Spec sheet · Schneider
Schneider Electric Multi 9 C60 UL1077 Circuit Breaker 24503 Product Data Sheet
Spec sheet3 pagesPDF 108 KB
All 3 pages are below, each with its text.
What this file really is
The old site listed this file as a spec sheet for the Schneider 24435. The sheet is for catalog number 24503; 24435 is not named.
Filed with · 1 model
Also filed with these models on the old site
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Schneider Electric product data sheet for the 24503, a discontinued Multi 9 C60 UL1077 miniature circuit breaker (1P, 4 A, D curve); the site files it under the 24435, which the sheet never names. It lists ratings, breaking capacities, dimensions, terminals, environment and the replacement part.
- What it is
- 24503: Multi 9 C60 UL1077 miniature circuit breaker, 1P, 4 A, D curve, 277 V, 5 kA p. 1
- Status
- 24503: discontinued, replaced by MG24503 p. 1, 3
- Rated current
- 4 A at 77 °F (25 °C) p. 1
- UL 1077 breaking capacity
- AIR 5 kA at 277 V AC, 10 kA at 240 V AC, 10 kA at 65 V DC p. 1
- Trip unit
- Thermal-magnetic; magnetic trip 12 x In +/- 20 % AC, 17 x In +/- 20 % DC p. 1, 2
- Network
- AC or DC, 50/60 Hz p. 1
- Dimensions
- 81 mm high, 18 mm wide, 73 mm deep; 0.11 kg p. 2
- Mounting
- Clip-on, DIN rail, 2 pitches of 9 mm p. 2
- Terminals
- Tunnel type, top or bottom, 2.5...25 mm² (AWG 14...AWG 4) rigid wire; strip 14 mm; 2.5 N.m p. 2
- Operating temperature
- -30...70 °C; storage -40...80 °C p. 2
- Durability
- 20000 cycles mechanical, 10000 cycles electrical p. 2
- Controls
- Toggle with ON/OFF indication; padlockable p. 2
What this sheet walks you through
- Finding the replacement for the discontinued 24503 p. 3
Good to know
- The sheet says it is not meant for deciding whether the product suits a specific application. p. 1
Questions this sheet answers
What replaces the Schneider 24503 breaker?
The sheet names the MG24503 Multi 9 C60 UL1077 breaker, 1P, 4 A, D curve, as its replacement. p. 3
What is the breaking capacity of the 24503 at 277 V?
AIR 5 kA at 277 V AC under UL 1077. p. 1
What wire size fits the 24503 terminals?
Rigid wire from 2.5 to 25 mm² (AWG 14 to AWG 4), stripped 14 mm and tightened to 2.5 N.m. p. 2
The file
Size and text
Every page · 3
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 3
Open in the PDF
The text of page 1, from the PDF itself
24503
Product data sheet Characteristics
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Multi 9 - C60 UL1077 - MCB - 1P - 4 A - D Curve 277 V - 5 kA
Discontinued Main Range
Multi 9Product nameMulti 9 C60
Product or component type
Miniature circuit-breaker
Device short nameC60 UL1077Device applicationDistributionPoles description1P
Number of protected poles
1[In] rated current4 A at 77 °F (25 °C)Network typeDC ACTrip unit technologyThermal-magneticCurve codeDBreaking capacity
AIR 10 kA at 65 V DC conforming to UL 1077 AIR 10 kA at 65 V DC conforming to CSA C22.2 No 235 Icu 3 kA at 415 V AC conforming to EN/IEC 60947-2 Icu 10 kA at 240 V AC conforming to EN/IEC 60947-2 Icu 3 kA at 415 V AC conforming to GB 14048.2 Icu 10 kA at 240 V AC conforming to GB 14048.2 AIR 5 kA at 277 V AC conforming to UL 1077 AIR 10 kA at 240 V AC conforming to UL 1077 AIR 5 kA at 277 V AC conforming to CSA C22.2 No 235 AIR 10 kA at 240 V AC conforming to CSA C22.2 No 235 Icu 10 kA at 60 V DC conforming to EN/IEC 60947-2 Icu 10 kA at 60 V DC conforming to GB 14048.2
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Complementary Network frequency
50/60 Hz
System Voltage
240 V AC 60 V DC 415 V AC
Magnetic tripping limit
12 x In +/- 20 % ACSep 7, 20181
Page2of 3
Open in the PDF
The text of page 2, from the PDF itself
17 x In +/- 20 % DC Limitation class
3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage
500 V ACconforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Contact position indicator
YesControl typeToggleLocal signallingON/OFF indicationMounting modeClip-onMounting supportDIN rail9 mm pitches2Height3.19 in (81 mm)Width0.71 in (18 mm)Depth2.87 in (73 mm)Product weight0.24 lb(US) (0.11 kg)ColourGreyMechanical durability20000 cyclesElectrical durability10000 cycles
Provision for padlocking
Padlockable
Connections - terminals
Tunnel type terminal, top or bottom rigid wire(s) 0...0.04 in² (2.5...25 mm²) max (AWG 14...AWG 4)
Wire stripping length
0.55 in (14 mm) top or bottom
Tightening torque
22.12 lbf.in (2.5 N.m) top or bottom
Environment Standards
UL 1077 GB 14048.2 EN/IEC 60947-2 CSA C22.2 No 235
Product certifications
CSA CCC IEC UR
IP degree of protection
IP40 modular enclosure conforming to IEC 60529 IP20 conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Overvoltage categoryIVTropicalisation
2 conforming to IEC 60068-1
Relative humidity95 % 131 °F (55 °C)Operating altitude6561.68 ft (2000 m)
Ambient air temperature for operation
-22...158 °F (-30...70 °C)
Ambient air temperature for storage
-40...176 °F (-40...80 °C)
Ordering and shipping details Category
99999 - DEFAULT ADD CATEGORY
Discount ScheduleN/ANbr. of units in pkg.1Package weight(Lbs)0ReturnabilityN
Offer Sustainability Sustainable offer status
Green Premium product
Product environmental profile
Available
Product end of life instructions
Need no specific recycling operations
2
Page3of 3
Open in the PDF
The text of page 3, from the PDF itself
Contractual warranty Warranty period
18 months
24503 is replaced by: Miniature circuit breakers MG24503 Multi 9 - C60 UL1077 - MCB - 1P - 4 A - D Curve - 277 V - 5 kA Qty 1 Reason for Substitution: End of life | Substitution date: 01 January 2017
3