6

EAC certification (ru) 1 MB, 15.03.2018 Code: q_aesp01

Images

Wiring example

Wiring example

Internal wiring diagram

K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal

Page 7

The data and values have been checked throroughly. Technical modifications and errors excepted. Generiert am 03.10.2018 - 18:21:13h Kasbase 3.3.0.F.64I