Page 1 of Schneider 24505 Spec Sheet

Spec sheet · Schneider

Schneider 24505 Spec Sheet

Spec sheet2 pagesPDF 74 KB

Both pages are below, each with its text.

Download the PDF74 KB

Covers · 1 model

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Schneider Electric product data sheet for the 24505, a Multi 9 C60 UL1077 miniature circuit breaker (1P, 8 A, D curve). It lists ratings, breaking capacities, dimensions, terminals and environmental limits.

What it is
Multi 9 C60 UL1077 miniature circuit breaker, 1P, 8 A, D curve, 277 V, 5 kA p. 1
Rated current
8 A at 77 °F (25 °C) p. 1
UL 1077 breaking capacity
AIR 5 kA at 277 V AC, 10 kA at 240 V AC, 10 kA at 65 V DC p. 1
Trip unit
Thermal-magnetic; magnetic trip 12 x In +/- 20% AC, 17 x In +/- 20% DC p. 1
Network
AC or DC, 50/60 Hz p. 1
Dimensions
81 mm high, 18 mm wide, 73 mm deep; 0.11 kg p. 1, 2
Mounting
Clip-on, DIN rail, 2 pitches of 9 mm p. 1
Terminals
Tunnel type, top or bottom, 2.5...25 mm² (AWG 14...AWG 4) rigid wire; strip 14 mm; 2.5 N.m p. 2
Operating temperature
-30...70 °C; storage -40...80 °C p. 2
Durability
20000 cycles mechanical, 10000 cycles electrical p. 2
Controls
Toggle with ON/OFF indication; padlockable p. 1, 2
Protection
IP20; IP40 in a modular enclosure p. 2

Good to know

  • The sheet says it is not meant for deciding whether the product suits a specific application. p. 1

Questions this sheet answers

What is the Schneider 24505?

A Multi 9 C60 UL1077 single-pole miniature circuit breaker rated 8 A with a D trip curve. p. 1

What is the breaking capacity of the 24505 at 277 V?

AIR 5 kA at 277 V AC under UL 1077. p. 1

What wire size fits the 24505 terminals?

Rigid wire from 2.5 to 25 mm² (AWG 14 to AWG 4), stripped 14 mm and tightened to 2.5 N.m. p. 2

The file

Size and text

Pages2
PDF74 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Schneider 24505 Spec Sheet

The text of page 1, from the PDF itself

Product data sheet Characteristics

24505

Multi 9 - C60 UL1077 - MCB - 1P - 8 A - D Curve 277 V - 5 kA

Range of productC60RangeMulti 9Product nameMulti 9 C60

Product or componenttype

Miniature circuit-breaker

Device short nameC60 UL1077Device applicationDistributionPoles description1P

Number of protectedpoles

1[In] rated current8 A at 77 °F (25 °C)Network typeAC DCTrip unit technologyThermal-magneticCurve codeDBreaking capacity codeNBreaking capacity

AIR 10 kA at 65 V DC conforming to UL 1077 AIR 10 kA at 65 V DC conforming to CSA C22.2 No 235 Icu 3 kA at 415 V AC conforming to EN/IEC 60947-2 Icu 10 kA at 240 V AC conforming to EN/IEC 60947-2 Icu 3 kA at 415 V AC conforming to GB 14048.2 Icu 10 kA at 240 V AC conforming to GB 14048.2 AIR 5 kA at 277 V AC conforming to UL 1077 AIR 10 kA at 240 V AC conforming to UL 1077 AIR 5 kA at 277 V AC conforming to CSA C22.2 No 235 AIR 10 kA at 240 V AC conforming to CSA C22.2 No 235 Icu 10 kA at 60 V DC conforming to EN/IEC 60947-2 Icu 10 kA at 60 V DC conforming to GB 14048.2

Suitability for isolation

Yes conforming to EN/IEC 60947-2

Complementary Network frequency

50/60 Hz

System Voltage

240 V AC 60 V DC 415 V AC

Magnetic tripping limit

12 x In +/- 20% AC 17 x In +/- 20% DC

Limitation class

3 conforming to EN/IEC 60947-2

[Ui] rated insulation voltage

500 V ACconforming to EN/IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-2

Contact position indicator

YesControl typeToggleLocal signallingON/OFF indicationMounting modeClip-onMounting supportDIN railConnection pitch

0.71 in (18 mm) Between devices

9 mm pitches2Height3.19 in (81 mm)Width0.71 in (18 mm)Sep 7, 20181

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Main

Page 2 of Schneider 24505 Spec Sheet

The text of page 2, from the PDF itself

Depth2.87 in (73 mm)Product weight0.24 lb(US) (0.11 kg)ColourGreyMechanical durability20000 cyclesElectrical durability10000 cycles

Provision for padlocking

Padlockable

Connections - terminals

Tunnel type terminal, top or bottom rigid wire(s) 0...0.04 in² (2.5...25 mm²) max (AWG 14...AWG 4)

Wire stripping length

0.55 in (14 mm) top or bottom

Tightening torque

22.12 lbf.in (2.5 N.m) top or bottom

Compatibility codeC60_UL1077Environment Standards

UL 1077 GB 14048.2 EN/IEC 60947-2 CSA C22.2 No 235

Product certifications

CSA CCC IEC UR

IP degree of protection

IP40 modular enclosure conforming to IEC 60529 IP20 conforming to IEC 60529

Pollution degree

3 conforming to EN/IEC 60947-2

Overvoltage categoryIVTropicalisation

2 conforming to IEC 60068-1

Relative humidity95 % 131 °F (55 °C)Operating altitude6561.68 ft (2000 m)

Ambient air temperature for operation

-22...158 °F (-30...70 °C)

Ambient air temperature for storage

-40...176 °F (-40...80 °C)

Ordering and shipping details Category

99999 - DEFAULT ADD CATEGORY

Discount ScheduleN/ANbr. of units in pkg.1Package weight(Lbs)0ReturnabilityN

Offer Sustainability RoHS (date code: YYWW)

Compliant - since 0629 - Schneider Electric declaration of conformity Electric declaration of conformity

Contractual warranty Warranty period

Product Life Status
2

18 months

End of commercialisation

Schneider-