Residual Current Devices www.schneider-electric.com
UL + IEC/EN
GFP - UL 1053 & IEC/EN 61008 - Ground Fault Protector (cont.) DB118767
Technical data GFP UL 1053 type A-SI Technical data Insulation voltage (Ui) Pollution degree Making and breaking capacity: rated residual current (IDm) Rated impulse withstand voltage (Uimp) Utilisation category Level of immunity
DB123312
Clip on DIN rail 35 mm.
6 kV AC 23A In current wave 8/20 µs: 3 k In dampened recurrent current wave 0.5 µs/100 kHz: 200 A 10 kA with 100 A gG upstream fuse
Short-circuit current withstand (IDc = Inc) Test button minimum 2P operating voltage 4P Phase-to-phase test circuit
IP40
Earth fault indication Number of cycles (O-C) Degree of protection (IEC 60529)
2
Instantaneous release: UL 1053 : ±15 % IEC/EN 61008 : +0 %, -50 % Residual current protection down to 0 V according to IEC/EN 61008-1 § 3.3.4
Behaviour in case of voltage drop
Device only Device in modular enclosure
Operating temperature Storage temperature Tropicalization (IEC 60068-1)
On front face by red mechanical indicator 20,000 cycles IP20 IP40 Insulation class II -25°C to +60°C / -13°F to 140°F -40°C to +70°C / -40°F to 158°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68
Dissipated power
Weight (g / oz) GFP UL 1053 type A-SI Type
GFP
2P 4P
220 g / 7.76 oz 450 g / 15.87 oz
Dimensions (mm / inches) DB124109
IP20
113 V AC 189 V AC To avoid external bridging on use on three-phase network without neutral By padlocking facility (not supplied)
Locking possible in “tripped” position Release with fixed sensitivity for all ratings
Indifferent position of installation.
DB123314
440 V 3 1 500 A mm in 4P 2P
72 2.83 36 1.42
6 0.24
81 3.19
60 2.36 44 1.73
9 0.35
45 1.77
31
Page 32
Residual Current Devices www.schneider-electric.com
IEC/EN
RCCB ID - IEC/EN 61008-1 – Residual Current Circuit Breakers – AC, A-SI types bb RCCB-ID residual current circuit breakers offer the following functions: vv protection of persons against electric shock by direct contact (30 mA), vv protection of persons against electric shock by indirect contact (300 mA), vv protection of installations against fire risks (300 mA).
A-SI type
PB111762-40
PB111761-40
IEC
The A-SI type offers enhanced immunity to electrical disturbances.
Catalogue numbers
RCCB-ID residual current circuit breakers Type
AC
Auxiliaries
See page 43 Sensitivity
30 mA
300 mA
30 mA
300 mA s
Rating
25 A 40 A
M9R11225 M9R11240
M9R14240
M9R31240
M9R35240
Sensitivity
30 mA
300 mA
30 mA
300 mA s
Rating
40 A
M9R11440
M9R14440
M9R31440
M9R35440
63 A
M9R11463
M9R14463
M9R31463
M9R35463
2P 4P
Operating frequency
230 - 240 V 400 - 415 V 50 Hz
Accessories
See page 48
DB122476
2P
Width in 9-mm modules
A-SI
DB122477
4P
Voltage rating (Ue)
4
8
Connection 5.5 mm
25 to 63 A PZ2
32
Copper cables Rigid
Flexible or with ferrule
DB122945
15 mm
Tightening torque
3.5 N.m (31 lb.in)
DB122946
DB123947
Rating
1 to 35 mm2
AWG #18 to #2
1 to 25 mm2
AWG #18 to #4
Page 33
Residual Current Devices www.schneider-electric.com
IEC/EN
RCCB ID - IEC/EN 61008-1 – Residual Current Circuit Breakers – AC, A-SI types (cont.) Window bb Tripping upon fault is indicated by a red mechanical status indicator on the front panel bb Test button bb Clip-on terminal markers bb Clip allowing dismounting with comb busbar in place
Positive contact indication bb Suitability for isolation in industrial sector bb The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.
DB123310
Technical data Main characteristics Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) According to IEC/EN 61008-1 Making and breaking capacity (Im/IDm) Impulse current AC type withstand (8/20 μs) A-SI type without tripping Rated conditional With fuse short-circuit current (Inc/IDc) Behaviour in case of voltage drop
DB123312
Clips on to 35 mm DIN rail.
440 V 3 6 kV 10 In 250  3 k 10,000 A Residual current protection down to 0 V according to IEC/EN 61008-1 § 3.3.4
Additional characteristics Degree of protection Device only (IEC 60529) Device in modular enclosure
Any installation position.
DB123314
IP20
IP40
Endurance (O-C)
Electrical
IP20 IP40 Insulation class II 2000 cycles
Operating temperature
Mechanical AC type A-SI type
20,000 cycles -5°C to +40°C / 23°F to 104°F -25°C to +40°C / -13°F to 104°F
Storage temperature Tropicalization (IEC 60068-1)
-40°C to +60°C / -40°F to 140°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68
Dissipated power
Dimensions (mm / inches)
Residual current circuit breakers mm in
Type
ID
2P 4P
230 g / 8.11 oz 450 g / 15.87 oz
DB406069
Weight (g / oz)
4P 2P
36 1.42
72 2.83
5.5 0.22
81 3.19
73 2.87 60 2.36 44 1.73
45 1.77 7.5 0.29
33
2
Page 34
Residual Current Devices www.schneider-electric.com
IEC/EN
RCCB ID - IEC/EN 61008-1 – Residual Current Circuit Breakers – B types IEC/EN 61008-1 VDE 0664 bb The RCCB-ID 125 A residual current circuit breakers provide: vv protection of persons against electric shock by direct contact (30 mA), vv protection of persons against electric shock by indirect contact (u 300 mA), vv protection of installations against the risk of fire (300 mA or 500 mA).
PB107510-33
PB111261-35
IEC
16766
B type The RCCB-ID B type residual current circuit breakers provide: bb protection in the event of a continuous fault current on three-phase networks generated by: vv controllers and variable speed drives, vv battery chargers and inverters, vv backed-up power supplies. bb They include and also guarantee protection against fault currents: vv sinusoidal AC residual currents (AC type), vv pulsed DC residual currents (A type).
PB100572-18
16940
They can be adapted to all the application cases defined in standards IEC 60364 and EN 50178. bb Schneider Electric guarantees that the type B RCCB-ID works correctly in combination with the variable speed drives manufactured by Schneider Electric.
16939
OFsp auxiliary bb Electrical indication: by OFsp auxiliary mounted to the left. It has a double changeover switch indicating the "open" or "closed" position of the RCCB-ID B type.
Accessories bb 4P sealable screw shield.
Catalogue numbers RCCB-ID B type residual current circuit breakers Type
Width in 9 mm module
B
4P DB123726
Rating
Sensitivity 30 mA
300 mA
300 mA s 500 mA
16750 16752 16756 16760 16763
16751 16753 16757 16761 16764
16754 16758 16762 16765
25 A 40 A 63 A 80 A 125 A
Voltage rating (Ue) Operating frequency
16755 16759 16766
8
230/400 V 50 Hz
Auxiliary
E91415
Type
Width in 9 mm module
Contact OFsp
Contact
Voltage
22
1A
110 V DC
6A
230 V AC (AC15)
12
21
14
16940
11
Accessory Type
Number of pole
Screw shield (set of 10) for upstream or downstream
4P
34
16939
1
Page 35
Residual Current Devices www.schneider-electric.com
IEC/EN
RCCB ID - IEC/EN 61008-1 – Residual Current Circuit Breakers – B types (cont.) Connection 6.5 mm
Copper cables Rigid
Flexible or with ferrule
RCCB-ID B type 3 N.m (27 lb.in) OFsp
PZ2
0.8 N.m (7 lb.in)
DB122946
11 mm
Tightening torque DB122945
DB123736
Type
1 x 1.5 to 50 mm2 2 x 1.5 to 16 mm2 1 to 1.5 mm2
1 x AWG #16 to #1 2 x AWG #16 to #6 AWG #18 to #16
1 x 1.5 to 35 mm2 2 x 1.5 to 16 mm2 1 to 1.5 mm2
1 x AWG #16 to #2 2 x AWG #16 to #6 AWG #18 to #16
Technical data Electrical characteristics
OFsp contact status, depending on the position of the residual current circuit breaker
Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp)
Type RCCB-ID B type
Contact OFsp
Closed bb
-
-
Open
- bb
-
Tripped on fault 22/21 12/11 14/11
-
- bb
Open
Closed
Closed
Closed
Open
Open
2
440 V 3 4 kV
According to IEC/EN 61008-1 Making and breaking capacity (Im/IDm)
25/40 A 63 A 80 A 125 A Surge current withstand No selective s (8/20 μs) without tripping Selective s Conditional rated short 25/40 A with FU 80 A gG fuse circuit current (Inc/IDc) 63 A with FU 100 A gG fuse 80/125 A with FU 125 A gG fuse
500 A 630 A 800 A 1250 A 3 k 5 k 10,000 A 10,000 A 10,000 A
DB122842
Additional characteristics Degree of protection (IEC 60529)
Device only
IP20
Device in modular enclosure
Endurance (O-C)
Electrical Mechanical 30 mA 300, 500 mA
IP40 Insulation class II > 2 000 cycles > 5 000 cycles 250...400 V AC 185...400 V AC -25°C to +40°C / -13°F to 104°F -40°C to +85°C / -40°F to 185°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68
Range of test button operating voltage
Operating temperature Storage temperature Tropicalization (IEC 60068-1)
Indication of the status of the RCCB-ID B type via the 3-position toggle and front panel indicator
Dissipated power
Dielectric test
DB109414
E63606 bb Closed (red indicator) bb Tripped on fault (green indicator) bb Open (green indicator)
Weight (g / oz) Residual current circuit breakers and auxiliary Type
RCCB-ID B type OFsp
4P
450 g / 15.87 oz
40 g / 1.41 oz mm in 72 2.83
6 0.24
86 3.39
RCCB-ID B type disconnect terminals 3, 5, 7 and 4, 6, 8.
76 2.99 60.5 2.38
DB124102
DB122838
Dimensions (mm / inches)
d To perform the dielectric test,
44 1.73 mm in 9 0.35
45 86 1.77 3.39
6 0.24
76 2.99 60.5 2.38
44 1.73
45 86 1.77 3.46
Contact OFsp
35
Page 36
Residual Current Devices www.schneider-electric.com
IEC/EN
Vigi C60 - IEC/EN 61009-1 – Residual current devices – Add-on for C60 IEC/EN 61009-1
IEC bb Combined with C60 circuit breaker, the Vigi C60 provide: vv protection of persons against electric shock by direct contact (30 mA), vv protection of persons against electric shock by indirect contact (300 mA), vv protection of installations against the risk of fire (300 mA).
DB406511-40
DB406510-40
DB406509-40 bb The A-SI type provides increased immunity from electrical interference and polluted or corrosive environments.
Catalogue numbers Vigi C60 add-on residual current devices Type
A-SI
AC
2P
Sensitivity 30 mA M9V11263
DB406518
Rating 63 A
3P
Sensitivity 30 mA M9V11363
DB406519
Rating 63 A
Sensitivity 30 mA
DB406520
4P
Voltage rating (Ue)
Rating 63 A
M9V11463
2P 3P-4P
230 - 240 V 400 - 415 V 50 Hz
Operating frequency
300 mA
30 mA
M9V14263
M9V31263
300 mA
30 mA
M9V14363
M9V31363
300 mA
30 mA
M9V14463
M9V31463
Width in 9-mm modules
4
7
7
Connection DB406159
Tightening torque
Copper cables Rigid
Flexible or with ferrule DB122946
DB122945
5.5 mm
14 mm PZ2
36
3.5 N.m (31 lb.in)
1 to 35 mm2
AWG #18 to #2
1 to 25 mm2
AWG #18 to #4
Page 37
Residual Current Devices www.schneider-electric.com
IEC/EN
Vigi C60 - IEC/EN 61009-1 – Residual current devices – Add-on for C60 (cont.) DB406909-55 bb Reinforced cable pull-out strength: serrated terminals bb Automatic cable guiding in the correct position: terminals with guard bb Every circuit breaker combined with a Vigi module remains compatible with the indication and tripping auxiliaries bb Test button
2
DB123310
Technical data Main characteristics According to IEC/EN 61009-1 Insulation voltage (Ui) Pollution degree
Phase-to-phase
Rated impulse withstand voltage (Uimp) Impulse current AC types withstand (8/20 μs) A-SI types without tripping Behaviour in case of voltage drop
DB123312
Clip on DIN rail 35 mm.
500 V AC 3 4 kV 250  3 k Residual current protection down to 0 V according to IEC/EN 61009-1 § 3.3.8
Additional characteristics Degree of protection (IEC 60529) Operating temperature
Indifferent position of installation.
DB123314
IP20
IP40
Device only Device in modular enclosure A-SI types
AC type Storage temperature Tropicalization (IEC 60068-1)
IP20 IP40 Insulation class II -25°C to +60°C / -13°F to 140°F -5°C to +60°C / 23°F to 140°F -40°C to +60°C / -40°F to 140°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68
Dissipated power
Weight (g / oz) Vigi modules Type 2P 3P 4P
DB 428265
Dimensions (mm / inches) mm in
36 1.42
72 2.83
54 2.13
36 1.42
2P
117 4.60
150 g / 4.29 oz 210 g / 7.40 oz 210 g / 7.40 oz
135 5.31
63 2.48
72 2.83
74 2.91 44 1.73
16 0.63
4P
3P
87 3.43
5.5 0.22
63 2.48
87 3.43
87 3.43
92 3.62
45 1.77
37
Page 38
Residual Current Devices www.schneider-electric.com
IEC/EN
Vigi N40 - IEC/EN 61009-1 – Residual current devices – Add-on for N40 IEC/EN 61009-1
IEC
PB111760-40
Earth leakage protection devices can ensure: b protection of electrical installations against insulation faults b protection for people against direct and indirect contact b protection of the installations against fire risks.
The Vigi N40N modules, to be combined with a circuit breaker, incorporate in a single enclosure the residual current relay and the toroid. bb The residual current tripping device is electromechanical and operates without an auxiliary source. bb A homogeneous unit in compliance with the EN 61009-1 and EN 61009-2-1 standards, a residual current device retains all the characteristics of the circuit breaker alone; in particular, the thermal tripping threshold of the circuit breaker is retained in the presence of the earth leakage module.
Operation bb When an earth fault occurs, the Vigi module causes automatic opening of the circuit breaker with which it is combined. Fault indication is performed by a red strip on the operating handle for Vigi module resetting. bb Resetting of the earth leakage module is performed, at the user's choice: vv either by the reset handle of the circuit breaker (in one operation), vv or independently of the circuit breaker (in 2 operations).
A-SI type
The A-SI type offers enhanced immunity to electrical disturbances.
Catalogue numbers Vigi N40 add-on residual current devices Type
DB123671
3P+N
Sensitivity 30 mA
N
Rating 40 A
N
Width in 9-mm modules
A-SI
AC
M9Y11740
300 mA
30 mA
300 mA
M9Y14740
M9Y31740
M9Y34740
4
T
N
N
Voltage rating (Ue)
400 - 415 V
Operating frequency
50 Hz
Connection DB406159
Tightening torque Copper cables Rigid
Flexible or with ferrule DB122946
DB122945
5.5 mm
13 mm PZ2 2 N.m (18 lb.in)
0.75 to 16 mm2
AWG #18 to #2
0.33 to 10 mm2
AWG #18 to #4 bb Where there is a comb busbar tooth, the connection of cables of cross section 16 mm2 remains possible. bb Connection: vv upstream: direct by comb busbar, vv downstream: by cables.
38
Page 39
Residual Current Devices www.schneider-electric.com
IEC/EN
Vigi N40 - IEC/EN 61009-1 – Residual current devices – Add-on for N40 (cont.) bb Test button PB111760-45 bb Reinforced cable pull-out strength: serrated terminals bb Automatic cable guiding in the correct position: terminals with guard bb Every circuit breaker combined with a Vigi module remains compatible with the indication and tripping auxiliaries
2
DB123310
Technical data Main characteristics According to IEC/EN 61009-1 Insulation voltage (Ui) Phase-to-phase 440 V AC Pollution degree 3 Rated impulse withstand voltage (Uimp) 4 kV Behaviour in the event of a phase-to-earth fault Residual breaking and making capacity (IΔm) in TN-S earthing system identical to the rated breaking capacity (Icn) Residual current protection down to 0 V Behaviour in case of voltage drop according to IEC/EN 61009-1 § 3.3.8
Clip on DIN rail 35 mm.
DB123312
Additional characteristics Degree of protection (IEC 60529) Operating temperature
Storage temperature Tropicalization (IEC 60068-1)
IP40
IP20 IP40 Insulation class II -5°C to +60°C / 23°F to 140°F -25°C to +60°C / -13°F to 140°F -40°C to +60°C / -40°F to 140°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68
Dissipated power
Weight (g / oz) Vigi modules Type 3P+N
210 g / 7.40 oz
Dimensions (mm / inches) DB406072
DB123314
Indifferent position of installation.
IP20
Device only Device in modular enclosure AC type A-SI types mm in
54 2.13
36 1.42
5 0.2
91 3.58
5.5 0.22
69 2.71 44 1.73
16 0.63
45 81 1.77 3.19
39
Page 40
Residual Current Devices www.schneider-electric.com
IEC/EN
N40 Vigi - IEC/EN 61009-1 – Residual current circuit breakers with overcurrent protection IEC/EN 61009-1
IEC PB111759-40 bb The N40 Vigi residual current device provides complete protection for final circuits (against overcurrents and insulation faults): vv protection for people against electric shocks by direct contacts (30 mA), vv protection for people against electric shocks by indirect contacts (300 mA), vv protection of installations against risk of fire (300 mA).
Catalogue numbers N40 Vigi 6 kA Type
AC
Auxiliaries
See page 43
1P+N
C curve
Sensitivity 30 mA Rating (In)
DB123871
Width in 9-mm modules 300 mA
6A
M9D11606
-
10 A
M9D11610
M9D14610
16 A
M9D11616
M9D14616
20 A
M9D11620
M9D14620
25 A
M9D11625
M9D14625
40 A
M9D11640
M9D14640
Voltage rating (Ue) Operating frequency
240 V AC 50 Hz
Accessories
See page 48
4 bb Test button
Positive contact indication bb A green strip on the toggle guarantees opening of all the poles in safety conditions (padlocking possible) for work to be carried out on live parts bb Fast closing bb Display of earth fault on the front panel by position of toggle
40