The text of a spec sheet · part 7 of 9
Multi 9: Modular protection for OEMs, Catalogue 2018, pages 61 to 70
Pages 61 to 70 of 84
The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Schneider 17414, Schneider 17423, Schneider 24430, Schneider 24435, Schneider 24503 and Schneider 24505
Page 61
Auxiliaries and accessories www.schneider-electric.com
Linergy DS screw distribution blocks (cont.) Technical data Common characteristics
To IEC/EN 60947-7-1 and IEC/EN 61439-1 & 2 Rated insulation voltage (Ui)
500 V AC
Rated operational voltage (Ue)
230 V AC (Ph/N) 440 V AC (Ph/Ph) 8 kV
Rated impulse withstand voltage (Uimp) DB406005_1.eps
Rated conditional short-circuit current of an assembly Network frequency
Up to the breaking capacity of Schneider Electric feeder circuit breakers, even in cascading configuration 50/60 Hz
Pollution degree
3
Overvoltage category
III
Additional technical characteristics
On LGY412560 and LGY416048 references. Input cabling facilitated by side terminals.
Reference temperature
40 °C
Operating temperature
-25 °C to 55 °C
Dielectric withstand (IEC/EN 60947-1)
2500 V AC
PB111247-20_1.eps
PB111248-20_1.eps
160 A
100 A
125 A
4 x 12
4 x 15
4 x 12
7
12
15
1 x Ø 9 mm
1 x Ø 9.5 mm
1 x Ø 12 mm
2 x Ø 7.5 mm
1 x Ø 9 mm
1 x Ø 9.5 mm
7 x Ø 7.5 mm
3 x Ø 8.5 mm
3 x Ø 9 mm
5 x Ø 5.5 mm
7 x Ø 7.5 mm
3 x Ø 8.5 mm
4 x Ø 6.5 mm
11 x Ø 6.5 mm
8 x Ø 7.5 mm
-
4 x Ø 6.5 mm
11 x Ø 6.5 mm
-
-
-
-
-
-
18 kÂ
18 kÂ
22 kÂ
-
-
-
26 kÂ
28 kÂ
36 kÂ
-
-
-
4.2 kA rms/1 s
4.2 kA rms/1 s
8.4 kA rms/1 s
-
-
-
14
20
18
7
14
17
100 x 126 x 50.5
100 x 162 x 50.5
100 x 174 x 50.5
20 x 70 x 35
20 x 125 x 35
20 x 155 x 35
390
559
567
63
111
149
LGYN12512
LGYN12515
LGYN12512
-
-
-
LGY412548
LGY412560
LGY416048
LGYN1007
LGYN12512
LGYN12515
125 A
PB111249-20_1.eps
PB111246-20_1.eps
PB111245-20_1.eps
PB111244-20_1.eps
Neutral terminal strip
3
Terminal technical data Type
PZ2 screw
Diameter
Ø 5.5 mm
Ø 5.8 mm
Ø 6 mm
Ø 6.5 mm
Ø 7.5 mm
Ø 8.5 mm
Ø 9 mm
Ø 9.5 mm
Section rigid cable
1.5 to 16 mm²
1.5 to 16 mm²
1.5 to 16 mm²
1.5 to 16 mm²
2.5 to 25 mm²
6 to 35 mm²
10 to 35 mm²
10 to 35 mm²
Section flexible cable or with ferrule
1.5 to 10 mm²
1.5 to 10 mm²
1.5 to 10 mm²
1.5 to 10 mm²
1.5 to 16 mm²
4 to 25 mm²
4 to 25 mm²
6 to 35 mm²
Tightening torque
2 N.m
2 N.m
2 N.m
2 N.m
2 N.m
2 N.m
2.5 N.m
2.5 N.m
Type
Hc screw
Diameter
Ø 9.5 mm
Ø 10 mm
Ø 12 mm
Ø 15.3 mm
Section rigid cable
10 to 35 mm²
1.5 to 50 mm²
25 to 70 mm²
35 to 120 mm² Ø y 15 mm
Section flexible cable or with ferrule
6 to 35 mm²
1.5 to 35 mm²
16 to 50 mm²
Tightening torque
8 N.m
4 N.m
1P: 9 N.m
25 to 95 mm² 4P: 5 N.m
14 N.m
61
Page 62
Auxiliaries and accessories www.schneider-electric.com
Linergy DS screw distribution blocks (cont.) Dimensions (mm) DB405953
95 27
36
45
5.5
45
85
DB405954
LGY112510
LGY116013
70
LGY125014
125
155
35 20
20
3.5
LGYN1007
LGYN12512
LGYN12515
DB405954
126 71
126
162
174
100
LGY410028
62
LGY412548
LGY412560
LGY416048
5
45
Page 63
www.schneider-electric.com
3
63
Page 64
Technical information www.schneider-electric.com
Breaker standards The setup of circuit protective devices depends on the electrical installation standard. Multi 9 devices (designed for machinery and equipment manufacturers, integrators, panelbuilders, etc.) are tested in accordance with the UL (Underwriter Laboratories) product standard in order to meet the requirements of the NEC (National Electric Code) installation standard, in force in the United States. To allow the most extensive possible use worldwide, Multi 9 “UL” products are also tested to ensure compliance with IEC and CSA standards. The CE Marking is an administrative formality for free circulation and sale on the territory of the European Union. Made compulsory by a European directive, the CE Marking of products complies with the administrative and legal requirements. Designed for the European supervisory authorities (customs authorities), the “CE Marking” declarations and dossiers are produced under the sole responsibility of the manufacturer and undergo no conformity check by a third-party organization. Only the quality marks, issued and inspected by an independent third-party organization, provide a full guarantee of operation, compatibility and safety in accordance with national and international standards.
UL 489 Branch circuit protection
The UL 489 standard applies primarily to the protection of circuits installed, in accordance with the NEC (National Electric Code): bb upstream of a device or a machine (branch circuit protection) bb inside the device or a machine, for certain loads (ventilation, air conditioning, heating, etc.) bb to power loads external to the device (motors, power sockets, etc.).
UL 1077 Supplementary protection - Internal protection of electrical equipment
The UL 1077 standard applies to circuit breakers for electrical equipment, in accordance with the NEC. These circuit breakers are considered as components forming part of the equipment but can in no case replace a UL 489 protective device. Their use is limited to the protection of specific loads exclusively inside the machine or equipment. Where the machine or equipment is powered upstream by a control panel, the UL 1077 protection must be combined with a UL 489 protective device in that panel.
CSA C22.2 No. 5-02 Branch circuit protection
The requirements of this standard cover circuit breakers that are specifically intended to provide service entrance, feeder and branch circuit protection in accordance with the National Installation Codes. This standard is close to UL489.
CSA C22.2 No. 235-04 Supplementary protection - Internal protection of electrical equipment
This Standard applies to supplementary protectors that are intended for use as components within appliances or other electrical equipment where branch-circuit protection is already provided (or is not required), in accordance with the Rules of the Canadian Electrical Code. This standard is close to UL1077.
IEC 60947-2 The IEC 60947-2 standard is an international product standard concerning circuit breakers; it is used for industrial circuit protection applications. It meets the requirements of the IEC 60364 installation standard.
GB 14048-2 The GB 14048-2 standard is close to the IEC 60947-2 standard for installations on Chinese territory.
64
Page 65
Technical information www.schneider-electric.com
The standards and their applications Example of use of UL 489 circuit breakers and UL 1077 electrical equipment internal protective devices UL 489 Distribution circuit “Branch circuit protection”
1
2 None if protection by secondary Miscellaneous circuit breaker devices
1
UL 489
UL 489
UL 1077
Internal power socket
3
External power socket
External motor
Electronics
2 UL 1077 Other sensitive devices
4 UL 489
Heating, ventilation and air conditioning equipment
Equipment case
UL 1077
UL 489
Applications allowing the use of electrical equipment internal protective devices
Applications requiring branch circuit protection
UL 1077
Equipment incoming end protection.
1 Supplements an existing protective device or provides additional protection inside equipment UL 1077
2
Used for the protection of internal circuits such as: b Computers and microprocessors b Telecommunications equipment b Electronic controllers b Power supply sources b Transformers b Small motors.
UL 489
UL 489
1
2
Power socket circuit protection (internal or external). UL 489
3
Protection of an external circuit (e.g. motor). UL 489
4
Protection of heating, ventilation and air conditionning equipment (HACR/HVAC).
65
4
Page 66
Technical information www.schneider-electric.com
DB124179
Circuit breakers tripping curves The following curves show the total fault current breaking time, depending on its amperage. For example: based on the curve on "Circuit breakers tripping curves", page 66, a C60 circuit breaker of curve C, 20 A rating, will interrupt a current of 100 A (5 times the rated current In) in: bb 1 second at least bb 7 seconds at most.
t
Thermal tripping limits
The circuit breakers’ tripping curves consist of two parts: bb tripping of overload protection (thermal tripping device): the higher the current, the shorter the tripping time bb tripping of short-circuit protection (magnetic tripping device): if the current exceeds the threshold of this protection device, the breaking time is less than 10 milliseconds. For short-circuit currents exceeding 20 times the rated current, the time-current curves do not give a sufficiently precise representation. The breaking of high short-circuit currents is characterized by the current limiting curves, in peak current and in energy. The total breaking time can be estimated at 5 times the value of the ratio (I2t)/(Î)2.
Electromagnetic tripping limits min.
Verification of the discrimination between two circuit breakers max.
In
By superimposing the curve of a circuit breaker on that of the circuit breaker installed upstream, one can check whether this combination will be discriminating in cases of overload (discrimination for all current values, up to the magnetic threshold of the upstream circuit breaker). This verification is useful when one of the two circuit breakers has adjustable thresholds; for fixed-threshold devices, this information is provided directly by the discrimination tables. To check discrimination on short circuit, the energy characteristics of the two devices must be compared.
Alternative current 50/60 Hz C60BP, C60BPR, C60SP
C60N, C60H, C60L, C60CTRL Curves Z, B, C, D
3600 s for I/In = 1.05
DB408502
According to IEC/EN 60947-2 (reference temperature 50°C)
Curves Z, B, C, D DB428049
According to IEC/EN 60947-2 (reference temperature 25°C)
3600 s for I/In= 1.3
3600 s for I/In = 1.05
1000
1000
100
100
10
10 t(s)
t(s) 1
1
0,1
0,01
Z
1
B
C
4±20%
8.5±20%
3±20%
I / In
D
12±20%
Note: IEC/EN 60947-2 tripping curves, respecting the tripping time specified by the standards UL 489, CSA C22.2 No 5, UL 1077 and CSA C22.2 No 235
66
3600 s for I/In= 1.3
0,1
0,01
Z
1
B
4±20% 3±20%
I / In
C
D
8.5±20% 12±20%
Page 67
Technical information www.schneider-electric.com
Circuit breakers tripping curves (cont.) Direct current C60N, C60H, C60L, C60CTRL
According to IEC/EN 60947-2 (reference temperature 25°C)
According to IEC/EN 60947-2 (reference temperature 50°C)
Curves Z, B, C, D
Curves Z, B, C, D
3600 s for I/In = 1.05
DB408503
DB428050
C60BP, C60BPR, C60SP
3600 s for I/In = 1.3
1000
3600 s for I/In = 1.05
3600 s for I/In = 1.3
1000
100
100
10
10 t(s)
t(s) 1
1
0,1
Z
B
C
D
5.7±20%
12±20%
0,01 1
4.2±20% I / In
17±20%
0.1
0.01
Z
1
B
C
5.7±20%
12±20%
4.2±20% I / In
D
17±20%
Note: IEC/EN 60947-2 tripping curves, respecting the tripping time specified by the standards UL 489, CSA C22.2 No 5, UL 1077 and CSA C22.2 No 235
C60H-DC According to IEC/EN 60947-2 (reference temperature 25°C) DB406178
Curves B, C, K
3600 s for I/In = 1.05
3600 s for I/In = 1.3
1000
100
4 10 t(s) 1
0.1
B 0.01
1
C
3...7
I / In
K 10...14
7...10
Note: IEC/EN 60947-2 tripping curves, respecting the tripping time specified by the standards UL 1077 and CSA C22.2 No 235
67
Page 68
Technical information www.schneider-electric.com
Influence of ambient temperature Influence of temperature on the operation Devices
Characteristics influenced by temperature
Temperature
Mini
Maxi
C60BP, C60BPR, C60SP, C60N, C60H, C60L, C60CTRL circuit breakers
Tripping on overload
-30°C
+70°C
N40N circuit breakers
Tripping on overload
-25°C
+70°C
C60H-DC circuit breakers
Tripping on overload
-25°C
+70°C
Circuit breakers with
Tripping on overload
-5°C
+60°C
-25°C
+60°C
Tripping on overload
-5°C
+60°C
Vigi AC Type Vigi A-SI Type
N40 Vigi GFP
A-SI Type
Maximum operating current
-25°C
+60°C
ID
AC Type
Maximum operating current
-5°C
+40°C
A-SI Type
-25°C
+40°C
B Type
-25°C
+40°C
Note: the temperature considered is the temperature viewed through the device.
Circuit breakers High temperatures bb A rise in temperature decreases the tripping current of the thermal protection. bb Protection is still ensured: the tripping threshold remains lower than the current acceptable by the cable (Iz) bb To prevent nuisance tripping, it should be checked that this threshold remains higher than the maximum operating current (IB) of the circuit, defined by: vv the rated load currents, vv the coefficients of expansion and simultaneity of use. If the temperature is sufficiently high for the tripping threshold to become lower than the operating current IB, switchboard ventilation should be provided for.
Low temperatures bb A fall in temperature increases the tripping current of the thermal protection. bb There is no risk of nuisance tripping: the threshold remains higher than the maximum operating current of the circuit (IB) demanded by the loads. bb It should be checked that the cable remains suitably protected, i.e. that its acceptable current (Iz) is higher than the values shown in the following tables (in amperes).
When the ambient temperature could vary within a broad range, both these aspects must be taken into account: bb the difference between the maximum operating current of the circuit (IB) and the tripping threshold of the circuit breaker for the minimum ambient temperature, bb the difference between the strength of the cable (IZ) and the maximum tripping threshold of the circuit breaker for the maximum ambient temperature.
68
Page 69
Technical information www.schneider-electric.com
Influence of ambient temperature (cont.) Maximum permissible current bb The maximum current allowed to flow through the device depends on the ambient temperature in which it is placed. bb The ambient temperature is the temperature inside the enclosure or switchboard in which the devices are installed. bb The reference temperature is in a halftone colour for the different devices. bb When several devices operating simultaneously are mounted side by side in a small enclosure, a temperature rise in the enclosure results in a reduction in the operating current. A reduction coefficient of 0.8 will then have to be assigned to the rating (already derated, if applicable, depending on the ambient temperature). bb Example: Depending on the ambient temperature and the method of installation, the table below shows how to determine, for a C60, the operating currents not to be exceeded for ratings 25 A, 32 A and 40 A (reference temperature 50°C).
Operating current not to be exceeded (A) Installation conditions (IEC 60947-2)
C60 alone
Ambient temperature (°C)
35 °C 50 °C 65 °C 35 °C
Type
Nominal rating (A)
Actual rating (A)
C60
Several C60 in the same enclosure (calculate with the reduction coefficient indicated below) 50 °C
25
26.7
25
23.2
26.7 x 0.8 = 21.4 25 x 0.8 = 20
32
34
32
29.9
34 x 0.8 = 27
40
42.9
40
36.9
42.9 x 0.8 = 34.3 40 x 0.8 = 32
65 °C
23.2 x 0.8 = 18.6
32 x 0.8 = 25.6 29.9 x 0.8 = 24 36.9 x 0.8 = 29.5
4
69
Page 70
Technical information www.schneider-electric.com
Influence of ambient temperature (cont.)
C60BP, C60BPR, C60SP derating table C60BP, C60BPR, C60SP
Ambient temperature (°C)
Rating
-30
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+70
0.5 A
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.4
0.4
0.4
0.4
1A
1.4
1.3
1.3
1.3
1.2
1.2
1.2
1.1
1.1
1.1
1.0
1.0
1.0
0.9
0.9
0.8
0.8
0.7
0.7
0.6
2A
2.5
2.5
2.4
2.4
2.3
2.3
2.3
2.2
2.2
2.1
2.1
2.0
1.9
1.9
1.8
1.8
1.7
1.6
1.6
1.4
3A
3.7
3.7
3.6
3.6
3.5
3.4
3.4
3.3
3.2
3.1
3.1
3.0
2.9
2.8
2.8
2.7
2.6
2.5
2.4
2.2
4A
5.0
4.9
4.8
4.8
4.7
4.6
4.5
4.4
4.3
4.2
4.1
4.0
3.9
3.8
3.7
3.6
3.4
3.3
3.2
2.9
5A
6.2
6.1
6.0
5.9
5.8
5.7
5.6
5.5
5.4
5.2
5.1
5.0
4.9
4.8
4.6
4.5
4.3
4.2
4.1
3.7
6A
7.8
7.6
7.5
7.3
7.2
7.0
6.9
6.7
6.5
6.4
6.2
6.0
5.8
5.6
5.4
5.2
5.0
4.8
4.5
4.0
8A
9.9
9.8
9.6
9.5
9.3
9.1
8.9
8.8
8.6
8.4
8.2
8.0
7.8
7.6
7.4
7.2
6.9
6.7
6.5
6.0
10 A
12.4
12.2
12.0
11.8
11.6
11.4
11.2
10.9
10.7
10.5
10.2
10.0
9.7
9.5
9.2
9.0
8.7
8.4
8.1
7.4
13 A
15.6
15.4
15.2
15.0
14.7
14.5
14.3
14.0
13.8
13.5
13.3
13.0
12.7
12.5
12.2
11.9
11.6
11.3
11.0
10.4
15 A
18.1
17.8
17.6
17.3
17.0
16.7
16.5
16.2
15.9
15.6
15.3
15.0
14.7
14.4
14.0
13.7
13.4
13.0
12.7
11.9
16 A
18.9
18.6
18.4
18.1
17.9
17.6
17.4
17.1
16.8
16.6
16.3
16.0
15.7
15.4
15.1
14.8
14.5
14.2
13.9
13.2
20 A
24.6
24.3
23.9
23.5
23.1
22.7
22.2
21.8
21.4
20.9
20.5
20.0
19.5
19.0
18.5
18.0
17.5
16.9
16.4
15.2
25 A
30.1
29.7
29.3
28.8
28.4
27.9
27.5
27.0
26.5
26.0
25.5
25.0
24.5
23.9
23.4
22.8
22.3
21.7
21.1
19.8
30 A
38.2
37.6
36.9
36.2
35.5
34.7
34.0
33.2
32.5
31.7
30.8
30.0
29.1
28.2
27.3
26.4
25.4
24.4
23.3
21.0
32 A
40.2
39.5
38.8
38.1
37.4
36.7
36.0
35.2
34.4
33.6
32.8
32.0
31.1
30.3
29.4
28.4
27.5
26.5
25.4
23.2
35 A
42.5
41.9
41.2
40.6
39.9
39.3
38.6
37.9
37.2
36.5
35.7
35.0
34.2
33.5
32.7
31.8
31.0
30.1
29.2
27.4
40 A
48.9
48.1
47.4
46.6
45.9
45.1
44.3
43.4
42.6
41.8
40.9
40.0
39.1
38.2
37.2
36.2
35.2
34.2
33.1
30.9
45 A
54.7
53.9
53.1
52.2
51.4
50.5
49.7
48.8
47.8
46.9
46.0
45.0
44.0
43.0
42.0
40.9
39.8
38.7
37.5
35.1
50 A
59.8
59.0
58.2
57.3
56.5
55.6
54.7
53.8
52.9
51.9
51.0
50.0
49.0
48.0
47.0
45.9
44.8
43.7
42.6
40.2
63 A
80.0
78.6
77.2
75.7
74.2
72.7
71.2
69.6
68.0
66.4
64.7
63.0
61.2
59.4
57.5
55.6
53.5
51.4
49.2
44.5
C60N, C60H, C60L, C60CTRL derating table C60N, C60H, Ambient temperature (°C) C60L, C60CTRL Rating
-30
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
1A
1.31
1.3
1.28
1.27
1.25
1.23
1.21
1.19
1.17
1.15
1.13
1.11
1.09
1.07
1.05
1.02
1
0.98
0.95
0.93
0.91
2A
2.55
2.59
2.56
2.52
2.49
2.45
2.41
2.37
2.34
2.3
2.26
2.22
2.17
2.13
2.09
2.04
2
1.95
1.91
1.88
1.84
3A
3.81
4.04
3.98
3.92
3.85
3.79
3.73
3.66
3.59
3.52
3.45
3.38
3.31
3.23
3.16
3.08
3
2.92
2.83
2.82
2.76
4A
4.9
4.86
4.81
4.76
4.7
4.65
4.59
4.54
4.48
4.42
4.37
4.31
4.25
4.19
4.13
4.06
4
3.94
3.87
3.81
3.74
6A
7.93
7.82
7.71
7.6
7.49
7.38
7.27
7.15
7.03
6.91
6.79
6.66
6.54
6.41
6.27
6.14
6
5.86
5.71
5.56
5.42
10 A
13.3
13.2
13
12.8
12.6
12.4
12.2
12
11.8
11.6
11.4
11.2
10.9
10.7
10.5
10.2
10
9.8
9.5
9.2
9
13 A
17
16.9
16.6
16.4
16.2
15.9
15.7
15.4
15.2
14.9
14.7
14.4
14.1
13.9
13.6
13.3
13
12.7
12.4
12.1
11.8
16 A
20
19.8
19.5
19.3
19.1
18.8
18.6
18.4
18.1
17.9
17.6
17.3
17.1
16.8
16.6
16.3
16
15.7
15.4
15.1
14.8
20 A
26.9
26.6
26.2
25.8
25.4
25
24.6
24.2
23.7
23.3
22.9
22.4
22
21.5
21
20.5
20
19.5
18.9
18.4
17.9
25 A
32.9
32.5
32.1
31.6
31.1
30.7
30.2
29.7
29.2
28.7
28.2
27.7
27.2
26.7
26.1
25.6
25
24.4
23.8
23.2
22.6
32 A
41.5
41.1
40.5
40
39.4
38.9
38.3
37.7
37.1
36.5
35.9
35.3
34.7
34
33.4
32.7
32
31.3
30.6
29.9
29.1
40 A
53.7
52.9
52.2
51.4
50.6
49.8
49
48.2
47.3
46.5
45.6
44.7
43.8
42.9
42
41
40
39
37.9
36.9
35.8
50 A 63 A
65 85.5
64.3 84.6
63.5 83.3
62.6 82
61.7 80.7
60.8 79.4
59.9 78
59 76.7
58.1 75.3
57.1 73.9
56.2 72.4
55.2 70.9
54.2 69.4
53.2 67.9
52.1 66.3
51.1 64.7
50 63
48.9 61.3
47.8 59.5
46.7 57.8
45.5 56
70