Page 41
Residual Current Devices www.schneider-electric.com
IEC/EN
N40 Vigi - IEC/EN 61009-1 – Residual current circuit breakers with overcurrent protection (cont.) Connection Rigid 5.5 mm
Flexible or with ferrule
2 N.m (18 lb.in)
PZ2
DB122946
13 mm
DB122945
DB406159
Tightening torque Copper cables
0.75 to 16 mm2
AWG #18 to #2
0.33 to 10 mm2
AWG #18 to #4
DB123310
Technical data
2
Main characteristics Insulation voltage (Ui) Pollution degree Rated impulse withstand voltage (Uimp) Setting temperature for ratings Earth leakage protection with instantaneous tripping Magnetic tripping C curve 8/20 µs impulse withstand current
Clip on DIN rail 35 mm.
400 V AC 3 4 kV 50°C / 122°F 30, 300 mA 8.5 In (± 20 %) 250 Â
According to IEC/EN 61009-1
DB123312
Limitation class Rated breaking capacity (Icn) Rated residual breaking and making capacity (IΔm) Behaviour in case of voltage drop
3 6000 A 6000 A Residual current protection down to 0 V according to IEC/EN 61009-1 § 3.3.8
According to IEC/EN 60947-2 6 kA 75 % Icu
Breaking capacity (Icu) Service breaking capacity (Ics)
Additional characteristics Degree of protection (IEC 60529)
Device only Device in modular enclosure Endurance (O-C) Electrical N40 Vigi ≤ 20A N40 Vigi ≥ 25A Mechanical Overvoltage category (IEC 60364) Operating temperature Storage temperature Tropicalization (IEC 60068-1)
Indifferent position of installation.
DB123314
IP20
IP40
Dissipated power
Dimensions (mm / inches)
Residual current device Type
N40 Vigi
1P+N
125 g / 4.41 oz
DB122729
Weight (g / oz)
IP20 IP40 Insulation class II 20,000 cycles 10,000 cycles 20,000 cycles IV -5°C to +60°C / 23°F to 140°F -30°C to +70°C / -22°F to 158°F Treatment 2 (relative humidity 95 % at 55°C / 131°F) See page 68 mm in
36 1.42
5.5 0.22
44 1.73
16 0.63
4.5 0.18 81 3.19
45 1.77 3.5 0.14 70 2.76
41
Page 42
www.schneider-electric.com
42
Page 43
Auxiliaries and accessories www.schneider-electric.com
IEC bb For UL 489 Branch circuit protection File #E215117. bb For CSA C22.2 No. 5 Branch circuit protection File #179014. bb For UL 1077 Supplementary Protection File #E90509. bb For CSA C22.2 No. 235 Supplementary Protection File #179014. bb For IEC 60947-1 and IEC 60947-5-1 circuit-breakers. bb CE Marked.
Combination table Indication auxiliaries
Tripping auxiliaries
+
+
1 SD+OF maxi
1 SD+OF maxi
1 maxi
1 OF maxi
1 (SD+OF or SD or OF) maxi
2 maxi
None 1 OF maxi
1 (SD+OF or OF) maxi 1 OF maxi
2 maxi 1 maxi
None
1 OFsp
None
Devices PB116665-18 b The electrical auxiliaries provide the remote tripping or position (open/closed/tripped) indication functions of these devices in the event of a fault. b They clip on (no tool required) to the lefthand side of the associated device. b The SD+OF auxiliary is a two-in-one product: a mechanical selector switch is used to select one of two contacts: SD or OF.
Tripping
DB405975
Indication
+
3
PB111749-19, PB111759-19
DB105729
DB105728
DB105730
Compliance with electrical auxiliaries standards
DB405227_1
DB105727
Common electrical auxiliaries
P100628_SE-18
PB111761
C60, N40N, N40 Vigi
+
RCCB-ID PB111261-18
PB107510-18
OF.S
RCCB-ID B type d
Tripping devices must be installed first. If two tripping devices are used: the MN undervoltage release must be installed first Indication auxiliaries: install the SD auxiliary first
43
Page 44
Auxiliaries and accessories www.schneider-electric.com
Common electrical auxiliaries (cont.)
Tripping
Auxiliaries
MN
Type
MNs
Undervoltage release Delayed
PB100202_SE-30
PB100203_SE-30
Instantaneous
Function bb Causes the device with which it is associated to trip when its input voltage decreases (between 70 % and 35 % of Un). Prevents the device from closing until its input voltage has been restored bb No tripping in the event of transient voltage dips (up to 0.2 s)
DB118804
Wiring diagrams
Utilization
Catalogue numbers Technical specifications Rated voltage (Ue) V AC V DC Operating Hz frequency Pollution degree Mechanical state indicator light, red Test function Width in 9 mm modules Operating current bb Emergency stop via a normally-closed pushbutton bb Ensures the safety of the power supply circuits of several machines by preventing accidental startups
M9A27108
M9A27107
M9A26960
M9A26961
M9A26959
M9A26963
24 24 50/60
120
220…240
48 48
115
220…240 – 50/60
400
3 On front face
3 On front face
– 2 –
– 2 –
Number of contacts
–
–
Operating temperature Storage temperature Standards
-25…+50°C / -13...122°F -40…+85°C / -40...185°F
-25…+50°C / -13...122°F -40…+85°C / -40...185°F
IEC/EN 60947-1 IEC/EN 60947-5-1 EN 60947-2 EN 62019-2 bb – bb – bb bb – bb – bb bb bb bb bb
–
– bb bb
44
Page 45
Auxiliaries and accessories www.schneider-electric.com
Common electrical auxiliaries (cont.)
MNx
MX
MX+OF
Shunt release bb Tripping of the associated device by opening of the control circuit (e.g. push-button, dry contact)
PB100198_SE-30
With open/closed auxiliary contact PB100199_SE-30
PB100205_SE-30
Independent of the supply voltage bb Trips the associated device when it is powered on
U<
E1
E2
N/ L1 bb Includes an open/closed contact (OF contact) to indicate the "open" or "closed" position of the associated device
DB123012
DB406947 bb A drop in the supply voltage does not trip the associated device bb A locking push-button control allows the circuit protected (e.g. machine control) to be placed in safety configuration
U>
L/ L2 bb Fail-safe emergency stop bb Emergency stop via a normally-open bb Insensitive to the variation in the control circuit voltage to pushbutton. improve continuity of service Important: Before any servicing operation switch off the mains power supply (voltage presence at terminals E1/E2) M9A26969 M9A26971 M9A26476 M9A26477 M9A26478 bb Emergency stop via a normally-open pushbutton bb Remote indication of the position of the associated device M9A26946
M9A26947
M9A26948
230 – 50/60
100…415 110…130 50/60
48 48
12…24 12…24
400
100…415 110…130 50/60
48 48
12…24 12…24
3 On front face
3 On front face
3 On front face
– 2 –
– 2 –
–
–
– 2 3 A / 415 V AC 6 A / y 240 V AC 1 NO/NC
-25…+50°C / -13...122°F -40…+85°C / -40...185°F
-25…+50°C / -13...122°F -40…+85°C / -40...185°F
-25…+50°C / -13°F...122°F -40…+85°C / -40°F...185°F bb – – – – bb – – – bb bb – – – bb
– bb bb
– bb bb
–
– bb bb bb bb
3
45
Page 46
Auxiliaries and accessories www.schneider-electric.com
Common electrical auxiliaries (cont.)
Signalisation
Auxiliaries
OF.S
OFsp
OF
SD
SD+OF
PB100625_SE-30
PB100626_SE-30
PB107510-30
PB100627_SE-30
Open/closed auxiliary contact Open/closed auxiliary Fault indicating contact Double open/closed or contact fault indicating contact PB100628_SE-30
Type
Function bb Changeover contact indicating bb Changeover contact the "open" or "closed" position of the indicating the "open" or associated device "closed" position of the associated device bb Changeover contact indicating the position of the associated device in the event of: vv electrical fault vv action on the tripping auxiliary d
Compulsory for the addition of tripping or indication auxiliaries on an ID RCCB bb The SD+OF auxiliary is a two-in-one product: choice of OF or SD contact via the selector switch d
Not compatible compatible with a RCCB-ID residual current circuit breaker, use a SD+OF in the SD position
21
14
12
DB118813
14
DB118812
12
DB118811
22
DB118810
DB118809
DB409611
Wiring diagrams
11
11
OF position Utilization
Catalogue numbers Technical specifications Rated voltage (Ue) V AC V DC Operating Hz frequency Pollution degree Mechanical state indicator light, red Test function Width in 9 mm modules Operating current bb Remote indication of the position of the associated device 26923
16940 bb Remote indication of the bb Remote fault tripping position of the associated indication of the associated device device M9A26924 M9A26927
24…415 24…130
230 110
240…415 24…130
240…415 24…130
240…415 24…130
50/60
50
50/60
50/60
50/60
3 _
3 _
3 _
3 On front face
3 On front face
– 1 3 A /415 V AC 6 A / y 240 V AC
On front face 1
On front face 1
SD position bb Remote position and/or fault tripping indication of the associated device M9A26929
Number of contacts
1 NO/NC
_ On front face 1 1 1 A /110 V DC 3 A /415 V AC 6 A / y 230 V 6 A / y 240 V AC AC 1 NC + NC/NO 1 NO/NC
1 NO/NC
1 NO/NC + 1 NO/NC
Operating temperature
-25…+50°C / -13°F...122°F -40…+85°C / -40°F...185°F
-25…+50°C / -25…+50°C / -13°F...122°F -13°F...122°F -40…+85°C / -40…+85°C / -40°F...185°F -40°F...185°F
-25…+50°C / -13°F...122°F -40…+85°C / -40°F...185°F
-25…+50°C / -13°F...122°F -40…+85°C / -40°F...185°F
– bb – bb –
– – – – –
– bb – bb bb
– bb – bb bb
– bb – bb bb
–
– bb bb bb
–
– bb bb bb
–
– bb bb bb
–
– bb bb bb
Storage temperature Standards IEC/EN 60947-1 IEC/EN 60947-5-1 EN 60947-2 EN 62019-2
46
Page 47
Auxiliaries and accessories www.schneider-electric.com
Common electrical auxiliaries (cont.)
Connection DB1261475
Type
Tightening torque
Copper cables Rigid DB122946
4 mm (0.16 inch)
Indication and tripping auxiliaries
1 N.m (9 lb.in)
DB405990
PZ1
9 mm (0.35 inch)
2 cables, 1.5 mm2 / #16 AWG or 1 cable, 2.5 mm2 / #14 AWG
OFsp
0.8 N.m (7 lb.in)
1 cable, 1.5 mm2 / #16 AWG
Dimensions (mm / inches) 9 0.35
85 3.35
5.5 0.22
68 60 2.68 44 2.36 1.73
81 3.19
9 0.35
45 1.77
OF.S, OF, SD DB124102
90 3.54
81 3.19
6 0.24
5.5 0.22
18 0.71
82.5 3.25
45 1.77
SD+OF mm in 9 0.35
68 60 2.68 44 2.36 1.73
5.5 0.22
DB428331
DB407309 mm in
68 60 2.68 44 2.36 1.73
81 3.19
45 1.77
MX, MN, MN S , MX+OF, MNx
76 3.00 61 2.40
Weight (g / oz)
44 1.73
3
Electrical auxiliaries Type MN MNs MNx MX MX+OF OF.S OF OFsp SD SD+OF
45 88 1.77 3.46
OFsp
DB123313
IP20
IP40
66 g / 2.32 oz 66 g / 2.32 oz 73 g / 2.57 oz 60 g / 2.32 oz 65 g / 2.12 oz 33 g / 1.16 oz 30 g / 1.06 oz 40 g / 1.41 oz 30 g / 1.06 oz 38 g / 1.34 oz
DB428329
2 DB428326
DB123309
DB428330
DB428327
C60BP or C60BPR association
1
DB123311
DB428328
Clip on DIN rail 35 mm.
3 2
Indifferent position of installation.
47
Page 48
Auxiliaries and accessories www.schneider-electric.com
Common accessories
Installation
Plug-in base
PB100137_SE-24
PB100138_SE-24
PB111764-40
Accessories Rotary handle
Function
Cat. numbers
Set of
Front or side control of 2, 3 and 4-pole circuit breakers bb Degree of protection: IP40 bb A complete rotary handle consists of: vv a circuit-breaker operating sub-assembly, cat. no. 27046, vv a handle cat. no. 27047 or a handle cat. no. 27048 bb Installation: vv the circuit-breaker operating sub-assembly cat. no. 27046 is fixed to the circuit breaker vv the removable handle cat. no. 27047 is mounted on the removable front panel or on the enclosure door vv the fixed handle cat. no. 27048 is fixed to the front or side panel of the enclosure
Allows a circuit breaker to be quickly removed or replaced, without touching the connections bb Degree of protection: IP20 bb It consists of: vv a base to be fixed to a rail (or panel) vv 2 “blades” to be fixed in the device terminals bb Connection: tunnel terminals for cables up to 50 mm² (rigid) or 35 mm² (flexible) bb Installation: vv on backplate vv on a horizontal rail bb Centreline between two rows: 200 mm bb Only on the circuit breaker, without a Vigi device or auxiliary bb Padlocking option (8 mm dia. padlock not supplied)
27047
27048
27046
26996
Removable extended handle
Fixed handle
Operating sub-assembly
(1 per pole)
1
1
1
1
Suitable for the following devices: bb 2P, 3P C60BP UL489, C60BPR UL489 C60SP UL1077 bb 2P, 3P, 4P C60H-DC bb 2P GFP UL1053 – C60N, H, L, bb 2P, 3P, 4P C60CTRL N40N bb 3P+N RCCB-ID – (AC, A-SI types) RCCB-ID B type – N40 Vigi – Operating -35°C to +70°C / température -31°F to 158°F
48
– bb bb bb bb – – – – -35°C to +70°C / -31°F to 158°F
Page 49
Auxiliaries and accessories www.schneider-electric.com
Common accessories (cont.)
Padlocking device 057209J_SE-20
A9A26380-40
Side DB409566-25
Front
A9A26381-40
Accessories
Function
Cat. numbers
Set of
Used to padlock a circuit breaker in the "open" or "closed" position bb Locking in the ON position does not prevent the circuit breaker from tripping in the event of a fault bb Isolation: in conformity with IEC/EN 60947-2. bb Diameter of the padlock: 8 mm max.
Used to padlock a circuit breaker in the "open" position bb Isolation: in conformity with UL 489/CSA C22.2 No 5 Listed and UL 1077 Reconized. bb Diameter of the padlock: 8 mm max.
Can be used to padlock a circuit breaker in open position bb Attached directly to the circuit breaker, it cannot be lost bb Padlock diameter: 6 mm
26970
M9PAF
MGN26380
MGN26381
Left-hand mounting
Right-hand mounting
1
1
1 bb bb bb bb bb – bb bb bb – bb bb bb – bb bb – bb – bb –
– – -35°C to +70°C / -31°F to 158°F
– – -35°C to +70°C / -31°F to 158°F
– – -35°C to +70°C / -31°F to 158°F
2
Suitable for the following devices: bb C60BP UL489, C60BPR UL489 C60SP UL1077 bb C60H-DC bb GFP UL1053 bb C60N, H, L, bb C60CTRL N40N bb RCCB-ID bb (AC, A-SI types) RCCB-ID B type – N40 Vigi bb Operating -35°C to +70°C / température -31°F to 158°F
3
49
Page 50
Auxiliaries and accessories www.schneider-electric.com
Common accessories (cont.)
Installation (continued)
Accessories Front mounting kit
Pole filler
Front mounting bracket DB409570
DB409567
DIN rail support DB409569
DB409568
Front mounting kit
Function
Cat. numbers bb Consists of a transparent, hinged, weatherproof cover bb Allows installation of up to twenty modules (10 poles of C60) of circuit breakers or supplementary protectors and accessories bb A DIN rail with support is also available bb Degree of protection a s per IEC 529: IP55 bb Includes a 10-Module divisible blanking plate and mounting template bb DIN rail with support for bb Used to fill empty panels spaces bb Provides a convenient way to mount front mounting kit cat. no. bb They clip into space circuit breakers, supplementary protectors 14210 bb They may be snapped apart in or accessories bb Allows installation of up to 9 mm increments bb Allows the C60 devices to be clipped twenty modules (10 poles of onto it in a standard manner C60) of circuit breakers or bb In 480 V AC UL 1077 applications, cat. supplementary protectors no. 26981 terminal screw shield should be and accessories used for increased isolation between the terminal screws of the device and the mounting bracket. These shields are included with the mounting bracket kits
14210
14211 bb 1P M9PF4
M9PF5 bb 2P
Set of
1
50
1
4
4
For multi-pole mounting kit cat. no.14210
For multi-pole mounting kit cat. no.14210 bb 4P
MG26983 MG26984 MG26985 MG26989
4 strips of 4 by 4 strips of 5 by 18 mm pole filler 18 mm pole filler Suitable for the following devices: bb C60BP UL489, C60BPR UL489 bb C60SP UL1077 C60H-DC bb GFP UL1053 bb C60N, H, L, bb C60CTRL N40N bb RCCB-ID bb (AC, A-SI types) RCCB-ID B type – N40 Vigi bb Operating -35°C to +70°C / température -31°F to 158°F bb 3P
1 bb bb bb bb bb bb bb – bb -35°C to +70°C / -31°F to 158°F