Spec sheet · Schneider
Schneider 24503 Spec Sheet
Spec sheet2 pagesPDF 76 KB
Both pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Schneider Electric's two-page product data sheet for the 24503, a Multi 9 C60 UL1077 single-pole miniature circuit breaker rated 4 A with a D trip curve. It lists the breaker's ratings, breaking capacities, dimensions, wiring terminals and operating environment.
- Device
- Multi 9 C60 UL1077 miniature circuit breaker, 1 pole, for distribution p. 1
- Rated current
- 4 A at 25 °C p. 1
- Trip curve
- D curve, thermal-magnetic trip unit p. 1
- Network
- AC and DC, 50/60 Hz p. 1
- Rated voltage (Ue)
- 240 V AC, 415 V AC, 60 V DC p. 1
- UL 1077 breaking capacity
- AIR 5 kA at 277 V AC, 10 kA at 240 V AC, 10 kA at 65 V DC p. 1
- IEC breaking capacity
- Icu 10 kA at 240 V AC, 3 kA at 415 V AC, 10 kA at 60 V DC (EN/IEC 60947-2) p. 1
- Magnetic trip
- 12 x In +/- 20 % AC; 17 x In +/- 20 % DC p. 1
- Terminals
- Tunnel terminals, top or bottom, rigid wire 2.5 to 25 mm² (AWG 14 to AWG 4), 14 mm strip, 2.5 N.m p. 2
- Mounting
- Clips onto DIN rail; 18 mm wide (two 9 mm pitches) p. 1
- Dimensions
- 81 mm high, 18 mm wide, 73 mm deep; 0.11 kg p. 1, 2
- Operating temperature
- -30 to 70 °C (storage -40 to 80 °C) p. 2
- Durability
- 20000 mechanical cycles, 10000 electrical cycles p. 2
- Insulation
- Ui 500 V AC; Uimp 6 kV p. 1
What this sheet walks you through
- Checking breaking capacity by voltage and standard p. 1
- Wiring the terminals: wire size, strip length and torque p. 2
- Operating environment: humidity, altitude and temperature p. 2
Good to know
- The sheet states it is not meant for judging whether the product suits a specific application. p. 1
- Protection is IP20, or IP40 in a modular enclosure (IEC 60529). p. 2
Questions this sheet answers
What is the current rating of Schneider 24503?
The 24503 is a 1-pole C60 UL1077 breaker rated 4 A at 25 °C, with a D trip curve. p. 1
Can the 24503 be used on DC?
Yes. The sheet lists DC and AC network types, with a rated voltage of 60 V DC and UL 1077 AIR of 10 kA at 65 V DC. p. 1
What wire size fits the 24503 terminals?
Its tunnel terminals take rigid wire of 2.5 to 25 mm² (AWG 14 to AWG 4), top or bottom, tightened to 2.5 N.m. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
Product data sheet Characteristics
24503
Multi 9 - C60 UL1077 - MCB - 1P - 4 A - D Curve - 277 V - 5 kA
Range of productC60RangeMulti 9Product nameMulti 9 C60
Product or componenttype
Miniature circuit-breaker
Device short nameC60 UL1077Device applicationDistributionPoles description1P
Number of protectedpoles
1[In] rated current4 A at 25 °CNetwork typeDC ACTrip unit technologyThermal-magneticCurve codeDBreaking capacity codeNBreaking capacity
AIR 10 kA at 65 V DC conforming to UL 1077 AIR 10 kA at 65 V DC conformingto CSA C22.2 No 235 Icu 3 kA at 415 V AC conforming to EN/IEC 60947-2 Icu 10 kA at 240 V AC conformingto EN/IEC 60947-2 Icu 3 kA at 415 V AC conforming to GB 14048.2 Icu 10 kA at 240 V AC conforming to GB 14048.2 AIR 5 kA at 277 V AC conforming to UL 1077 AIR 10 kA at 240 V AC conforming to UL 1077 AIR 5 kA at 277 V AC conformingto CSA C22.2 No 235 AIR 10 kA at 240 V AC conformingto CSA C22.2 No 235 Icu 10 kA at 60 V DC conforming to EN/IEC 60947-2 Icu 10 kA at 60 V DC conforming to GB 14048.2
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Complementary Network frequency
50/60 Hz
[Ue] rated operational voltage
240 V AC 60 V DC 415 V AC
Magnetic tripping limit
12 x In +/- 20 % AC 17 x In +/- 20 % DC
Limitation class
3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage
500 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Contact position indicator
YesControl typeToggleLocal signallingON/OFF indicationMounting modeClip-onMounting supportDIN railConnection pitch18 mm Between devices9 mm pitches2Height81 mmWidth18 mmSep 7, 20181
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
Depth73 mmProduct weight0.11 kgColourGreyMechanical durability20000 cyclesElectrical durability10000 cycles
Provision for padlocking
Padlockable
Connections - terminals
Tunnel type terminal, top or bottom rigid wire(s) 2.5...25 mm² max (AWG 14...AWG 4)
Wire stripping length14 mm top or bottomTightening torque2.5 N.m top or bottomCompatibility codeC60_UL1077Environment Standards
UL 1077 GB 14048.2 EN/IEC 60947-2 CSA C22.2 No 235
Product certifications
CSA CCC IEC UR
IP degree of protection
IP40 for modular enclosure conforming to IEC 60529 IP20 conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Overvoltage categoryIVTropicalisation
2 conforming to IEC 60068-1
Relative humidity95 % 55 °COperating altitude2000 m
Ambient air temperature for operation
-30...70 °C
Ambient air temperature for storage
-40...80 °C
Offer Sustainability Sustainable offer status
Green Premium product
Product environmental profile
Available
Product end of life instructions
Need no specific recycling operations
Contractual warranty Warranty period
- Product Life Status
- 2
18 months
End of commercialisation