The text of a spec sheet ยท part 2 of 2
170 ADI 340 00 24 VDC - 16 Pt. Discrete Input Module Base, pages 9 to 16
Pages 9 to 16 of 16
The original document is the PDF (559 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Schneider 170-ADI-340-00
Page 9
170 ADI 340 00
Field Wiring Guidelines
Overview
Inputs are field wired to row 1 of the base. This section contains guidelines and precautions.
Terminal Connector Required
To connect field devices to the I/O base, you need a field wiring terminal connector. Schneider Automations sells terminal connectors in sets of three:
Busbar May Be Required
Type
Part Number
Screw-in
170 XTS 001 00
Spring-clip
170 XTS 002 00
If you are using 4-wire devices, you will need a 1-row busbar to connect them to protective earth (PE). Type
Part Number
Screw-in
170 XTS 006 01
Spring-clip
170 XTS 007 01
Continued on next page
870 USE 002 00 V.2
209
Page 10
170 ADI 340 00
Field Wiring Guidelines, Continued
Mapping Terminal Blocks and Busbar
A busbar may be attached to this I/O base to provide a fourth row for protective earth (PE). Row
Terminal
Function
1
1...16
Inputs
17
Return (M-)
18
+ 24 VDC Operating voltage (L+)
2
3
4
1 ... 17
Sensor/input device voltages
18
+ 24 VDC for inputs
1 ... 17
Returns for sensor/input devices (for 3and 4-wire devices)
18
Return for inputs
1 ... 18
Protective earth (PE)
CAUTION POTENTIAL FOR SHORT CIRCUITS AND/OR POWER-UP SPIKES Provide external fuses on the operating voltage to protect the module. Appropriate fuse values are shown in the wiring diagram. An unprotected module may be subject to short circuits and/or power-up spikes. See Protective Actuator Circuit on page 84. Failure to observe this precaution can result in injury or equipment damage.
210
870 USE 002 00 V.2
Page 11
170 ADI 340 00
Wiring Diagrams
Overview
Two-Wire Devices
This section contains diagrams to assist you in wiring the following types of devices: โ
2-wire devices
โ
3-wire devices
โ
4-wire devices
The diagram below shows an example of wiring for two-wire devices.
Continued on next page
870 USE 002 00 V.2
211
Page 12
170 ADI 340 00
Wiring Diagrams, Continued
Three- and FourWire Devices
The diagram below shows an example of wiring for three- and four-wire devices. A 1-row busbar is used to provide PE for the 4-wire sensor. No busbar would be required if only 2- and/or 3-wire sensors were used.
212
870 USE 002 00 V.2
Page 13
170 ADI 340 00
Simplified Schematics
Overview
This section contains a simplified schematic diagram of the field-side input circuitry.
Diagram
The following diagram shows the field-side input circuitry.
870 USE 002 00 V.2
213
Page 14
170 ADI 340 00
Section 11.3 Configuration Discrete Inputs
Overview
This I/O base supports sixteen discrete inputs. This section describes how to map I/O data between the I/O base and the CPU.
Number of Words
Sixteen bits of discrete input data are returned from the base to the processor as one 16-bit word.
IEC vs. Ladder Logic
In order to correctly field wire the inputs and map the input data, you need to know which type of Momentum Adapter is mounted on the base and which type of programming software has been used to configure and program the CPU. Adapters and programming software may be either IEC compliant or 984 Ladder Logic compliant. IEC Compliant
984 Ladder Logic Compliant
Momentum Processor Adapters
All
None
Momentum Communication Adapters
All, except 170 NEF 110 21 170 NEF 160 21
170 NEF 110 21 170 NEF 160 21
Programming Software
Concept 2.1 or higher
Modsoft 2.5
Continued on next page
214
870 USE 002 00 V.2
Page 15
170 ADI 340 00
Discrete Inputs, Continued
Data Mapping
870 USE 002 00 V.2
The figure below shows how data is mapped between the I/O base and the CPU with different combinations of programming software and adapters.
215
Page 16
170 ADI 340 00
216
870 USE 002 00 V.2