Page 51
Auxiliaries and accessories www.schneider-electric.com
Common accessories (cont.)
Terminal shield
Interpole barrier Spacer DB123898
DB122950
PB124114
PB100572-07
Screw shield
PB104483-35
Safety
Accessories
Function Prevents all contact with the fixing screws bb The degree of protection becomes IP40 bb Sealable, max. diameter 1.2 mm bb Dividable
Prevents all contact with the terminals bb Degree of protection becomes IP40 bb Sealable, max. diameter 1.2 mm bb 1P
Improves the insulation between the connections: cables, terminals, lugs, etc.
bb 2P bb 3P: 1 x 26975 + 1 x 26976 bb 4P: 2 x 26976 Cat. numbers
26981
16939
26975
Set of
2 (4P dividable)
10
2 (for upstream/downstream 10 terminal)
1
–
–
–
– bb
– – – – bb bb – bb bb bb – bb bb bb bb bb bb bb bb bb
– –
– bb
– bb
– bb bb bb bb – -35°C to +70°C / -31°F to 158°F
– – – – -35°C to +70°C / -31°F to 158°F
– – -35°C to +70°C / -31°F to 158°F bb bb -35°C to +70°C / -31°F to 158°F
Suitable for the following devices: – C60BP UL489, C60BPR UL489 bb C60SP UL1077 C60H-DC bb GFP UL1053 bb C60N, H, L, bb C60CTRL N40N – RCCB-ID bb (AC, A-SI types) RCCB-ID B type – N40 Vigi – Operating -35°C to +70°C / température -31°F to 158°F
26976
27001 bb Used to: vv complete the rows vv separate the devices bb Width: 1 x 9 mm module bb Allows that 2 cables are routed from one row to another (above and below), up to 6 mm² 27062
3
51
Page 52
Auxiliaries and accessories www.schneider-electric.com
Common accessories
Connection
Function
50 mm² / #1 AWG Al terminal Connection kit for ring terminals DB122951
DB409586
Multi-cable terminal DB103334_SE-19
Accessories
Cat. numbers 19091 Set of 4 Suitable for the following devices:
For 16 to 50 mm² aluminium cables
For terminal up to 63 A, front or rear access (screw Ø 5 mm) b It incorporates a "conductive" part and an "insulating" part which ensures the phase-tophase clearance
27060 1
M9A17400 24
–
–
– – – – bb bb – bb bb bb
– bb – bb bb bb – –
– – 10 N.m (89 lb.in) 13 mm (0.51 in) Hc 1/5" or 5 mm (0.2 in) -35°C to +70°C / -31°F to 158°F
– – 2 N.m (18 lb.in) – Diameter 5 mm (0.2 in) or PZ2 -35°C to +70°C / -31°F to 158°F
DB122935
DB118787
For 3 copper cables: bb Rigid up to 16 mm² bb Flexible up to 10 mm²
19096 3
– – C60BP UL489, C60BPR UL489 – C60SP UL1077 y 25 A – C60SP UL1077 > 25 A bb bb GFP UL1053 bb bb C60N, H, L, y 25 A – – C60CTRL C60N, H, L, > 25 A bb bb C60CTRL C60H-DC y 25 A – – C60H-DC > 25 A bb bb N40N – – bb bb RCCB-ID (AC, A-SI types) RCCB-ID B type – – N40 Vigi – – Tightening torque 2 N.m (18 lb.in) Stripping length 11 mm (0.43 in) Tools to be used Diameter 5 mm (0.2 in) or PZ2 Operating -35°C to +70°C / -31°F to 158°F température
Identification
Clip-on terminal marker strip
031204D_SE-23
Accessories
Function
Cat. numbers
52
For connection identification
0: AB1-R0 A: AB1-GA 1: AB1-R1 B: AB1-GB 2: AB1-R2 C: AB1-GC 3: AB1-R3 D: AB1-GD 4: AB1-R4 E: AB1-GE 5: AB1-R5 F: AB1-GF 6: AB1-R6 G: AB1-GG 7: AB1-R7 H: AB1-GH 8: AB1-R8 I: AB1-GI 9: AB1-R9 J: AB1-GJ Set of 250 Suitable for the following devices: – C60BP UL489 – C60BPR UL489 bb 4 repères maxi. par pôle C60SP UL1077 bb 4 repères maxi. par pôle C60H-DC GFP UL1053 bb 4 repères maxi. par pôle bb 4 repères maxi. par pôle C60H-DC C60N, H, L, bb 4 markers max. per pole C60CTRL N40N bb 4 markers max. per pole RCCB-ID (2P) bb 4 markers max. per pole (AC, A-SI types) RCCB-ID B type – N40 Vigi bb 4 markers max. per device
K: AB1-GK L: AB1-GL M: AB1-GM N: AB1-GN O: AB1-GO P: AB1-GP Q: AB1-GQ R: AB1-GR S: AB1-GS T: AB1-GT
U: AB1-GU V: AB1-GV W: AB1-GW X: AB1-GX Y: AB1-GY Z: AB1-GZ +: AB1-R12 -: AB1-R13 Blank : AB1-RV
Page 53
Auxiliaries and accessories www.schneider-electric.com
DB105730
Comb busbars for C60BP (UL489) These comb busbars are aimed to be used only with C60BP circuit-breakers.
IEC
They perform distribution and subdistribution of the electric power supply and allow rapid assembly and disassembly of equipment.
Comb busbars
Connection accessories
Comb busbars
Function bb The comb busbars make it easier to install C60BP UL 489 circuit breakers bb They must not be cut
Use bb Power supply by insulated connector PB116673-16
PB116672-14
Standard comb busbars
Number of poles
1P
Catalogue numbers
M9XUP106
M9XUP112
2P M9XUP206
M9XUP212
3P M9XUP306
M9XUP312
Number of 18 mm modules
6
12
6
12
6
12
Set of Cuttable comb busbars
1
PB116676-18
1
PB116675-18
PB116674-17
1
3 L
Aux.
L
L1 L2 L3 L1 L2 L3 Aux. Aux.
With spare spaces of 9 mm for 9 mm electrical auxiliary Number of poles
1P
2P
3P
1P+Aux
3P+Aux
Catalogue numbers
M9XCP157
M9XCP256
M9XCP357
M9XCA137
M9XCA348
Number of 18 mm modules
57
56
57
37
48
Set of
1
1
1
1
1
Technical specifications Acceptable current at 40°C (Ie) Resistance to short-circuit currents Voltage rating (Ue) Insulation voltage (Ui) Pollution degree Fire resistance Colour Standards
Standard comb busbars: 115 A Cuttable comb busbars: 80 A Compatible with the breaking capacity of Schneider Electric modular circuit breakers 480Y/277 V 1000 V AC 3 Self-extinguishability 960°C 30 secondes RAL 9001 UL489 and UL508
53
Page 54
Auxiliaries and accessories www.schneider-electric.com
DB105730
Comb busbars for C60BP (UL489) (cont.) These comb busbars are aimed to be used only with C60BP circuit-breakers.
IEC
They perform distribution and subdistribution of the electric power supply and allow rapid assembly and disassembly of equipment.
Accessories
Connection accessories
Insulated connectors
Tooth covers
End-piece bb Comb busbar power supply bb Vertical incoming feeder bb Insulation of teeth remaining free bb Essential to ensure the correctly comb busbars insulation
Function Use bb Rigid and flexible copper cable: 6 to 35 mm2 (AWG #10 to #2) bb Tightening torque: 3.5 N.m (31 Ib.in). -
PB116680-18
PB116679-28
Standard comb busbars
Number of poles
All
All
-
Catalogue numbers
M9XUPC04
M9XUTC15
-
Number of 18 mm modules
-
-
-
Set of
4
5x3
PB116677-20
PB116680-18
PB116678-27
Cuttable comb busbars
Number of poles
All
All
All
Catalogue numbers
M9XCPC04
M9XCTC15
M9XCEC10
Number of 18 mm modules
-
-
-
Set of
4
5x3
10
Compatible with the breaking capacity of Schneider Electric modular circuit breakers 480Y/277 V 1000 V AC 3 Self-extinguishability 960°C 30 secondes RAL 7035 UL486E
Compatible with the breaking capacity of Schneider Electric modular circuit breakers 480Y/277 V 1000 V AC 3 Self-extinguishability 960°C 30 secondes RAL 1021 -
Compatible with the breaking capacity of Schneider Electric modular circuit breakers 480Y/277 V 1000 V AC 3 Self-extinguishability 960°C 30 secondes RAL 7035 -
Technical specifications Acceptable current at 40°C (Ie) Resistance to short-circuit currents Voltage rating (Ue) Insulation voltage (Ui) Pollution degree Fire resistance Colour Standards
54
Page 55
Auxiliaries and accessories www.schneider-electric.com
DB105730
Comb busbars for C60SP (UL1077) The comb busbars are used only for C60SP circuit breakers UL 1077 supplementary protection in conformity with standards: UL 1077 / CSA C22.2 No. 235 / IEC 60947-2 / GB 14048-2.
IEC
They perform distribution and subdistribution of the electric power supply and allow rapid assembly and disassembly of equipment.
Comb busbars
Accessory
Comb busbar
Tooth cover end-piece 62233-10
058963N-15
Connection accessories
Function bb The comb busbars make it easier to install Schneider Electric circuit breakers bb The Tooth Caps are insulated protectors which UL 1077 supplementary protection may be slipped onto the unused teeth of the comb bb Power supply directly in the cage of the circuit-breaker busbar bb They come in strips with 1-pole spacing, but can be snapped apart to be used individually 1P 2P 3P All 480Y/277 V AC 480Y/277 V AC 480Y/277 V AC –
Number of poles Voltage rating (Ue) Catalogue numbers
10285
Number of 18 mm modules
12 (8.5 inches/216 mm) 12 (8.5 inches/216 mm)
10286
12 (8.5 inches/216 mm)
10287
–
Set of
1
1
20
1
60488
Technical specifications
100 A with 2 power supply points
3
– bb Power supply via cable directly in the cage of the device: vv cross section maxi: 3 AWG (25 mm2) vv cross section mini: 10 AWG (5.27 mm2) Compatible with the breaking capacity of C60SP Schneider Electric circuit breakers UL 1077 supplementary protection 3 Self-extinguishability 960°C 30 secondes RAL 7035 UL 1077
RAL 1021 –
Dimensions (mm / inches) DB405991
Resistance to short-circuit currents Pollution degree Fire resistance Colour Standards
– –
DB110397
DB110396
Insulation voltage (Ui) 690 V Impulse withstand voltage 12 kV under 240 V (Uimp) 5 kV under 480Y/277 V or 277 V Acceptable current at 40°C (Ie) 63 A with 1 central power supply point mm in
216 8.5
11.2 0.44 22 35 0.87 1.4
198 7.8
18 0.7
3.8 0.15
13 0.5
1.5 0.06
55
Page 56
Auxiliaries and accessories www.schneider-electric.com
Comb busbars for C60N, C60H, C60L (IEC/EN, 18 mm pitch) IEC 60947-7-1, IEC 61439-2
IEC
18 mm
C60
18 mm poles, cuttable
Number of poles
1P
2P
3P
4P
3 (N+P)
L1
L1 L2
L1 L2 L3
N L1 L2 L3
N L1 N L2 N L3
Type
L1…
L1L2…
L1L2L3...
NL1L2L3…
NL1NL2NL3…
Set of
1
1
1
1
1
A9XPH106 A9XPH112 A9XPH124 A9XPH157
A9XPH212 A9XPH224 A9XPH257
A9XPH306 A9XPH312 A9XPH324 A9XPH357
A9XPH412 A9XPH424 A9XPH457
A9XPH512 A9XPH518 A9XPH524 A9XPH557
Catalogue numbers 6 modules of 18 mm 12 modules of 18 mm 18 modules of 18 mm 24 modules of 18 mm 57 modules of 18 mm
Technical data Operating current at 40°C
(Ie)
Short circuit (Isc) current Rated insulation (Ui) voltage Operating voltage (Ue) Pollution degree Fire resistance IEC 695-2-1 Color
100 A Compatible with the breaking capacity of Schneider Electric circuit breakers 500 V AC 415 V AC 3 Self-extinguishing at 960°C 30 secondes RAL 7016 (anthracite grey)
Accessories Number of poles
Set of Catalogue numbers
56
1P
2P
3P
4P
-
-
End-pieces
Tooth covers
Lateral end-pieces providing IP20 protection
Insulate teeth that have been left free
Connectors Monoconnect Comb busbar power supply. Horizontal incomer on each side. For 35 mm2 cable. Tightening torque 4 N.m 4 A9XPCM04
10 10 10 10 20 A9XPE110 A9XPE210 A9XPE310 A9XPE410 A9XPT920
Page 57
Auxiliaries and accessories www.schneider-electric.com
Comb busbars for C60N, C60H, C60L (IEC/EN, 18 mm pitch) (cont.)
+
Cuttable comb busbars, 18 mm modules, with 9 mm auxiliary Aux+1P
Aux.
L1
Aux+2P
Aux.
Aux+3P
L1 L2
L1 L2 L3
Aux+4P
Aux.
Aux.
N L1 L2 L3
3 (Aux+1P)
3 (Aux+N+1P)
L1 L2 L3 Aux. Aux. Aux.
Aux.
N L1 N L2 N L3 Aux. Aux.
AuxL1...
AuxL1L2…
AuxL1L2L3…
AuxNL1L2L3…
AuxL1AuxL2AuxL3…
AuxL1AuxL2AuxL3…
1
1
1
1
1
1
A9XAH157
A9XAH257
A9XAH357
A9XAH457
A9XAH657
A9XAH557
3
57
Page 58
Auxiliaries and accessories www.schneider-electric.com
Comb busbars for N40N, N40 Vigi (IEC/EN, 9 mm pitch) IEC 60439-1
IEC
9 mm
9 mm poles, cuttable
N40N, N40 Vigi Number of poles
1P + N
3P + N
Number of 18 mm modules Supplied accessories Tooth covers (for 3 modules of 18 mm) End-pieces Catalogue numbers
12 1
18 1
24 2
48 -
12 1
18 1
24 2
48 -
4 21501
4 19512
4 21503
21089
4 21505
4 19516
4 21507
21093
N L
Technical data
Operating current at 40°C Short circuit current Rated insulation voltage Operating voltage Degree of protection Pollution degree Fire resistance IEC 695-2-1 Color
Accessories Number of poles
1P + N
End-pieces Set of 40 Catalogue numbers 021094
58
(Ie) (Isc) (Ui) (Ue)
N L1 N L2 N L3
80 A Compatible with the breaking capacity of Schneider Electric circuit breakers 440 V AC 230 V AC (P + N) - 400 V AC (3P + N) IP20 3 Self-extinguishing at 960°C 30 secondes RAL 7035
3P + N
021095
Tooth covers (3 x 18 mm modules) Tooth covers (1 x 18 mm module) 12 10 021096 010405
Connectors (grey) 4 021098
Page 59
Auxiliaries and accessories www.schneider-electric.com
Comb busbars for N40N, N40 Vigi (IEC/EN, 9 mm pitch) (cont.) IEC 60439-1
IEC
+
+
9 mm
Comb busbar for 1P+N circuit breaker with 9 mm auxiliary OF, SD N40N, N40 Vigi
9 mm poles, cuttable
Number of poles
Aux., N, L
Aux. NL1, Aux. NL2, Aux. NL3
Aux., N, L1
Aux. NL1, Aux. NL2, Aux. NL3
18 mm
18 mm
Aux.
N L
Aux.
N L1 N L2 N L3 Aux. Aux.
Aux.
N L
Aux.
N L
Aux.
N L1
N40N comb busbar
N40 Vigi comb busbar
Number of 18 mm modules
56
56
56
56
Catalogue numbers
A9N21035
A9N21036
A9N21037
A9N21038
Technical data
Operating current at 40°C Short circuit current Rated insulation voltage Operating voltage Degree of protection Pollution degree Fire resistance IEC 695-2-1 Color
(Ie) (Isc) (Ui) (Ue)
18 mm
Aux.
N L2
Aux.
N L3
3
63 A Compatible with the breaking capacity of Schneider Electric circuit breakers 500 V AC 230 V AC (P + N) - 400 V AC (3P + N) IP20 3 Self-extinguishing at 960°C 30 secondes RAL 7035
Accessories Number of poles
Aux., N, L
Aux. NL1, Aux. NL2, Aux. NL3
End-pieces
Connectors (grey)
Neutral connectors (bleu)
Tooth covers (1 x 18 mm module)
Set of
20
10
10
10
Catalogue numbers
A9N21039
A9N21041
A9N21042
A9N21050
A9N21040
59
Page 60
Auxiliaries and accessories www.schneider-electric.com
Linergy DS screw distribution blocks
PB111254-30_1.eps
IEC/EN 60947-7-1, IEC/EN 61439-1 & 2 Description
PB111253-30_1.eps bb Single-pole or four-pole distribution block that can be installed on a standard DIN rail or on a mounting plate. bb Compatible with Prisma G and P, Pragma, Mini Pragma and Resbo series switchboards. bb Incomers and feeders are connected to screw terminals that accept rigid or flexible cables with ferrule. bb Optional: additional neutral terminal strip for four-pole distribution block.
Advantages bb Simplified power supply for main incomers. bb Easy phase balancing. bb Easy, effortless cabling due to excellent accessibility. bb Visible cabling. bb Insulation between phases. bb The single-pole distribution blocks are adjacent and bridgeable via the second incoming hole for parallel connection.
Screw distribution blocks
PB111243-20_1.eps
PB111252-20_1.eps
4P PB111251-20_1.eps
1P
PB111250-20_1.eps
Number of poles
Rated operational current
125 A
160 A
250 A
100 A
Total connections capacity
10
13
14
4x7
2 x Ø 9.5 mm
2 x Ø 12 mm
1 x Ø 15.3 mm
2 x Ø 7.5 mm
2 x Ø 7.5 mm
3 x Ø 7.5 mm
1 x Ø 10 mm
5 x Ø 5.5 mm
6 x Ø 5.8 mm
8 x Ø 5.8 mm
4 x Ø 6 mm
-
-
-
8 x Ø 7.5 mm
-
25 kÂ
36 kÂ
60 kÂ
14 kÂ
-
-
-
24 kÂ
Rated short-time withstand current (Icw) (IEC/EN 60947-7-1)
4.2 kA rms/1 s
8.4 kA rms/1 s
14.4 kA rms/1 s
3 kA rms/1 s
Width (number of 9 mm pitches)
3
4
5
8
Dimension (H x W x D)
85 x 27 x 50.5
85 x 36 x 50.5
85 x 45 x 50.5
100 x 71 x 50.5
Weight (g)
125
163
239
210
Neutral terminal strip (optional) -
-
-
LGYN1007
References
LGY116013
LGY125014
LGY410028
Terminal capacity Diameter
Rated peak Ipk/60 ms withstand current Ipk/6 ms (Ipk)
60
LGY112510