The text of a spec sheet · part 3 of 9
Multi 9: Modular protection for OEMs, Catalogue 2018, pages 21 to 30
Pages 21 to 30 of 84
The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Schneider 17414, Schneider 17423, Schneider 24430, Schneider 24435, Schneider 24503 and Schneider 24505
Page 21
Miniature circuit breakers www.schneider-electric.com
IEC/EN 60947-2
C60N - B, C, D curves (cont.) Connection
Without accessory Tightening torque
Rigid, flexible or with ferrule DB122945
14 mm 6.5 mm
PZ2
1
Copper cables
1 to 25 A 32 to 63 A
2.5 N.m (22 lb.in) 3.5 N.m (31 lb.in)
DB122946
DB123060
Rating
1 to 25 mm2 1.5 to 35 mm2
AWG #18 to #3 AWG #16 to #2
Technical data DB118767
According to IEC/EN 60947-2 Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) Thermal tripping Reference temperature Magnetic tripping (Ii) B curve in alternative current in direct current C curve in alternative current in direct current D curve in alternative current in direct current According to current frequency Utilization category
DB123312
Clip on DIN rail 35 mm.
Additional characteristics Degree of protection Device only (IEC 60529) Device in modular enclosure Endurance (O-C) Indifferent position of installation.
IP20
Electrical Mechanical
Service temperature Storage temperature Tropicalization (IEC 60068-1)
IP40
Dissipated power
IP20 IP40 Insulation class II 10,000 cycles 20,000 cycles -30°C to +70°C / -22°F to 158°F -40°C to +80°C / -40°F to 176°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68
Weight (g / oz) Circuit-breaker Type
C60N
1P 2P 3P 4P
120 g / 4.23 oz 240 g / 8.46 oz 360 g / 12.70 oz 480 g / 16.93 oz
Dimensions (mm / inches) DB406067
DB123314
500 V AC 3 6 kV 50°C / 122°F 4 In ± 20 % 5.7 In (± 20 %) 8.5 In ± 20 % 12 In (± 20 %) 12 In ± 20 % 17 In (± 20 %) 50/60 Hz A
72 2.83 54 2.13 36 1.42 mm in
18 0.71
5.5 0.22
81 3.19
72 2.83 44 1.73
16 0.63
45 1.77
5 0.2
21
Page 22
Miniature circuit breakers www.schneider-electric.com
IEC/EN 60947-2
C60H - B, C, D curves DB405227
IEC/EN 60947-2 bb C60H circuit breakers are circuit breakers which combine the following functions: vv circuit protection against short-circuit currents, vv circuit protection against overload currents, vv breaking and industrial disconnection as per standards IEC/EN 60947-2. bb The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.
PB111752-40
PB111747-40
IEC bb Increased product service life thanks: vv overvoltage resistance, vv high performance limitation, vv to fast closing independent of the speed of actuation of the toggle. bb Upstream or downstream connection.
Positive contact indication bb Suitability for isolation in accordance with the IEC/EN 60947-2 standard.
C60H 3P
Alternating current (AC) 50/60 Hz
PB111755-40
PB111750-40
C60H 1P
Ultimate breaking capacity (Icu) as per IEC/EN 60947-2 Voltage (Ue) Ph/Ph (2P, 3P, 4P)
240 V
415 V
-
Ph/N (1P)
-
240 V
415 V
-
30 kA 1.2 x 12 In
15 kA
3 kA(*)
10 kA
Rating (In) iIT
1 to 63 A
440 V
Service breaking capacity (Ics) 50 % of Icu
(*) Breaking capacity under 1 pole with IT isolated neutral system (case of double fault).
C60H 2P
Direct current (DC)
C60H 4P
Breaking capacity (Icu) according to IEC/EN 60947-2 Voltage (Ue)
Catalogue numbers
Between +/- y 72 V y 125 V y 125 V y 250 V
Number of poles
1P
2P
3P
4P
Rating (In) 1 to 63 A
20 kA
25 kA
40 kA
50 kA
Service breaking capacity (Ics) 100 % of Icu
C60N circuit breaker
Auxiliaries Vigi C60 Rating (In)
See page 43 See page 36 Curve B
C
Curve D
4P
B
E45097
3P E45095
2P E45094
1P E45092
Type
Curve C
D
B
Curve C
D
B
C
D
1A M9F13101 M9F14101 M9F15101 M9F13201 M9F14201 M9F15201 M9F13301 M9F14301 M9F15301 M9F13401 M9F14401 M9F15401 2A M9F13102 M9F14102 M9F15102 M9F13202 M9F14202 M9F15202 M9F13302 M9F14302 M9F15302 M9F13402 M9F14402 M9F15402 3A M9F13103 M9F14103 M9F15103 M9F13203 M9F14203 M9F15203 M9F13303 M9F14303 M9F15303 M9F13403 M9F14403 M9F15403 4A M9F13104 M9F14104 M9F15104 M9F13204 M9F14204 M9F15204 M9F13304 M9F14304 M9F15304 M9F13404 M9F14404 M9F15404 6A M9F13106 M9F14106 M9F15106 M9F13206 M9F14206 M9F15206 M9F13306 M9F14306 M9F15306 M9F13406 M9F14406 M9F15406 10 A M9F13110 M9F14110 M9F15110 M9F13210 M9F14210 M9F15210 M9F13310 M9F14310 M9F15310 M9F13410 M9F14410 M9F15410 13 A M9F13113 M9F14113 M9F15113 M9F13213 M9F14213 M9F15213 M9F13313 M9F14313 M9F15313 M9F13413 M9F14413 M9F15413 16 A M9F13116 M9F14116 M9F15116 M9F13216 M9F14216 M9F15216 M9F13316 M9F14316 M9F15316 M9F13416 M9F14416 M9F15416 20 A M9F13120 M9F14120 M9F15120 M9F13220 M9F14220 M9F15220 M9F13320 M9F14320 M9F15320 M9F13420 M9F14420 M9F15420 25 A M9F13125 M9F14125 M9F15125 M9F13225 M9F14225 M9F15225 M9F13325 M9F14325 M9F15325 M9F13425 M9F14425 M9F15425 32 A M9F13132 M9F14132 M9F15132 M9F13232 M9F14232 M9F15232 M9F13332 M9F14332 M9F15332 M9F13432 M9F14432 M9F15432 40 A M9F13140 M9F14140 M9F15140 M9F13240 M9F14240 M9F15240 M9F13340 M9F14340 M9F15340 M9F13440 M9F14440 M9F15440 50 A M9F13150 M9F14150 M9F15150 M9F13250 M9F14250 M9F15250 M9F13350 M9F14350 M9F15350 M9F13450 M9F14450 M9F15450 63 A M9F13163 M9F14163 M9F15163 M9F13263 M9F14263 M9F15263 M9F13363 M9F14363 M9F15363 M9F13463 M9F14463 M9F15463 Width in 9-mm 2 4 6 8 modules Accessories See page 48
22
Page 23
Miniature circuit breakers www.schneider-electric.com
IEC/EN 60947-2
C60H - B, C, D curves (cont.) Connection
Without accessory Tightening torque
Rigid, flexible or with ferrule DB122945
14 mm 6.5 mm
PZ2
1
Copper cables
1 to 25 A 32 to 63 A
2.5 N.m (22 lb.in) 3.5 N.m (31 lb.in)
DB122946
DB123060
Rating
1 to 25 mm2 1.5 to 35 mm2
AWG #18 to #3 AWG #16 to #2
Technical data DB118767
According to IEC/EN 60947-2 Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) Thermal tripping Reference temperature Magnetic tripping (Ii) B curve in alternative current in direct current C curve in alternative current in direct current D curve in alternative current in direct current According to current frequency Utilization category
DB123312
Clip on DIN rail 35 mm.
Additional characteristics Degree of protection Device only (IEC 60529) Device in modular enclosure Endurance (O-C) Indifferent position of installation.
IP20
Electrical Mechanical
Service temperature Storage temperature Tropicalization (IEC 60068-1)
IP40
Dissipated power
IP20 IP40 Insulation class II 10,000 cycles 20,000 cycles -30°C to +70°C / -22°F to 158°F -40°C to +80°C / -40°F to 176°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 38
Weight (g / oz) Circuit-breaker Type
C60H
1P 2P 3P 4P
120 g / 4.23 oz 240 g / 8.46 oz 360 g / 12.70 oz 480 g / 16.93 oz
Dimensions (mm / inches) DB406067
DB123314
500 V AC 3 6 kV 50°C / 122°F 4 In ± 20 % 5.7 In (± 20 %) 8.5 In ± 20 % 12 In (± 20 %) 12 In ± 20 % 17 In (± 20 %) 50/60 Hz A
72 2.83 54 2.13 36 1.42 mm in
18 0.71
5.5 0.22
81 3.19
72 2.83 44 1.73
16 0.63
45 1.77
5 0.2
23
Page 24
Miniature circuit breakers www.schneider-electric.com
IEC/EN 60947-2 C60L - C curve
IEC/EN 60947-2 bb C60L circuit breakers are circuit breakers which combine the following functions: vv circuit protection against short-circuit currents, vv circuit protection against overload currents, vv breaking and industrial disconnection as per standards IEC/EN 60947-2. bb The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.
PB111753-40
PB111748-40
IEC bb Increased product service life thanks: vv overvoltage resistance, vv high performance limitation, vv to fast closing independent of the speed of actuation of the toggle. bb Upstream or downstream connection.
Positive contact indication bb Suitability for isolation in accordance with the IEC/EN 60947-2 standard.
C60L 3P
Alternating current (AC) 50/60 Hz
PB111756-40
PB111763-40
C60L 1P
Ultimate breaking capacity (Icu) as per IEC/EN 60947-2 Voltage (Ue) Ph/Ph (2P, 3P, 4P)
240 V
415 V
-
Ph/N (1P)
-
240 V
415 V
-
50 kA 1.2 x 8.5 In
25 kA
3 kA(*)
20 kA
Rating (In) iIT
1 to 25 A
Service breaking capacity (Ics)
440 V
50 % of Icu
(*) Breaking capacity under 1 pole with IT isolated neutral system (case of double fault).
C60L 2P
C60L 4P
Direct current (DC) Breaking capacity (Icu) according to IEC/EN 60947-2 Voltage (Ue) Between +/- y 72 V y 125 V y 125 V y 250 V
Number of poles
1P
2P
3P
4P
Rating (In) 1 to 25 A
25 kA
30 kA
50 kA
60 kA
Service breaking capacity (Ics) 100 % of Icu
Catalogue numbers C60L circuit breaker 3P
4P
E45097
E45095
2P E45094
1P E45092
Type
24
Auxiliaries
See page 43
Vigi C60
See page 36
Rating (In)
Curve C
Curve C
Curve C
Curve C
1A 2A 3A 4A 6A 10 A 16 A 20 A 25 A Width in 9-mm modules Accessories
M9F17101 M9F17102 M9F17103 M9F17104 M9F17106 M9F17110 M9F17116 M9F17120 M9F17125 2 See page 48
M9F17201 M9F17202 M9F17203 M9F17204 M9F17206 M9F17210 M9F17216 M9F17220 M9F17225 4
M9F17301 M9F17302 M9F17303 M9F17304 M9F17306 M9F17310 M9F17316 M9F17320 M9F17325 6
M9F17401 M9F17402 M9F17403 M9F17404 M9F17406 M9F17410 M9F17416 M9F17420 M9F17425 8
Page 25
Miniature circuit breakers www.schneider-electric.com
IEC/EN 60947-2
C60L - C curve (cont.) Connection
Without accessory Tightening torque
1
Copper cables Rigid, flexible or with ferrule DB122945
14 mm 6.5 mm
1 to 25 A
2.5 N.m (22 lb.in)
DB122946
DB123060
Rating
1 to 25 mm2
AWG #18 to #3
PZ2
Technical data DB118767
According to IEC/EN 60947-2 Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) Thermal tripping Reference temperature Magnetic tripping (Ii) C curve in alternative current in direct current According to current frequency Utilization category
Clip on DIN rail 35 mm.
500 V AC 3 6 kV 50°C / 122°F 8.5 In ± 20 % 12 In (± 20 %) 50/60 Hz A
Additional characteristics DB123312
Degree of protection Device only (IEC 60529) Device in modular enclosure Endurance (O-C)
Electrical Mechanical
Service temperature Storage temperature Tropicalization (IEC 60068-1)
IP20
Dissipated power
IP40 Weight (g / oz) Circuit-breaker Type
C60L
1P 2P 3P 4P
120 g / 4.23 oz 240 g / 8.46 oz 360 g / 12.70 oz 480 g / 16.93 oz
Dimensions (mm / inches) DB406067
DB123314
Indifferent position of installation.
IP20 IP40 Insulation class II 10,000 cycles 20,000 cycles -30°C to +70°C / -22°F to 158°F -40°C to +80°C / -40°F to 176°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68
72 2.83 54 2.13 36 1.42 mm in
18 0.71
5.5 0.22
81 3.19
72 2.83 44 1.73
16 0.63
45 1.77
5 0.2
25
Page 26
Miniature circuit breakers www.schneider-electric.com
IEC/EN 60947-2
C60CTRL - Z and C curves – For control circuits protection IEC/EN 60947-2. "C60CTRL circuit breakers for the protection of control circuits" protect and isolate: bb control circuits for industrial equipment with contactor coils, transformers, small motors, etc. bb programmable controllers (PLCs), voltage presence indicators, measuring and monitoring instruments, etc. bb single-phase auxiliary circuits such as solenoid valves, battery chargers, etc. bb C60CTRL circuit breakers combine the following features: vv protection of circuits against short-circuit and overload currents, vv breaking and isolation capability in the industrial sector to IEC/EN 60947-2.
PB112743-40
PB112742-40
IEC bb The presence of the green strip guarantees that the contacts open physically and allows work to be carried out safely on the downstream circuit. bb The service life of the products is improved by: vv good overvoltage withstand capacity, vv fast closure, independent of handle operating speed. C60CTRL 1P
C60CTRL 2P bb They can be connected upstream and downstream.
Alternating current (AC) 50/60 Hz
Breaking capacity (Icu) to IEC/EN 60947-2 Voltage (Ue) Ph/Ph (2P) Ph/N (1P) Rating (In)
240 V 100 kA
1 to 4 A
Service breaking capacity (Ics) 415 V 240 V 100 kA
50 % of Icu
Direct current (DC)
Breaking capacity (Icu) to IEC/EN 60947-2 Voltage (Ue)
Service breaking capacity (Ics)
Between +/-
60 V
125 V
Number of poles
1P
2P
25 kA
30 kA
Rating (In)
1 to 4 A
100 % of Icu
Catalogue numbers C60CTRL circuit breakers for the protection of control circuits 1P
2P
26
E45094
E45092
Type
Auxiliaries
See page 43
Vigi C60
See page 36
Rating (In)
C curve
Z curve
C curve
Z curve
1A 2A 3A 4A Width in 9 mm modules Accessories
M9C01101 M9C01102 M9C01103 M9C01104 2 See page 48
M9C02301 M9C02302 M9C02303 M9C02304
M9C01201 M9C01202 M9C01203 M9C01204 4
M9C02401 M9C02402 M9C02403 M9C02404
Page 27
Miniature circuit breakers www.schneider-electric.com
IEC/EN 60947-2
C60CTRL - Z and C curves – For control circuits protection (cont.) Connection
Without accessory Tightening torque
1
Copper cables Rigid, flexible or with ferrule DB122945
14 mm 6.5 mm
1 to 4 A
2.5 N.m (22 lb.in)
DB122946
DB123060
Rating
1 to 25 mm2
AWG #18 to #3
PZ2
Technical data DB118767
According to IEC/EN 60947-2 Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) Thermal tripping Reference temperature Magnetic tripping (Ii) C curve in alternative current in direct current Z curve in alternative current in direct current According to current frequency Utilization category
Clip on DIN rail 35 mm.
DB123312
Additional characteristics Degree of protection Device only (IEC 60529) Device in modular enclosure Endurance (O-C)
Electrical Mechanical Operating temperature Storage temperature Tropicalization (IEC 60068-1)
Indifferent position of installation.
Dissipated power
IP20
IP20 IP40 Insulation class II 10,000 cycles 20,000 cycles -30°C to +70°C / -22°F to 158°F -40°C to +80°C / -40°F to 176°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68
IP40
Weight (g / oz) Circuit breakers Type
C60CTRL
1P 2P
120 g / 4.23 oz 240 g / 8.46 oz
Dimensions (mm / inches) DB406222
DB123314
500 V AC 1 6 kV 50°C / 122°F 8.5 In ± 20 % 12 In (± 20 %) 3 In ± 20 % 4.2 In (± 20 %) 50/60 Hz A mm in
2P 1P
36 1.42 18 0.71
5.5 0.22
81 3.19
72 2.83 44 1.73
16 0.63
45 1.77
5 0.2
27
Page 28
Miniature circuit breakers www.schneider-electric.com
IEC/EN 60947-2 N40N - C curve
IEC/EN 60947-2
PB111758-40
PB111757-40
IEC bb N40N circuit breakers are circuit breakers which combine the following functions: vv circuit protection against short-circuit currents, vv circuit protection against overload currents, vv breaking and industrial disconnection as per standards IEC/EN 60947-2. bb The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety. bb Increased product service life thanks: vv overvoltage resistance, vv high performance limitation, vv to fast closing independent of the speed of actuation of the toggle. bb Upstream or downstream connection.
Positive contact indication bb Suitability for isolation in accordance with the IEC/EN 60947-2 standard.
Alternating current (AC) 50/60 Hz
Ultimate breaking capacity (Icu) as per IEC/EN 60947-2 Voltage (Ue) Ph/Ph (3P+N)
415 V
Ph/N (1P+N)
240 V
Rating (In)
10 kA
1 to 40 A iIT
75 % of Icu
1.2 x 8.5 In
Catalogue numbers N40N circuit breakers 10 kA
28
3P+N DB123661
1P+N DB123389
Type
Service breaking capacity (Ics)
Auxiliaries
See page 43
Vigi
See page 38
Rating (In)
C curve
C curve
1A 2A 3A 4A 6A 10 A 16 A 20 A 25 A 32 A 40 A Width in 9-mm modules
M9P22601 M9P22602 M9P22603 M9P22604 M9P22606 M9P22610 M9P22616 M9P22620 M9P22625 M9P22632 M9P22640 2
M9P22706 M9P22710 M9P22716 M9P22720 M9P22725 M9P22732 M9P22740 6
Accessories
See page 48
Page 29
Miniature circuit breakers www.schneider-electric.com
IEC/EN 60947-2
N40N - C curve (cont.) Connection Rigid
5.5 mm
PZ2
1
Copper cables Flexible or with ferrule
DB122945
13 mm
Tightening torque
1 to 40 A
2 N.m (18 lb.in)
DB122946
DB123947
Rating
0.75 to 16 mm2
AWG #18 to #6
0.33 to 10 mm2
AWG #22 to #8 bb Connection by comb busbar or cables (as per EN 50027).
DB123310
Technical data Main characteristics According to IEC/EN 60947-2 Insulation voltage (Ui) Thermal tripping
Phase-to-phase
240...415 V AC
Reference temperature
50°C / 122°F
Magnetic tripping
C curve
8.5 In (± 20 %)
Rated impulse withstand voltage (Uimp) Pollution degree
Clips on to 35 mm DIN rail.
4 kV 3
Additional characteristics Device only IP20 Device in modular enclosure IP40 Insulation class II Endurance (O-C) Electrical y 20 A 20,000 cycles u 25 A 10,000 cycles Mechanical 20,000 cycles Operating temperature -25°C to +70°C / -13°F to 158°F Storage temperature -40°C to +70°C / -40°F to 158°F Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95 % at 55°C / 131°F) Dissipated power See page 68
DB123312
Degree of protection (IEC 60529)
IP20
IP40 Dimensions (mm / inches) DB406070
DB123314
Indifferent position of installation.
mm in
3P+N 1P+N
54 18 2.13 0.71
81 3.19
4.5 0.18
5.5 0.22
44 1.73
78 3.07
45 1.77
4.5 0.18
Weight (g / oz) Circuit breakers Type
N40N
1P+N 3P+N
115 g / 4.06 oz 322 g / 11.35 oz
29
Page 30
Residual Current Devices www.schneider-electric.com
UL + IEC/EN
IEC/EN 61008-1 UL 1053
IEC
UL 1053 residual current circuit breakers already protected upstream by a shortcircuit and overload protection device are used for: bb control and disconnection of electric circuits bb protection of people against electric shock by direct and indirect contacts bb protection of installations against insulation faults bb enhanced continuity of supply, during a series of close lightning strokes, IT earthing system, equipment including interference suppression filters, variable speed controllers, frequency converters, electronic ballasts for lighting bb enhanced earth leakage protection: in presence of harmonics or high frequency rejections.
PB116670-40
DB105727
GFP - UL 1053 & IEC/EN 61008 - Ground Fault Protector
They comply with RCD standards UL 1053 and IEC/EN 61008. A-SI type GFPs are ideal for operation in environments with a humid atmosphere and/or polluted by aggressive agents: swimming pools, marinas, agri-food industries, water treatment stations, industrial sites, etc.
PB116671-40
Catalogue numbers GFP UL 1053 type A-SI A-SI type
Auxiliaries 2P
Rating Sensitivity (A) (mA) UL IEC/ 1053 EN 61008
26 86 260 26 260 26
30 100 300 30 300 30
M9R81225 M9R12225 M9R84225 M9R81240 M9R84240 M9R81263
M9R41225 M9R44225 M9R41240 -
4
26 86 260 40 26 260 63 26 86 100 86 260 Accessories See page 48 Voltage rating 2P 230 - 240 V (Ue) 4P 400 - 415 V Operating frequency 50/60 Hz
30 100 300 30 300 30 100 100 300
-
M9R81425 M9R12425 M9R84425 M9R81440 M9R84440 M9R81463 M9R12463 M9R12491 M9R84491
8
DB109525
25
63 DB109526
4P 25
UL 486A connections for copper cables, document #E216919 DB123537
Without accessory
Tightening torque
Copper cables Rigid, flexible or with ferrule DB122946
6.5 mm DB122945
14 mm
120 or 240 V 230 or 240 V
Width in mod. of 9 mm 240 V 480Y/277 V (0.354 in.) 230/400 or 240/415 V
Without auxiliaries
40
Rating
Cat. no.
IEC/EN 61008-1
UL 486A-B
1 to 35 mm2
AWG #18 to #2
PZ2 25 to 100 A
30
3.5 N.m (31 lb.in)