Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 3 of 9

Multi 9: Modular protection for OEMs, Catalogue 2018, pages 21 to 30

Pages 21 to 30 of 84

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Schneider 17414, Schneider 17423, Schneider 24430, Schneider 24435, Schneider 24503 and Schneider 24505

Page 21

Miniature circuit breakers www.schneider-electric.com

IEC/EN 60947-2

C60N - B, C, D curves (cont.) Connection

Without accessory Tightening torque

Rigid, flexible or with ferrule DB122945

14 mm 6.5 mm

PZ2

1

Copper cables

1 to 25 A 32 to 63 A

2.5 N.m (22 lb.in) 3.5 N.m (31 lb.in)

DB122946

DB123060

Rating

1 to 25 mm2 1.5 to 35 mm2

AWG #18 to #3 AWG #16 to #2

Technical data DB118767

According to IEC/EN 60947-2 Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) Thermal tripping Reference temperature Magnetic tripping (Ii) B curve in alternative current in direct current C curve in alternative current in direct current D curve in alternative current in direct current According to current frequency Utilization category

DB123312

Clip on DIN rail 35 mm.

Additional characteristics Degree of protection Device only (IEC 60529) Device in modular enclosure Endurance (O-C) Indifferent position of installation.

IP20

Electrical Mechanical

Service temperature Storage temperature Tropicalization (IEC 60068-1)

IP40

Dissipated power

IP20 IP40 Insulation class II 10,000 cycles 20,000 cycles -30°C to +70°C / -22°F to 158°F -40°C to +80°C / -40°F to 176°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68

Weight (g / oz) Circuit-breaker Type

C60N

1P 2P 3P 4P

120 g / 4.23 oz 240 g / 8.46 oz 360 g / 12.70 oz 480 g / 16.93 oz

Dimensions (mm / inches) DB406067

DB123314

500 V AC 3 6 kV 50°C / 122°F 4 In ± 20 % 5.7 In (± 20 %) 8.5 In ± 20 % 12 In (± 20 %) 12 In ± 20 % 17 In (± 20 %) 50/60 Hz A

72 2.83 54 2.13 36 1.42 mm in

18 0.71

5.5 0.22

81 3.19

72 2.83 44 1.73

16 0.63

45 1.77

5 0.2

21

Page 22

Miniature circuit breakers www.schneider-electric.com

IEC/EN 60947-2

C60H - B, C, D curves DB405227

IEC/EN 60947-2 bb C60H circuit breakers are circuit breakers which combine the following functions: vv circuit protection against short-circuit currents, vv circuit protection against overload currents, vv breaking and industrial disconnection as per standards IEC/EN 60947-2. bb The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.

PB111752-40

PB111747-40

IEC bb Increased product service life thanks: vv overvoltage resistance, vv high performance limitation, vv to fast closing independent of the speed of actuation of the toggle. bb Upstream or downstream connection.

Positive contact indication bb Suitability for isolation in accordance with the IEC/EN 60947-2 standard.

C60H 3P

Alternating current (AC) 50/60 Hz

PB111755-40

PB111750-40

C60H 1P

Ultimate breaking capacity (Icu) as per IEC/EN 60947-2 Voltage (Ue) Ph/Ph (2P, 3P, 4P)

240 V

415 V

-

Ph/N (1P)

-

240 V

415 V

-

30 kA 1.2 x 12 In

15 kA

3 kA(*)

10 kA

Rating (In) iIT

1 to 63 A

440 V

Service breaking capacity (Ics) 50 % of Icu

(*) Breaking capacity under 1 pole with IT isolated neutral system (case of double fault).

C60H 2P

Direct current (DC)

C60H 4P

Breaking capacity (Icu) according to IEC/EN 60947-2 Voltage (Ue)

Catalogue numbers

Between +/- y 72 V y 125 V y 125 V y 250 V

Number of poles

1P

2P

3P

4P

Rating (In) 1 to 63 A

20 kA

25 kA

40 kA

50 kA

Service breaking capacity (Ics) 100 % of Icu

C60N circuit breaker

Auxiliaries Vigi C60 Rating (In)

See page 43 See page 36 Curve B

C

Curve D

4P

B

E45097

3P E45095

2P E45094

1P E45092

Type

Curve C

D

B

Curve C

D

B

C

D

1A M9F13101 M9F14101 M9F15101 M9F13201 M9F14201 M9F15201 M9F13301 M9F14301 M9F15301 M9F13401 M9F14401 M9F15401 2A M9F13102 M9F14102 M9F15102 M9F13202 M9F14202 M9F15202 M9F13302 M9F14302 M9F15302 M9F13402 M9F14402 M9F15402 3A M9F13103 M9F14103 M9F15103 M9F13203 M9F14203 M9F15203 M9F13303 M9F14303 M9F15303 M9F13403 M9F14403 M9F15403 4A M9F13104 M9F14104 M9F15104 M9F13204 M9F14204 M9F15204 M9F13304 M9F14304 M9F15304 M9F13404 M9F14404 M9F15404 6A M9F13106 M9F14106 M9F15106 M9F13206 M9F14206 M9F15206 M9F13306 M9F14306 M9F15306 M9F13406 M9F14406 M9F15406 10 A M9F13110 M9F14110 M9F15110 M9F13210 M9F14210 M9F15210 M9F13310 M9F14310 M9F15310 M9F13410 M9F14410 M9F15410 13 A M9F13113 M9F14113 M9F15113 M9F13213 M9F14213 M9F15213 M9F13313 M9F14313 M9F15313 M9F13413 M9F14413 M9F15413 16 A M9F13116 M9F14116 M9F15116 M9F13216 M9F14216 M9F15216 M9F13316 M9F14316 M9F15316 M9F13416 M9F14416 M9F15416 20 A M9F13120 M9F14120 M9F15120 M9F13220 M9F14220 M9F15220 M9F13320 M9F14320 M9F15320 M9F13420 M9F14420 M9F15420 25 A M9F13125 M9F14125 M9F15125 M9F13225 M9F14225 M9F15225 M9F13325 M9F14325 M9F15325 M9F13425 M9F14425 M9F15425 32 A M9F13132 M9F14132 M9F15132 M9F13232 M9F14232 M9F15232 M9F13332 M9F14332 M9F15332 M9F13432 M9F14432 M9F15432 40 A M9F13140 M9F14140 M9F15140 M9F13240 M9F14240 M9F15240 M9F13340 M9F14340 M9F15340 M9F13440 M9F14440 M9F15440 50 A M9F13150 M9F14150 M9F15150 M9F13250 M9F14250 M9F15250 M9F13350 M9F14350 M9F15350 M9F13450 M9F14450 M9F15450 63 A M9F13163 M9F14163 M9F15163 M9F13263 M9F14263 M9F15263 M9F13363 M9F14363 M9F15363 M9F13463 M9F14463 M9F15463 Width in 9-mm 2 4 6 8 modules Accessories See page 48

22

Page 23

Miniature circuit breakers www.schneider-electric.com

IEC/EN 60947-2

C60H - B, C, D curves (cont.) Connection

Without accessory Tightening torque

Rigid, flexible or with ferrule DB122945

14 mm 6.5 mm

PZ2

1

Copper cables

1 to 25 A 32 to 63 A

2.5 N.m (22 lb.in) 3.5 N.m (31 lb.in)

DB122946

DB123060

Rating

1 to 25 mm2 1.5 to 35 mm2

AWG #18 to #3 AWG #16 to #2

Technical data DB118767

According to IEC/EN 60947-2 Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) Thermal tripping Reference temperature Magnetic tripping (Ii) B curve in alternative current in direct current C curve in alternative current in direct current D curve in alternative current in direct current According to current frequency Utilization category

DB123312

Clip on DIN rail 35 mm.

Additional characteristics Degree of protection Device only (IEC 60529) Device in modular enclosure Endurance (O-C) Indifferent position of installation.

IP20

Electrical Mechanical

Service temperature Storage temperature Tropicalization (IEC 60068-1)

IP40

Dissipated power

IP20 IP40 Insulation class II 10,000 cycles 20,000 cycles -30°C to +70°C / -22°F to 158°F -40°C to +80°C / -40°F to 176°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 38

Weight (g / oz) Circuit-breaker Type

C60H

1P 2P 3P 4P

120 g / 4.23 oz 240 g / 8.46 oz 360 g / 12.70 oz 480 g / 16.93 oz

Dimensions (mm / inches) DB406067

DB123314

500 V AC 3 6 kV 50°C / 122°F 4 In ± 20 % 5.7 In (± 20 %) 8.5 In ± 20 % 12 In (± 20 %) 12 In ± 20 % 17 In (± 20 %) 50/60 Hz A

72 2.83 54 2.13 36 1.42 mm in

18 0.71

5.5 0.22

81 3.19

72 2.83 44 1.73

16 0.63

45 1.77

5 0.2

23

Page 24

Miniature circuit breakers www.schneider-electric.com

IEC/EN 60947-2 C60L - C curve

IEC/EN 60947-2 bb C60L circuit breakers are circuit breakers which combine the following functions: vv circuit protection against short-circuit currents, vv circuit protection against overload currents, vv breaking and industrial disconnection as per standards IEC/EN 60947-2. bb The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.

PB111753-40

PB111748-40

IEC bb Increased product service life thanks: vv overvoltage resistance, vv high performance limitation, vv to fast closing independent of the speed of actuation of the toggle. bb Upstream or downstream connection.

Positive contact indication bb Suitability for isolation in accordance with the IEC/EN 60947-2 standard.

C60L 3P

Alternating current (AC) 50/60 Hz

PB111756-40

PB111763-40

C60L 1P

Ultimate breaking capacity (Icu) as per IEC/EN 60947-2 Voltage (Ue) Ph/Ph (2P, 3P, 4P)

240 V

415 V

-

Ph/N (1P)

-

240 V

415 V

-

50 kA 1.2 x 8.5 In

25 kA

3 kA(*)

20 kA

Rating (In) iIT

1 to 25 A

Service breaking capacity (Ics)

440 V

50 % of Icu

(*) Breaking capacity under 1 pole with IT isolated neutral system (case of double fault).

C60L 2P

C60L 4P

Direct current (DC) Breaking capacity (Icu) according to IEC/EN 60947-2 Voltage (Ue) Between +/- y 72 V y 125 V y 125 V y 250 V

Number of poles

1P

2P

3P

4P

Rating (In) 1 to 25 A

25 kA

30 kA

50 kA

60 kA

Service breaking capacity (Ics) 100 % of Icu

Catalogue numbers C60L circuit breaker 3P

4P

E45097

E45095

2P E45094

1P E45092

Type

24

Auxiliaries

See page 43

Vigi C60

See page 36

Rating (In)

Curve C

Curve C

Curve C

Curve C

1A 2A 3A 4A 6A 10 A 16 A 20 A 25 A Width in 9-mm modules Accessories

M9F17101 M9F17102 M9F17103 M9F17104 M9F17106 M9F17110 M9F17116 M9F17120 M9F17125 2 See page 48

M9F17201 M9F17202 M9F17203 M9F17204 M9F17206 M9F17210 M9F17216 M9F17220 M9F17225 4

M9F17301 M9F17302 M9F17303 M9F17304 M9F17306 M9F17310 M9F17316 M9F17320 M9F17325 6

M9F17401 M9F17402 M9F17403 M9F17404 M9F17406 M9F17410 M9F17416 M9F17420 M9F17425 8

Page 25

Miniature circuit breakers www.schneider-electric.com

IEC/EN 60947-2

C60L - C curve (cont.) Connection

Without accessory Tightening torque

1

Copper cables Rigid, flexible or with ferrule DB122945

14 mm 6.5 mm

1 to 25 A

2.5 N.m (22 lb.in)

DB122946

DB123060

Rating

1 to 25 mm2

AWG #18 to #3

PZ2

Technical data DB118767

According to IEC/EN 60947-2 Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) Thermal tripping Reference temperature Magnetic tripping (Ii) C curve in alternative current in direct current According to current frequency Utilization category

Clip on DIN rail 35 mm.

500 V AC 3 6 kV 50°C / 122°F 8.5 In ± 20 % 12 In (± 20 %) 50/60 Hz A

Additional characteristics DB123312

Degree of protection Device only (IEC 60529) Device in modular enclosure Endurance (O-C)

Electrical Mechanical

Service temperature Storage temperature Tropicalization (IEC 60068-1)

IP20

Dissipated power

IP40 Weight (g / oz) Circuit-breaker Type

C60L

1P 2P 3P 4P

120 g / 4.23 oz 240 g / 8.46 oz 360 g / 12.70 oz 480 g / 16.93 oz

Dimensions (mm / inches) DB406067

DB123314

Indifferent position of installation.

IP20 IP40 Insulation class II 10,000 cycles 20,000 cycles -30°C to +70°C / -22°F to 158°F -40°C to +80°C / -40°F to 176°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68

72 2.83 54 2.13 36 1.42 mm in

18 0.71

5.5 0.22

81 3.19

72 2.83 44 1.73

16 0.63

45 1.77

5 0.2

25

Page 26

Miniature circuit breakers www.schneider-electric.com

IEC/EN 60947-2

C60CTRL - Z and C curves – For control circuits protection IEC/EN 60947-2. "C60CTRL circuit breakers for the protection of control circuits" protect and isolate: bb control circuits for industrial equipment with contactor coils, transformers, small motors, etc. bb programmable controllers (PLCs), voltage presence indicators, measuring and monitoring instruments, etc. bb single-phase auxiliary circuits such as solenoid valves, battery chargers, etc. bb C60CTRL circuit breakers combine the following features: vv protection of circuits against short-circuit and overload currents, vv breaking and isolation capability in the industrial sector to IEC/EN 60947-2.

PB112743-40

PB112742-40

IEC bb The presence of the green strip guarantees that the contacts open physically and allows work to be carried out safely on the downstream circuit. bb The service life of the products is improved by: vv good overvoltage withstand capacity, vv fast closure, independent of handle operating speed. C60CTRL 1P

C60CTRL 2P bb They can be connected upstream and downstream.

Alternating current (AC) 50/60 Hz

Breaking capacity (Icu) to IEC/EN 60947-2 Voltage (Ue) Ph/Ph (2P) Ph/N (1P) Rating (In)

240 V 100 kA

1 to 4 A

Service breaking capacity (Ics) 415 V 240 V 100 kA

50 % of Icu

Direct current (DC)

Breaking capacity (Icu) to IEC/EN 60947-2 Voltage (Ue)

Service breaking capacity (Ics)

Between +/-

60 V

125 V

Number of poles

1P

2P

25 kA

30 kA

Rating (In)

1 to 4 A

100 % of Icu

Catalogue numbers C60CTRL circuit breakers for the protection of control circuits 1P

2P

26

E45094

E45092

Type

Auxiliaries

See page 43

Vigi C60

See page 36

Rating (In)

C curve

Z curve

C curve

Z curve

1A 2A 3A 4A Width in 9 mm modules Accessories

M9C01101 M9C01102 M9C01103 M9C01104 2 See page 48

M9C02301 M9C02302 M9C02303 M9C02304

M9C01201 M9C01202 M9C01203 M9C01204 4

M9C02401 M9C02402 M9C02403 M9C02404

Page 27

Miniature circuit breakers www.schneider-electric.com

IEC/EN 60947-2

C60CTRL - Z and C curves – For control circuits protection (cont.) Connection

Without accessory Tightening torque

1

Copper cables Rigid, flexible or with ferrule DB122945

14 mm 6.5 mm

1 to 4 A

2.5 N.m (22 lb.in)

DB122946

DB123060

Rating

1 to 25 mm2

AWG #18 to #3

PZ2

Technical data DB118767

According to IEC/EN 60947-2 Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) Thermal tripping Reference temperature Magnetic tripping (Ii) C curve in alternative current in direct current Z curve in alternative current in direct current According to current frequency Utilization category

Clip on DIN rail 35 mm.

DB123312

Additional characteristics Degree of protection Device only (IEC 60529) Device in modular enclosure Endurance (O-C)

Electrical Mechanical Operating temperature Storage temperature Tropicalization (IEC 60068-1)

Indifferent position of installation.

Dissipated power

IP20

IP20 IP40 Insulation class II 10,000 cycles 20,000 cycles -30°C to +70°C / -22°F to 158°F -40°C to +80°C / -40°F to 176°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68

IP40

Weight (g / oz) Circuit breakers Type

C60CTRL

1P 2P

120 g / 4.23 oz 240 g / 8.46 oz

Dimensions (mm / inches) DB406222

DB123314

500 V AC 1 6 kV 50°C / 122°F 8.5 In ± 20 % 12 In (± 20 %) 3 In ± 20 % 4.2 In (± 20 %) 50/60 Hz A mm in

2P 1P

36 1.42 18 0.71

5.5 0.22

81 3.19

72 2.83 44 1.73

16 0.63

45 1.77

5 0.2

27

Page 28

Miniature circuit breakers www.schneider-electric.com

IEC/EN 60947-2 N40N - C curve

IEC/EN 60947-2

PB111758-40

PB111757-40

IEC bb N40N circuit breakers are circuit breakers which combine the following functions: vv circuit protection against short-circuit currents, vv circuit protection against overload currents, vv breaking and industrial disconnection as per standards IEC/EN 60947-2. bb The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety. bb Increased product service life thanks: vv overvoltage resistance, vv high performance limitation, vv to fast closing independent of the speed of actuation of the toggle. bb Upstream or downstream connection.

Positive contact indication bb Suitability for isolation in accordance with the IEC/EN 60947-2 standard.

Alternating current (AC) 50/60 Hz

Ultimate breaking capacity (Icu) as per IEC/EN 60947-2 Voltage (Ue) Ph/Ph (3P+N)

415 V

Ph/N (1P+N)

240 V

Rating (In)

10 kA

1 to 40 A iIT

75 % of Icu

1.2 x 8.5 In

Catalogue numbers N40N circuit breakers 10 kA

28

3P+N DB123661

1P+N DB123389

Type

Service breaking capacity (Ics)

Auxiliaries

See page 43

Vigi

See page 38

Rating (In)

C curve

C curve

1A 2A 3A 4A 6A 10 A 16 A 20 A 25 A 32 A 40 A Width in 9-mm modules

M9P22601 M9P22602 M9P22603 M9P22604 M9P22606 M9P22610 M9P22616 M9P22620 M9P22625 M9P22632 M9P22640 2

M9P22706 M9P22710 M9P22716 M9P22720 M9P22725 M9P22732 M9P22740 6

Accessories

See page 48

Page 29

Miniature circuit breakers www.schneider-electric.com

IEC/EN 60947-2

N40N - C curve (cont.) Connection Rigid

5.5 mm

PZ2

1

Copper cables Flexible or with ferrule

DB122945

13 mm

Tightening torque

1 to 40 A

2 N.m (18 lb.in)

DB122946

DB123947

Rating

0.75 to 16 mm2

AWG #18 to #6

0.33 to 10 mm2

AWG #22 to #8 bb Connection by comb busbar or cables (as per EN 50027).

DB123310

Technical data Main characteristics According to IEC/EN 60947-2 Insulation voltage (Ui) Thermal tripping

Phase-to-phase

240...415 V AC

Reference temperature

50°C / 122°F

Magnetic tripping

C curve

8.5 In (± 20 %)

Rated impulse withstand voltage (Uimp) Pollution degree

Clips on to 35 mm DIN rail.

4 kV 3

Additional characteristics Device only IP20 Device in modular enclosure IP40 Insulation class II Endurance (O-C) Electrical y 20 A 20,000 cycles u 25 A 10,000 cycles Mechanical 20,000 cycles Operating temperature -25°C to +70°C / -13°F to 158°F Storage temperature -40°C to +70°C / -40°F to 158°F Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95 % at 55°C / 131°F) Dissipated power See page 68

DB123312

Degree of protection (IEC 60529)

IP20

IP40 Dimensions (mm / inches) DB406070

DB123314

Indifferent position of installation.

mm in

3P+N 1P+N

54 18 2.13 0.71

81 3.19

4.5 0.18

5.5 0.22

44 1.73

78 3.07

45 1.77

4.5 0.18

Weight (g / oz) Circuit breakers Type

N40N

1P+N 3P+N

115 g / 4.06 oz 322 g / 11.35 oz

29

Page 30

Residual Current Devices www.schneider-electric.com

UL + IEC/EN

IEC/EN 61008-1 UL 1053

IEC

UL 1053 residual current circuit breakers already protected upstream by a shortcircuit and overload protection device are used for: bb control and disconnection of electric circuits bb protection of people against electric shock by direct and indirect contacts bb protection of installations against insulation faults bb enhanced continuity of supply, during a series of close lightning strokes, IT earthing system, equipment including interference suppression filters, variable speed controllers, frequency converters, electronic ballasts for lighting bb enhanced earth leakage protection: in presence of harmonics or high frequency rejections.

PB116670-40

DB105727

GFP - UL 1053 & IEC/EN 61008 - Ground Fault Protector

They comply with RCD standards UL 1053 and IEC/EN 61008. A-SI type GFPs are ideal for operation in environments with a humid atmosphere and/or polluted by aggressive agents: swimming pools, marinas, agri-food industries, water treatment stations, industrial sites, etc.

PB116671-40

Catalogue numbers GFP UL 1053 type A-SI A-SI type

Auxiliaries 2P

Rating Sensitivity (A) (mA) UL IEC/ 1053 EN 61008

26 86 260 26 260 26

30 100 300 30 300 30

M9R81225 M9R12225 M9R84225 M9R81240 M9R84240 M9R81263

M9R41225 M9R44225 M9R41240 -

4

26 86 260 40 26 260 63 26 86 100 86 260 Accessories See page 48 Voltage rating 2P 230 - 240 V (Ue) 4P 400 - 415 V Operating frequency 50/60 Hz

30 100 300 30 300 30 100 100 300

-

M9R81425 M9R12425 M9R84425 M9R81440 M9R84440 M9R81463 M9R12463 M9R12491 M9R84491

8

DB109525

25

63 DB109526

4P 25

UL 486A connections for copper cables, document #E216919 DB123537

Without accessory

Tightening torque

Copper cables Rigid, flexible or with ferrule DB122946

6.5 mm DB122945

14 mm

120 or 240 V 230 or 240 V

Width in mod. of 9 mm 240 V 480Y/277 V (0.354 in.) 230/400 or 240/415 V

Without auxiliaries

40

Rating

Cat. no.

IEC/EN 61008-1

UL 486A-B

1 to 35 mm2

AWG #18 to #2

PZ2 25 to 100 A

30

3.5 N.m (31 lb.in)