Spec sheet · Schneider
Multi 9: Modular protection for OEMs, Catalogue 2018
Spec sheet84 pagesPDF 11 MB
Schneider Electric Multi 9 catalog of DIN rail miniature circuit breakers, residual current devices and accessories for OEMs.
Filed with · 6 models
Also filed with these models on the old site
Summary
What is in it
Schneider Electric's 2018 catalog for the Multi 9 range of DIN rail modular protection devices for equipment manufacturers. It lists miniature circuit breakers (C60BP, C60BPR, C60SP, C60H-DC, C60N, C60H, C60L, C60CTRL, N40N) with ratings, breaking capacities, catalog numbers, dimensions and technical data, then residual current devices, auxiliaries, comb busbars and distribution blocks, and technical information on standards, tripping curves and temperature effects.
Its parts
- Miniature circuit breakers
- Residual Current Devices
- Auxiliaries and accessories
- Technical information
- Control panel technical guides library
From the sheet
Key facts from this sheet
Each line names its page in the PDF.
Schneider Electric's 2018 catalogue for the Multi 9 range of DIN rail modular protection devices for equipment makers. It covers the C60BP, C60BPR, C60SP, C60H-DC, C60N, C60H, C60L, C60CTRL and N40N miniature circuit breakers, residual current devices, and common auxiliaries and accessories, with ratings, technical data and catalogue numbers. The catalogue numbers the site files it under (17414, 17423, 24430, 24435, 24503, 24505) do not appear in the pages read.
- Range
- Multi 9: DIN rail modular devices for equipment makers (OEMs), giving protection, signaling functions and accessories p. 3
- Circuit breakers
- C60BP, C60BPR, C60SP, C60H-DC, C60N, C60H, C60L, C60CTRL and N40N miniature circuit breakers p. 9
- C60BP
- C60BP: UL 489 branch circuit breaker, Z, C and D curves, tunnel terminals, 0.5 to 63 A p. 10
- C60BP UL 489 ratings
- C60BP: up to 35 A at 480Y/277V and up to 63 A at 240 V p. 7
- C60BP standards
- The catalogue states UL 489 (document #E215117), CSA C22.2 No 5, IEC/EN 60947-2 and GB 14048-2 conformity for the C60BP p. 11
- C60BP electrical data
- C60BP: insulation voltage 500 V, impulse withstand 6 kV, reference temperature 25°C / 77°F p. 11
- C60BP temperatures
- C60BP: operating -30°C to +70°C / -22°F to 158°F; storage -40°C to +80°C / -40°F to 176°F p. 11
- C60N
- C60N: IEC/EN 60947-2 breaker, B, C and D curves, 1P to 4P, 1 to 63 A p. 20
- C60H
- C60H: IEC/EN 60947-2 breaker, B, C and D curves, 1P to 4P, 1 to 63 A p. 22
- C60H-DC
- C60H-DC: UL1077 breaker for direct current circuits up to 500 V DC p. 7, 9
- Mounting
- Clips on a 35 mm DIN rail, any mounting position p. 11, 21
- Auxiliaries
- Remote tripping and open/closed/tripped indication auxiliaries clip on the left side without tools p. 43
- MN undervoltage release
- MN: trips the breaker when its input voltage falls to between 70 % and 35 % of Un p. 44
- Residual current devices
- GFP ground fault protector, RCCB ID, Vigi C60 and Vigi N40 add-ons, N40 Vigi p. 9
What this sheet walks you through
- Choosing a Multi 9 breaker by standard, trip curve and terminal type p. 9
- C60BP breaking capacities and catalogue numbers p. 10
- Connecting copper cables to the C60BP p. 11
- C60N and C60H breaking capacities and catalogue numbers p. 20, 22
- C60N and C60H connection and technical data p. 21, 23
- Combining indication and tripping auxiliaries on one device p. 43
- Undervoltage releases for emergency stop and preventing accidental startups p. 44
- Shunt releases for tripping from a pushbutton or dry contact p. 45
- Open/closed and fault indicating contacts (OF, OF.S, OFsp, SD, SD+OF) p. 46
Good to know
- Tripping auxiliaries go on first; with two tripping devices, the MN undervoltage release first; among indication auxiliaries, the SD first. p. 43
- Before any servicing, switch off the mains supply, since voltage is present at terminals E1/E2. p. 45
- The C60H-DC is for DC circuits only. p. 9
- The C60CTRL is meant for protecting control circuits. p. 9
Questions this sheet answers
What is the UL 489 rating of the C60BP?
Up to 35 A at 480Y/277V and up to 63 A at 240 V. p. 7
What temperatures can a C60BP work in?
It operates from -30°C to +70°C (-22°F to 158°F) and can be stored from -40°C to +80°C. p. 11
What current ratings does the C60N come in?
1 to 63 A, with B, C or D trip curves and 1 to 4 poles. p. 20
What does the MN undervoltage release do?
It trips the breaker when its input voltage falls to between 70 % and 35 % of Un, and keeps it from closing until the voltage returns. p. 44
How do Multi 9 auxiliaries attach to a breaker?
They clip onto the left-hand side of the breaker with no tool. p. 43
The whole text · 9 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file