Page 71
Technical information www.schneider-electric.com
Influence of ambient temperature (cont.)
N40N, N40 vigi derating table N40N, N40 Vigi
Ambient temperature (°C)
Rating
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
1A
1.66
1.62
1.59
1.55
1.51
1.47
1.43
1.39
1.35
1.3
1.26
1.21
1.16
1.11
1.06
1
0.94
0.88
0.81
0.73
2A
2.64
2.6
2.56
2.52
2.48
2.44
2.4
2.36
2.32
2.28
2.23
2.19
2.14
2.1
2.05
2
1.95
1.9
1.85
1.79
3A
3.97
3.91
3.86
3.8
3.74
3.68
3.61
3.55
3.49
3.42
3.36
3.29
3.22
3.15
3.07
3
2.92
2.85
2.77
2.68
4A
5.19
5.12
5.05
4.98
4.9
4.83
4.75
4.67
4.6
4.52
4.43
4.35
4.27
4.18
4.09
4
3.91
3.81
3.72
3.62
6A
7.42
7.34
7.25
7.16
7.07
6.98
6.89
6.8
6.7
6.61
6.51
6.41
6.31
6.21
6.11
6
5.89
5.78
5.67
5.56
10 A
12.9
12.7
12.5
12.3
12.2
12
11.8
11.6
11.4
11.2
11
10.8
10.6
10.4
10.2
10
9.8
9.6
9.3
9.1
16 A
20.4
20.1
19.8
19.6
19.3
19
18.7
18.5
18.2
17.9
17.6
17.3
17
16.7
16.3
16
15.7
15.3
15
14.6
20 A
25.7
25.3
25
24.6
24.3
23.9
23.6
23.2
22.8
22.4
22
21.7
21.3
20.8
20.4
20
19.6
19.1
18.7
18.2
25 A
31.6
31.2
30.8
30.4
30
29.6
29.2
28.7
28.3
27.8
27.4
26.9
26.5
26
25.5
25
24.5
24
23.5
22.9
32 A
41.1
40.5
40
39.4
38.9
38.3
37.7
37.1
36.5
35.9
35.3
34.7
34
33.4
32.7
32
31.3
30.6
29.9
29.1
40 A
52
51.3
50.6
49.8
49.1
48.3
47.6
46.8
46
45.2
44.4
43.5
42.7
41.8
40.9
40
39.1
38.1
37.1
36.1
C60H-DC derating table C60H-DC
Ambient temperature (°C)
Rating
-25
-20
-15
-10
-5
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
+55
+60
+65
+70
0.5 A
0.62
0.61
0.6
0.59
0.58
0.56
0.55
0.54
0.53
0.51
0.5
0.49
0.47
0.46
0.44
0.43
0.41
0.39
0.38
0.36
1A
1.17
1.15
1.14
1.12
1.1
1.09
1.07
1.05
1.04
1.02
1
0.98
0.96
0.94
0.92
0.9
0.88
0.86
0.84
0.82
2A
2.5
2.45
2.41
2.36
2.31
2.26
2.21
2.16
2.11
2.06
2
1.94
1.88
1.82
1.76
1.7
1.63
1.56
1.48
1.41
3A
3.71
3.65
3.58
3.51
3.45
3.38
3.3
3.23
3.16
3.08
3
2.92
2.84
2.75
2.66
2.57
2.48
2.38
2.27
2.17
4A
4.99
4.9
4.81
4.71
4.62
4.52
4.42
4.32
4.22
4.11
4
3.89
3.77
3.65
3.53
3.4
3.27
3.13
2.98
2.83
5A
5.92
5.83
5.74
5.66
5.57
5.48
5.39
5.29
5.2
5.1
5
4.9
4.8
4.69
4.58
4.47
4.36
4.24
4.12
4
6A
7.15
7.04
6.94
6.83
6.71
6.6
6.48
6.37
6.25
6.12
6
5.87
5.74
5.61
5.47
5.33
5.19
5.04
4.89
4.73
10 A
12.4
12.2
11.9
11.7
11.5
11.3
11
10.8
10.5
10.3
10
9.7
9.5
9.2
8.9
8.6
8.3
7.9
7.6
7.2
13 A
15.3
15.1
14.9
14.6
14.4
14.2
14
13.7
13.5
13.3
13
12.8
12.5
12.2
12
11.7
11.4
11.1
10.8
10.5
15 A
18.3
18
17.7
17.4
17.1
16.7
16.4
16.1
15.7
15.4
15
14.6
14.3
13.9
13.5
13
12.6
12.2
11.7
11.2
16 A
19.1
18.9
18.6
18.3
18
17.6
17.3
17
16.7
16.3
16
15.7
15.3
14.9
14.6
14.2
13.8
13.4
13
12.5
20 A
23.7
23.4
23
22.7
22.3
21.9
21.6
21.2
20.8
20.4
20
19.6
19.2
18.7
18.3
17.9
17.4
16.9
16.4
15.9
25 A
29.9
29.5
29
28.5
28.1
27.6
27.1
26.6
26.1
25.5
25
24.5
23.9
23.3
22.7
22.1
21.5
20.9
20.2
19.6
30 A
36.7
36.1
35.5
34.9
34.2
33.5
32.9
32.2
31.5
30.7
30
29.2
28.5
27.7
26.8
26
25.1
24.2
23.2
22.3
32 A
37.9
37.4
36.8
36.2
35.7
35.1
34.5
33.9
33.3
32.6
32
31.4
30.7
30
29.3
28.6
27.9
27.1
26.3
25.5
40 A
48.2
47.4
46.7
45.9
45.1
44.3
43.5
42.6
41.8
40.9
40
39.1
38.2
37.2
36.2
35.2
34.2
33.1
32
30.8
50 A
59.1
58.3
57.4
56.5
55.6
54.7
53.8
52.9
52
51
50
49
48
46.9
45.9
44.8
43.6
42.5
41.3
40.1
63 A
76.9
75.6
74.3
73
71.7
70.3
68.9
67.5
66
64.5
63
61.4
59.8
58.2
56.5
54.7
52.9
51.1
49.1
47.1
RCCB bb In all cases, the RCCB are correctly protected against overloads by a circuit breaker with a lower or equal rating, operating at the same ambient temperature.
71
4
Page 72
Technical information www.schneider-electric.com
Dissipated power, Impedance and Voltage drop Multi 9 products Rating (A)
0.5 1
2
The following table indicates the average dissipated power per pole in W for a current equal to the rating of the device and at the operating voltage.
3
4
5 2.2
6
8
1.2
1.7
10 13 15 16 20 25 30 32 35 40 45 50 63 80 100 125
Circuit breakers C60BP, C60BPR, C60SP 2.6
1.3
1.7
1.9
2.0
C60N, C60H, C60L, C60CTRL
1.3
1.7
1.9
2.0
N40N C60H-DC
2.6
1.2
1.9
2.4
2.6
2.2
3.4
1.9
2.4
2.6
2.2
2.7
3.2
4.7
4.7
4.6
5.8
2.4
2.6
2.2
2.7
3.2
3.6
2.5
1.9
2.1
2.6
2.7
2.7
1.3
1.7
1.9
2.0
1.2
1.9
2.3
2.5
2.8 3.2
3.5
3.6 3.6
3.9
4.8
4.8
4.8
4.3
4.8
4.3
RCCB GFP A-SI Type
1,4
3.6
4.4
ID AC / A-SI Type
1.4
3.6
4.4
ID B Type
1.2
2.9
7.2
4.5
6.4
18 12
RCBO N40 Vigi
4.1
3.2
3.9
4.4
Add-on residual current devices Vigi C60 AC / A-SI Type Vigi N40 AC / A-SI Type
3.0 2.1
Note: RCBO dissipated power per pole is the sum of circuit breaker dissipated power per pole + add-on residual current device dissipated power per pole. Example: C60N (63 A) + Vigi C60 (63 A) = 4.3 + 3.0 = 7.3 W.
Impedance calculation: Z = P / I² Z: impedance in Ohms P: dissipated power in Watts (table values) I: rating in Amperes
72
Voltage drop calculation: U=P/I U: voltage drop in Volts P: dissipated power in Watts (table values) I: rating in Amperes
28
Page 73
Technical information www.schneider-electric.com
DB125793
Short-circuit current limiting Definition
Isc Prospective peak Isc
The limiting capacity of a circuit breaker is its ability to lessen the effects of a short circuit on an electrical installation by reducing the current amplitude and the dissipated power.
Benefits of limiting
Prospective Isc
Long installation service life
Limited peak Isc Limited Isc tc t
Prospective current and real limit current.
Savings through cascading
DB125794
I²sc A²
Thermal effects Lower temperature rise at the conductor level, hence increased service life for cables and all components that are not self-protected (e.g. switches, contactors, etc.) Mechanical effects Lower electrodynamic repulsion forces, hence less risk of deformation or breakage of electrical contacts and busbars. Electromagnetic effects Less interference on sensitive equipment located in the vicinity of an electric circuit.
Prospective energy 100%
Cascading is a technique derived directly from current limiting: downstream of a current-limiting circuit breaker it is possible to use circuit breakers of breaking capacity lower than the prospective short-circuit current (in line with the cascading tables). The breaking capacity is heightened thanks to current limiting by the upstream device. Substantial savings can be achieved in this way on switchgear and enclosures.
Discrimination of protection devices
The circuit breakers' current limiting capacity improves discrimination with the protection devices located upstream: this is because the required energy passing through the upstream protection device is greatly reduced and can be not enough to cause it to trip. Discrimination can thus be natural without having to install a time-delayed protection device upstream. Limited energy 100% t
4
73
Page 74
Technical information www.schneider-electric.com
Short-circuit current limiting (cont.) Representation: Current limiting curves
The current limiting capacity of a circuit breaker is reflected by 2 curves which give, as a function of the prospective short-circuit current (current which would flow in the absence of a protection device): bb the real peak current (limited) bb the thermal stress (in A²s), this value, multiplied by the resistance of any element through which the short-circuit current passes, gives the power dissipated by this element. The straight line "10 ms" representing the energy A²s of a prospective short-circuit current of a half-period (10 ms) indicates the energy that would be dissipated by the short-circuit current in the absence of limiting by the protection device (see example).
DB409741
Example 1000000
100000
> as shown in the graph opposite: b this short-circuit current (10 kA rms) is likely to dissipate up to 1,000 kA2s b the C60N circuit breaker reduces this thermal stress to: 43 kA2s, which is 23 times less.
50 - 63 32 - 40 20 - 25
43 kA2s
Thermal stress (A²s)
What is the energy limited by a C60N 25 A circuit breaker for a prospective short-circuit current of 10 kA rms. What is the quality of current limiting?
10 ms
10 - 16
10000
6 4 3 2
1000
1
Example of use: Stresses acceptable by the cables
100
10 0.01
0.1
1
10
Prospective short-circuit current (kA eff.)
100
The following table shows the thermal stresses acceptable by the cables depending on their insulation, their composition (Cu or Al) and their cross section. Cross-section values are expressed in mm² and stresses in A²s. S (mm²) PVC
C60N Thermal stress (380-415 V AC)
Cu
1.5
2.5
4
6
2.97 x 104
8.26 x 104
2.12 x 105
4.76 x 105
Al PRC
Cu
S (mm²)
PRC
1.32 x 106 5.41 x 105
4.10 x 104
1.39 x 105
2.92 x 105
6.56 x 105
Al PVC
10
1.82 x 106 7.52 x 105
16
25
35
50
Cu
3.4 x 106
8.26 x 106
1.62 x 107
3.21 x 107
Al
1.39 x 106
3.38 x 106
6.64 x 106
1.35 x 107
Cu
4.69 x 10
6
1.39 x 10
7
2.23 x 10
7
4.56 x 107
Al
1.93 x 106
4.70 x 106
9.23 x 106
1.88 x 107
Example DB409740
Is a Cu/PRC cable of cross section 6 mm² protected by a C60N 40 A device? The above table shows that the acceptable stress is 6.56 x 105 A²s. Any short-circuit current at the point where a C60N 40 A device (Icu = 25 kA) is installed will be limited, with a thermal stress of less than 5.7 x 105 A²s. The cable is therefore always protected up to the breaking capacity of the circuit breaker.
Peak current (kA)
100
10 63 40 16 - 25 10
5.7 kA
6 4
1
1
10
Prospective short-circuit current (kA eff.)
C60N Peak current (380-415 V AC)
74
100
Page 75
Technical information www.schneider-electric.com
Short-circuit current limiting (cont.) Ue: 380-415 V AC
Limitation curves for network Ue: 380-415 V AC (Ph/N 220-240 V AC) C60BP, C60BPR, C60SP 1P / 2P / 3P Peak current DB409735
DB409734
Thermal stress 10 ms
50 - 63 32 - 40 20 - 25
100000
10
Thermal stress (A²s)
100
Peak current (kA)
1000000
63 40 16 - 25 10 6
10 - 16
10000
6 4 3 2
1000
1
100
≤4
0.5
1
1
10
10 0.01
100
Prospective short-circuit current (kA eff.)
0.1
1
10
Prospective short-circuit current (kA eff.)
100
C60N 1P / 2P / 3P / 4P Peak current DB409737
DB409736
Thermal stress
Thermal stress (A²s)
Peak current (kA)
10 ms
100000
100
10 63 40 16 - 25 10
1
10
Prospective short-circuit current (kA eff.)
50 - 63 32 - 40 20 - 25 10 - 16
10000
6 4 3 2
1000
1
100
6
≤4
1
1000000
100
10 0.01
0.1
1
10
Prospective short-circuit current (kA eff.)
4
100
75
Page 76
Technical information www.schneider-electric.com
Short-circuit current limiting (cont.) Ue: 380-415 V AC
Limitation curves for network Ue: 380-415 V AC (Ph/N 220-240 V AC) C60H 1P / 2P / 3P / 4P Peak current DB409731
DB409730
Thermal stress 1000000
10
Thermal stress (A²s)
Peak current (kA)
50 - 63 32 - 40 20 - 25
100000
100
63 40 16 - 25 10 6
1
10 - 16
10000
6 4 3 2
1000
1
100
≤4
1
10 ms
10
Prospective short-circuit current (kA eff.)
10 0.01
100
0.1
1
10
Prospective short-circuit current (kA eff.)
100
C60L 1P / 2P / 3P / 4P Peak current DB409733
DB409732
Thermal stress 1000000
100000
10
Thermal stress (A²s)
Peak current (kA)
100
16 - 25 10 6
76
1
10
Prospective short-circuit current (kA eff.)
20 - 25 10 - 16 6
10000
4 3 2
1000
1
100
≤4
1
10 ms
100
10 0.01
0.1
1
10
Prospective short-circuit current (kA eff.)
100
Page 77
Technical information www.schneider-electric.com
Short-circuit current limiting (cont.) Ue: 380-415 V AC
Limitation curves for network Ue: 380-415 V AC (Ph/N 220-240 V AC) N40N, N40 Vigi 1P+N / 3P+N Peak current DB124270
DB124271
Thermal stress 1 000 000 10 ms
100
10 32 - 40 16 - 25 10 6 3-4 2
1
Thermal stress (A²s)
Peak current (kA)
100 000 32 - 40 16 - 25 10
10 000
6 3-4 2
1 000
1 1 0,1 0,01
0,1
1
Prospective short-circuit current (kA eff.)
10
100
0,01
0,1
1
Prospective short-circuit current (kA eff.)
10
4
77
Page 78
Technical information www.schneider-electric.com
Short-circuit current limiting (cont.) Direct current network
Limitation curves for direct current network C60H-DC C curve 1P (250 V DC) - 2P (500 V DC) Peak current DB409739
DB409738
Thermal stress
1000000 10 ms
100000
Thermal stress (A²s)
Peak current (kA)
100
10 50 - 63 32 - 40 16 10 6 4 3 2
1
20 - 25
50 - 63 32 - 40
10000
20 - 25 16 10 6 4
1000
3 0.5 - 2
≤1
0.1 0.01
78
0.1
1
10
Prospective short-circuit current (kA eff.)
100
100 0.01
0.1
1
10
Prospective short-circuit current (kA eff.)
100
Page 79
www.schneider-electric.com
DB4028051
Minimum clearance bewteen device and bare sheet metal (mm/inches) A
B
C
C
UL standard Products
C60BP
C60BPR
C60SP, C60H-DC
GFP
N40 Vigi
Vigi modules
Auxiliaries
A B C
10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 16 mm/0.63 in. 16 mm/0.63 in. 20 mm/0.79 in. 20 mm/0.79 in. 20 mm/0.79 in. 0 0 0 0 0
B
Details of minimum distances between the product and earthed metal parts for device intended for use without enclosure.
IEC standard Products
C60BP
A B C
10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 10 mm/0.39 in. 20 mm/0.79 in. 20 mm/0.79 in. 20 mm/0.79 in. 20 mm/0.79 in. 20 mm/0.79 in. 20 mm/0.79 in. 20 mm/0.79 in. 0 0 0 0 0 0 0 0 0
C60BPR
C60SP, C60H-DC
C60N, N40N C60H, C60L, C60CTRL
ID
Auxiliaries
4
79
Page 80
Control panel technical guides library
Discover our technical guides collection.
www.schneider-electric.com
How to reduce damage to components through effective thermal management inside an enclosure
How to protect a machine from malfunctions due to electromagnetic disturbances
Ref.: CPTG001_EN
Ref.: CPTG003_EN
They are dedicated to frequent issues faced when designing an installing a control panel.
Click on QR code or scan to download
Click on QR code or scan to download
How to prevent machine malfunctions and electronic damage due to voltage surges
How to ensure trouble-free approval of your UL-compliant control panels
Ref.: CPTG002_EN
Ref.: CPTG005_EN
Click on QR code or scan to download
Click on QR code or scan to download
Free download on www.schneider-electric.com with the document reference or from the QR codes.
80