Spec sheet · Schneider
170 ADI 340 00 24 VDC - 16 Pt. Discrete Input Module Base
Spec sheet16 pagesPDF 559 KB
Manual chapter for the 170 ADI 340 00 TSX Momentum 24 VDC 16-point discrete input base: LEDs, specifications, wiring, setup.
Covers · 1 model
The models it covers
Summary
What is in it
A chapter from a TSX Momentum I/O base manual describing the 170 ADI 340 00, a 24 VDC base with 16 discrete inputs. It shows the front panel components and LED meanings, lists general and discrete input specifications (supply, power dissipation, fusing, EMC, approvals, dimensions, weight), and covers internal pin connections, field wiring guidelines, wiring diagrams, simplified schematics and configuration of the discrete inputs.
Its parts
- Module Overview
- Wiring
- Configuration
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
A chapter of the TSX Momentum I/O base manual (870 USE 002 00) on the 170 ADI 340 00, a 24 VDC base with 16 discrete inputs. It covers the front panel and LEDs, specifications, field wiring for 2-, 3- and 4-wire devices, and how input data maps to the CPU.
- What it is
- TSX Momentum I/O base with 16 discrete 24 VDC inputs in 1 group p. 1, 5
- Supply
- 24 VDC (20...30 VDC), max. 250 mA at 24 VDC p. 5
- Input levels
- ON +11 ... +30 VDC, OFF -3 ... +5 VDC; true high, IEC 1131 type 1+ p. 6
- Input current
- 2.5 mA min. ON (6 mA at 24VDC), 1.2 mA maximum OFF; input resistance 4 kOhm p. 6
- Response time
- 2.2 ms OFF to ON, 3.3 ms ON to OFF p. 6
- I/O map
- 1 input word (16 bits) p. 5, 14
- Fuses
- No internal fuse; external 315 mA fast-blow on the operating voltage (Wickmann 19193-315 mA or 19194-315 mA); inputs not over 4A fast-blow p. 5
- Terminal connectors
- Sets of three: 170 XTS 001 00 screw-in or 170 XTS 002 00 spring-clip p. 9
- Busbars
- 1-row busbar for 4-wire devices: 170 XTS 006 01 screw-in or 170 XTS 007 01 spring-clip p. 9
- Row 1 terminals
- 1...16 inputs, 17 return (M-), 18 +24 VDC operating voltage (L+) p. 10
- Dimensions
- 125 mm wide, 40 mm deep without adapter, 141.5 mm long with no or one busbar; 190 g p. 6
- Power dissipation
- 6 W + (# of input points on x .144 W) p. 5
- LEDs
- ready (5 V logic present), 1L+ (input voltage present), IN 1 ... 16 (one per input) p. 4
- Approvals
- The document lists UL, CUL, CE p. 5
What this sheet walks you through
- Identifying the front panel parts p. 3
- Reading the status LEDs p. 4
- Field wiring and terminal row layout p. 9, 10
- Wiring 2-, 3- and 4-wire input devices p. 11, 12
- Mapping input data to the CPU with IEC or 984 Ladder Logic software p. 14, 15
Good to know
- External fuses must be fitted on the operating voltage; an unprotected module may suffer short circuits or power-up spikes. p. 10
- A busbar is needed only for 4-wire sensors, to give them protective earth. p. 12
- Wiring and mapping depend on whether the adapter and software are IEC or 984 Ladder Logic compliant. p. 14
Questions this sheet answers
What fuse does the 170 ADI 340 00 need?
It has no internal fuse. Fit an external 315 mA fast-blow fuse on the operating voltage, such as Wickmann 19193-315 mA or 19194-315 mA. p. 5
Which terminal connector fits the 170 ADI 340 00?
The 170 XTS 001 00 screw-in or 170 XTS 002 00 spring-clip set of three. p. 9
What voltage turns on a 170 ADI 340 00 input?
+11 to +30 VDC is ON and -3 to +5 VDC is OFF. p. 6
The whole text · 2 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file