Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Schneider Electric Multi 9 C60 UL1077 Circuit Breaker 24503 Product Data Sheet

Spec sheet · Schneider

Schneider Electric Multi 9 C60 UL1077 Circuit Breaker 24503 Product Data Sheet

Spec sheet3 pagesPDF 108 KB

All 3 pages are below, each with its text.

What this file really is

The old site listed this file as a spec sheet for the Schneider 24435. The sheet is for catalog number 24503; 24435 is not named.

Download the PDF108 KB

Filed with · 1 model

Also filed with these models on the old site

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Schneider Electric product data sheet for the 24503, a discontinued Multi 9 C60 UL1077 miniature circuit breaker (1P, 4 A, D curve); the site files it under the 24435, which the sheet never names. It lists ratings, breaking capacities, dimensions, terminals, environment and the replacement part.

What it is
24503: Multi 9 C60 UL1077 miniature circuit breaker, 1P, 4 A, D curve, 277 V, 5 kA p. 1
Status
24503: discontinued, replaced by MG24503 p. 1, 3
Rated current
4 A at 77 °F (25 °C) p. 1
UL 1077 breaking capacity
AIR 5 kA at 277 V AC, 10 kA at 240 V AC, 10 kA at 65 V DC p. 1
Trip unit
Thermal-magnetic; magnetic trip 12 x In +/- 20 % AC, 17 x In +/- 20 % DC p. 1, 2
Network
AC or DC, 50/60 Hz p. 1
Dimensions
81 mm high, 18 mm wide, 73 mm deep; 0.11 kg p. 2
Mounting
Clip-on, DIN rail, 2 pitches of 9 mm p. 2
Terminals
Tunnel type, top or bottom, 2.5...25 mm² (AWG 14...AWG 4) rigid wire; strip 14 mm; 2.5 N.m p. 2
Operating temperature
-30...70 °C; storage -40...80 °C p. 2
Durability
20000 cycles mechanical, 10000 cycles electrical p. 2
Controls
Toggle with ON/OFF indication; padlockable p. 2

What this sheet walks you through

  • Finding the replacement for the discontinued 24503 p. 3

Good to know

  • The sheet says it is not meant for deciding whether the product suits a specific application. p. 1

Questions this sheet answers

What replaces the Schneider 24503 breaker?

The sheet names the MG24503 Multi 9 C60 UL1077 breaker, 1P, 4 A, D curve, as its replacement. p. 3

What is the breaking capacity of the 24503 at 277 V?

AIR 5 kA at 277 V AC under UL 1077. p. 1

What wire size fits the 24503 terminals?

Rigid wire from 2.5 to 25 mm² (AWG 14 to AWG 4), stripped 14 mm and tightened to 2.5 N.m. p. 2

The file

Size and text

Pages3
PDF108 KB
TextText from the PDF itself.

Every page · 3

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Schneider Electric Multi 9 C60 UL1077 Circuit Breaker 24503 Product Data Sheet

The text of page 1, from the PDF itself

24503

Product data sheet Characteristics

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications

Multi 9 - C60 UL1077 - MCB - 1P - 4 A - D Curve 277 V - 5 kA

Discontinued Main Range

Multi 9Product nameMulti 9 C60

Product or component type

Miniature circuit-breaker

Device short nameC60 UL1077Device applicationDistributionPoles description1P

Number of protected poles

1[In] rated current4 A at 77 °F (25 °C)Network typeDC ACTrip unit technologyThermal-magneticCurve codeDBreaking capacity

AIR 10 kA at 65 V DC conforming to UL 1077 AIR 10 kA at 65 V DC conforming to CSA C22.2 No 235 Icu 3 kA at 415 V AC conforming to EN/IEC 60947-2 Icu 10 kA at 240 V AC conforming to EN/IEC 60947-2 Icu 3 kA at 415 V AC conforming to GB 14048.2 Icu 10 kA at 240 V AC conforming to GB 14048.2 AIR 5 kA at 277 V AC conforming to UL 1077 AIR 10 kA at 240 V AC conforming to UL 1077 AIR 5 kA at 277 V AC conforming to CSA C22.2 No 235 AIR 10 kA at 240 V AC conforming to CSA C22.2 No 235 Icu 10 kA at 60 V DC conforming to EN/IEC 60947-2 Icu 10 kA at 60 V DC conforming to GB 14048.2

Suitability for isolation

Yes conforming to EN/IEC 60947-2

Complementary Network frequency

50/60 Hz

System Voltage

240 V AC 60 V DC 415 V AC

Magnetic tripping limit

12 x In +/- 20 % ACSep 7, 20181

Page 2 of Schneider Electric Multi 9 C60 UL1077 Circuit Breaker 24503 Product Data Sheet

The text of page 2, from the PDF itself

17 x In +/- 20 % DC Limitation class

3 conforming to EN/IEC 60947-2

[Ui] rated insulation voltage

500 V ACconforming to EN/IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-2

Contact position indicator

YesControl typeToggleLocal signallingON/OFF indicationMounting modeClip-onMounting supportDIN rail9 mm pitches2Height3.19 in (81 mm)Width0.71 in (18 mm)Depth2.87 in (73 mm)Product weight0.24 lb(US) (0.11 kg)ColourGreyMechanical durability20000 cyclesElectrical durability10000 cycles

Provision for padlocking

Padlockable

Connections - terminals

Tunnel type terminal, top or bottom rigid wire(s) 0...0.04 in² (2.5...25 mm²) max (AWG 14...AWG 4)

Wire stripping length

0.55 in (14 mm) top or bottom

Tightening torque

22.12 lbf.in (2.5 N.m) top or bottom

Environment Standards

UL 1077 GB 14048.2 EN/IEC 60947-2 CSA C22.2 No 235

Product certifications

CSA CCC IEC UR

IP degree of protection

IP40 modular enclosure conforming to IEC 60529 IP20 conforming to IEC 60529

Pollution degree

3 conforming to EN/IEC 60947-2

Overvoltage categoryIVTropicalisation

2 conforming to IEC 60068-1

Relative humidity95 % 131 °F (55 °C)Operating altitude6561.68 ft (2000 m)

Ambient air temperature for operation

-22...158 °F (-30...70 °C)

Ambient air temperature for storage

-40...176 °F (-40...80 °C)

Ordering and shipping details Category

99999 - DEFAULT ADD CATEGORY

Discount ScheduleN/ANbr. of units in pkg.1Package weight(Lbs)0ReturnabilityN

Offer Sustainability Sustainable offer status

Green Premium product

Product environmental profile

Available

Product end of life instructions

Need no specific recycling operations

2

Page 3 of Schneider Electric Multi 9 C60 UL1077 Circuit Breaker 24503 Product Data Sheet

The text of page 3, from the PDF itself

Contractual warranty Warranty period

18 months

24503 is replaced by: Miniature circuit breakers MG24503 Multi 9 - C60 UL1077 - MCB - 1P - 4 A - D Curve - 277 V - 5 kA Qty 1 Reason for Substitution: End of life | Substitution date: 01 January 2017

3

More documents · 1

For the same models