Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Schneider 24430 Spec Sheet

Spec sheet · Schneider

Schneider 24430 Spec Sheet

Spec sheet2 pagesPDF 77 KB

Both pages are below, each with its text.

Download the PDF77 KB

Covers · 1 model

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Schneider Electric product data sheet dated Sep 7, 2018 for the 24430, a Multi 9 C60 UL1077 one-pole 6 A C-curve miniature circuit-breaker. It lists the ratings, breaking capacities under several standards, dimensions, terminals and environmental limits.

What it is
Multi 9 C60 UL1077 miniature circuit-breaker, 1P, thermal-magnetic, C curve p. 1
Rated current
6 A at 77 °F (25 °C) p. 1
UL/CSA breaking capacity
AIR 5 kA at 277 V AC, 10 kA at 240 V AC, 10 kA at 65 V DC (UL 1077, CSA C22.2 No 235) p. 1
IEC breaking capacity
Icu 10 kA at 240 V AC, 3 kA at 415 V AC, 10 kA at 60 V DC (EN/IEC 60947-2) p. 1
Network
AC and DC, 50/60 Hz; system voltage 240 V AC, 415 V AC, 60 V DC p. 1
Size and weight
Height 3.19 in (81 mm), width 0.71 in (18 mm), depth 2.87 in (73 mm); 0.24 lb(US) (0.11 kg) p. 1, 2
Magnetic tripping
8.5 x In +/- 20 % AC; 12 x In +/- 20 % DC p. 1
Mounting
Clip-on, DIN rail; 0.71 in (18 mm) pitch, 2 x 9 mm pitches p. 1
Terminals
Tunnel type, top or bottom, 2.5...25 mm² (AWG 14...AWG 4); strip 0.55 in (14 mm); torque 22.12 lbf.in (2.5 N.m) p. 2
Operation
Toggle with ON/OFF indication and contact position indicator; padlockable p. 1, 2
Durability
Mechanical 20000 cycles; electrical 10000 cycles p. 2
Operating temperature
-22...158 °F (-30...70 °C); storage -40...176 °F (-40...80 °C) p. 2
Protection
IP20; IP40 in a modular enclosure (IEC 60529) p. 2
Standards
The data sheet lists UL 1077, GB 14048.2, EN/IEC 60947-2 and CSA C22.2 No 235 p. 2

What this sheet walks you through

  • Breaking capacity under UL, CSA, IEC and GB standards p. 1
  • Wire size, stripping length and torque for the terminals p. 2

Good to know

  • The data sheet is a general description and is not meant for judging suitability for a specific application. p. 1

Questions this sheet answers

What is the Schneider 24430?

A Multi 9 C60 UL1077 one-pole, 6 A, C-curve miniature circuit-breaker rated 277 V, 5 kA. p. 1

What is the interrupting rating of the 24430 at 277 V AC?

AIR 5 kA at 277 V AC under UL 1077 and CSA C22.2 No 235; at 240 V AC it is 10 kA. p. 1

Can the 24430 be used on DC circuits?

Yes. Its network type is AC and DC, with AIR 10 kA at 65 V DC under UL 1077. p. 1

What wire size fits the 24430 terminals?

Rigid wire of 2.5...25 mm² (AWG 14...AWG 4), top or bottom, tightened to 22.12 lbf.in (2.5 N.m). p. 2

How wide is the 24430 breaker?

0.71 in (18 mm), which is two 9 mm pitches on the DIN rail. p. 1, 2

The file

Size and text

Pages2
PDF77 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Schneider 24430 Spec Sheet

The text of page 1, from the PDF itself

Product data sheet Characteristics

24430

Multi 9 - C60 UL1077 - MCB - 1P - 6 A - C Curve 277 V - 5 kA

Range of productC60RangeMulti 9Product nameMulti 9 C60

Product or componenttype

Miniature circuit-breaker

Device short nameC60 UL1077Device applicationDistributionPoles description1P

Number of protectedpoles

1[In] rated current6 A at 77 °F (25 °C)Network typeDC ACTrip unit technologyThermal-magneticCurve codeCBreaking capacity codeNBreaking capacity

AIR 10 kA at 65 V DC conforming to UL 1077 AIR 10 kA at 65 V DC conforming to CSA C22.2 No 235 Icu 3 kA at 415 V AC conforming to EN/IEC 60947-2 Icu 10 kA at 240 V AC conforming to EN/IEC 60947-2 Icu 3 kA at 415 V AC conforming to GB 14048.2 Icu 10 kA at 240 V AC conforming to GB 14048.2 AIR 5 kA at 277 V AC conforming to UL 1077 AIR 10 kA at 240 V AC conforming to UL 1077 AIR 5 kA at 277 V AC conforming to CSA C22.2 No 235 AIR 10 kA at 240 V AC conforming to CSA C22.2 No 235 Icu 10 kA at 60 V DC conforming to EN/IEC 60947-2 Icu 10 kA at 60 V DC conforming to GB 14048.2

Suitability for isolation

Yes conforming to EN/IEC 60947-2

Complementary Network frequency

50/60 Hz

System Voltage

240 V AC 60 V DC 415 V AC

Magnetic tripping limit

8.5 x In +/- 20 % AC 12 x In +/- 20 % DC

Limitation class

3 conforming to EN/IEC 60947-2

[Ui] rated insulation voltage

500 V ACconforming to EN/IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-2

Contact position indicator

YesControl typeToggleLocal signallingON/OFF indicationMounting modeClip-onMounting supportDIN railConnection pitch

0.71 in (18 mm) Between devices

9 mm pitches2Height3.19 in (81 mm)Sep 7, 20181

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Main

Page 2 of Schneider 24430 Spec Sheet

The text of page 2, from the PDF itself

Width0.71 in (18 mm)Depth2.87 in (73 mm)Product weight0.24 lb(US) (0.11 kg)ColourGreyMechanical durability20000 cyclesElectrical durability10000 cycles

Provision for padlocking

Padlockable

Connections - terminals

Tunnel type terminal, top or bottom rigid wire(s) 0...0.04 in² (2.5...25 mm²) max (AWG 14...AWG 4)

Wire stripping length

0.55 in (14 mm) top or bottom

Tightening torque

22.12 lbf.in (2.5 N.m) top or bottom

Compatibility codeC60_UL1077Environment Standards

UL 1077 GB 14048.2 EN/IEC 60947-2 CSA C22.2 No 235

Product certifications

CSA CCC IEC UR

IP degree of protection

IP40 modular enclosure conforming to IEC 60529 IP20 conforming to IEC 60529

Pollution degree

3 conforming to EN/IEC 60947-2

Overvoltage categoryIVTropicalisation

2 conforming to IEC 60068-1

Relative humidity95 % 131 °F (55 °C)Operating altitude6561.68 ft (2000 m)

Ambient air temperature for operation

-22...158 °F (-30...70 °C)

Ambient air temperature for storage

-40...176 °F (-40...80 °C)

Offer Sustainability Sustainable offer status RoHS (date code: YYWW)

Green Premium product Compliant - since 0629 - Schneider Electric declaration of conformity Electric declaration of conformity

Product environmental profile

Available

Product end of life instructions

Need no specific recycling operations

Contractual warranty Warranty period

Product Life Status
2

18 monthsCommercialisedSchneider-