The text of a manual · part 10 of 15
Programmable controller Twido Catalog: Connections (continued), pages 45 to 52
Pages 45 to 52 of 76, from Programmable controller Twido Catalog
The original document is the PDF (3.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Schneider ABE 7E16EPN20, Schneider ABE 7E16SPN20, Schneider TWDALM3LT, Telemecanique ABE 7E16SPN22 and Telemecanique ABE 7E16SRM20
Page 45
Presentation (continued), characteristics (continued)
Twido programmable controller 0
0
Communication Communication protocols
ASCII protocol 3
1 4
3 2
7
Link by modem 1 Simple ASCII display 2 Cable TSX PCX 1031 on serial port (Rx/Tx crossing to be made or use cable TSX PCX 1130) 3 Modem for transmitting/receiving data 4 Telephone or radio link 5 Twido compact or modular controller 6 ASCII printer 7 Standard RS 485/RS 232 cable on optional port
5
6
3 4 3 Link by cable 1 Simple ASCII display 2 Standard RS 485 cable or cable TSX PCX 1031 for RS 232 conversion, on serial port 3 Twido compact or modular controller 4 Standard RS 485/RS 232 cable on optional link 5 ASCII printer
1 2 3 4 5
Characteristics Protocol type Flow rate
Kbit/s
Data bits Stop bits Parity Physical layer Connection Compatibility
ASCII 1.2…38.4 Initial value: 19.2 7 or 8 Initial value: 8 1 or 2 Initial value: 1 Without, even or odd Initial value: without RS 485/RS 232 Serial port (RS 485) or optional port (RS 485/RS 232) Compact base controllers TWD LCpA pppp and TWD LCAp 40DRF and modular base controllers TWD LMDA pppp
“Remote link” protocol
1
3 (1)
3 (1)
3 (1)
2 (1) Connection is made either to the serial port, or to the optional port.
“Remote Link” decentralized I/O Each compact or modular base controller can be extended by means of Twido base controllers used either as an I/O extension, or as a local “reflex” controller. v When used as an I/O extension, these base controllers cannot take any I/O extensions. v When used as a local “reflex” controller, these base controllers have their own application program. Internal words are reserved for automatic exchange of information between the base controllers. 1 Base controller 2 RS 485, 3-wire cable on serial port or on optional port 3 Twido base controllers used as I/O extension or as local “reflex” controller
Characteristics Protocol type Flow rate Physical layer Connection Number of Twido modules that can be connected Compatibility
Kbit/s
“Remote link” 38.4 RS 485 Serial port or optional port only. 1 to 7 Compact base controllers TWD LCpA pppp and TWD LCAp 40DRF and modular base controllers TWD LMDA pppp
45
Page 46
References
0
Twido programmable controller
0
532664
Communication
CANopen bus master module and TwidoPort interface module Description
540393
TWD NCO1M
Number of modules per base controller
Max. number External of slaves supply and channels c 24 V CANopen bus master module 1 16 slaves max. for base controllers version ≥ 3.0 16 TPDO (Transmit PDO) and 16 RPDO TWD LCpA 24DRF/LCAp (Receive PDO) 40DRF and TWD LMDA pppp Mounting kit Plate or panel mounting of module TWD NCO1M (sold in lots of 5) Description Characteristics
Reference
TwidoPort interface module 10/100 Mbit/s. Auto MDIX function. RJ45 connector. for all base controllers version ≥ 3.0 Cable TWD XCA RJP03P supplied. Ethernet network cables Fitted with 2 RJ45 connectors Length (1)
TWDNCO1M r
Weight kg 0.100
TWDXMT5
–
Reference 499TWD01100
Weight kg 0.200
490NTW000pp
–
Serial link modules and adapters Compatibility
Modules with integrated serial link adapter (able to take a TWD XCP ODC digital display) Serial interface adapters
Modular base controllers TWD LMDA 20/40Dpp
570732
499 TWD 01100
Description
Modules with integrated serial link adapter
Connection
Physical layer Mini-DIN connector RS 232C RS 485 Screw terminals RS 485
Compact base controllers Mini-DIN connector TWD LCpA 16/24DRF and TWD LCAp 40DRF Screw terminals Built-in display module TWD XCP ODM Modular base controllers Mini-DIN connector TWD LMDA 20/40Dpp Screw terminals
521589
TWD NAC 232D/485D
Reference TWDNOZOD232D r TWDNOZOD485D r TWDNOZOD485T r
Weight kg 0.185 0.185 0.185
RS 232C RS 485 RS 485
TWDNAC232D TWDNAC485D TWDNAC485T
0.010 0.010 0.010
RS 232C RS 485 RS 485
TWDNOZ232D TWDNOZ485D TWDNOZ485T
0.085 0.085 0.085
Built-in display module Description
Application
Reference
Built-in display module
For base controllers TWD LMDA 20/40Dpp Mounted on left-hand TWDXCPODM side of base controller. Enables adjustment and diagnostics of the controller. Can take a serial adapter TWD NAC pppp
Weight kg 0.105
Accessories
570711
TWD NAC 485T
570710
TWD NOZ ppp
TWD XCP ODM
Description
Link from to Serial link connection cables Serial interface adapter or Modbus module serial interface module (RJ45 connector) RS 485 (mini-DIN connector) Programming protocol connection cable (2) supplied with the TwidoPort module Connection cable (2) Cable with RJ45 connector and end with free wires Cable with 8-way Mini-DIN connector and end with free wires Adapter cable for Twido modular base controllers Cable for serial port
Modem connection cable Display connection cable
All Twido controllers All Twido controllers
USB port cable Description
All Twido controllers Application
533234 r Available 3rd quarter 2005 ■ Available 1st quarter 2005 46
Reference
Weight kg
0.3 m 1m 3m 0.3 m
TWDXCARJ003 TWDXCARJ010 TWDXCARJ030 TWDXCARJP03P
– 0.090 0.160 –
All Twido controllers (Mini-DIN connector)
Modbus module (RJ45 connector)
All Twido controllers (Mini-DIN connector) All Twido controllers
Modbus module (RJ45 connector) Modbus module
0.3 m
TWDXCARJP03
–
1m
TWDXCAFJ010
–
All Twido controllers
Modbus module
1m 10 m
TWDXCAFD010 TSXCX100
– –
Twido modular base controllers All Twido controllers
Cable XBT Z978
12 cm
TWDXCAXBTN010
–
Serial port on PC with TwidoSoft software installed Modem Magelis displays XBT Np00 USB port on PC (3)
2.5 m
TSXPCX1031
0.225
2.5 m 2.5 m
TSXPCX1130 XBTZ978
0.240 0.180
2.5 m
TSXPCX3030 Reference
0.210 Weight kg 0.155
Range 10 m (class 2). VW3A8114 ■ Items supplied: b 1 Bluetooth gateway with 1 RJ45 connector, b 1 x 0.1 m length cable with two RJ45 connectors, b 1 x 0.1 m length cable with one RJ45 connector and one mini-DIN connector for TwidoSoft software, b 1 x RJ45/9-way SUB-D adapter. Bluetooth gateway Range 10 m (class 2). Required for a PC not equipped with VW3A8115 ■ 0.300 for non-equipped PC Bluetooth technology. Connection to the USB port on the PC. (1) Replace the pp in the reference with 02: 2 m, 05: 5 m, 12: 12 m, 40: 40 m and 80: 80 m. (2) Cable TWD XCA RJP03P, connected to port 1 on the Twido controller, forces configuration of the port according to the parameters of the Programming protocol. Using cable TWD XCA RJP03, sold separately, allows port 1 of the Twido controller to be used with the parameters described in the application configuration. (3) PC with TwidoSoft software installed and running under Windows 2000 or XP operating system only. Bluetooth gateway
VW3 A8114
Length
Page 47
Twido programmable controller
Dimensions, connections
0
0
Communication
Dimensions 2.91 (74)
2.75 (70)
0.57 (14.6)
0.88 (22.5)
2.75 (70)
1.17(4.5)
3.54 (90)
1.16 (29.7)
3.54 (90)
0.14 (3.8)
Module 499 TWD 01100
3.54 (90)
Module TWD NCO1M
Dual Dimensions inches (mm)
Modules TWD NOZ ppp and TWD XCP ODM 2.75 (70)
a
0.54 (13.9)
a 0.88” (22.50) 1.49” (38)
TWD NOZ pppp TWD XCP ODM
3.54 (90)
0.17 (4.5)
Connections Serial link RS 485
Optional link RS 485D
RS 232D
8
7
6
8
7
6
8
7
5
4
3
5
4
3
5
4
2
1
2
1
2
RS 485T
6 3
A
B
SG
1
TWD LCpA pppp TWD NAC 485D TWD NAC 232D TWD NAC 485T TWD LCAp 40DRF TWD NOZ 485D TWD NOZ 232D TWD NOZ 485T TWD LMDA pppp 1 A D1 (A +) D1 (A +) RTS D1 (A +) 2 B D0 (B -) D0 (B -) DTR D0 (B -) 3 SG 0 V NPC NC TXD 4 /DE NC RXD 5 /DPT NC DSR 6 NPC NC 0V 7 0V 0V 0V 8 5 V (180 mA) 5 V (180 mA) 5 V (180 mA) NC: not connected NPC: do not connect /DPT: 1 = master. If not connected, the PUNIT protocol is used for communication with PCs (at state 1, 19 200 bauds, without parity). If connected to 0 V, the communication parameters are those configured by the TwidoSoft software.
47
Page 48
Connection interfaces
Selection guide
0
Advantys, Telefast® pre-wired system for Twido Connection sub-bases
Applications
Connection sub-bases for discrete inputs and outputs
Compatibility
Twido modular base controllers equipped with HE 10 connectors
Relay amplification
–
Control voltage c 24 V
Output voltage c 24 V c 24 V (solid state) c 5…30 V, a 250 V (electromechanical)
5…7 mA 0.3 A
5…7 mA 2 A (solid state) 3 A (electromechanical)
Electromechanical and solid state, fixed
Current per channel Input Output
Modularity
20 (12 inputs/8 outputs)
Type of I/O v 12 inputs (1 common/ 12 channels) v 8 outputs (1 common/ 8 channels)
v 12 inputs (1 common/ 12 channels) v 8 outputs with fuse protection (1 common/ 8 channels)
v 12 inputs (1 common/12 channels) v 2 solid state outputs (1 common/2 channels) v 6 relay outputs (electromechanical) 1 N/O (1 common/6 channels)
LED indication
Number of terminals per channel
2 3 (with optional snap-on terminal block)
Connection to Twido programmable controller
HE 10 connector, 26-way
Type of terminal
Fixed screw terminal block
Interface type
ABE 7B20MPN20
ABE 7B20MPN22
ABE 7B20MRM20
Pages
58
58
58
48
Page 49
0
Connection sub-bases for discrete inputs
Connection sub-bases for discrete outputs
Twido I/O modules equipped with HE 10 connectors
–
Electromechanical, fixed c 24 V c 24 V c 5…30 V, a 250 V (electromechanical)
5 mA –
– 0.1 A
– 3A
16 inputs
16 outputs v 16 inputs (1 common/16 channels)
v 16 outputs (1 common/16 channels)
v 16 outputs with fuse protection LED indication v 16 relay outputs (electromechanical) 1 N/O (1 common/4 channels)
ABE 7E16EPN20
ABE 7E16SPN20
ABE 7E16SPN22
ABE 7E16SRM20
58
58
58
58
2 3 (with optional snap-on terminal block)
HE 10 connector, 20-way
Fixed screw terminal block
49
Page 50
Connection interfaces
Presentation
0
Advantys, Telefast® pre-wired system for Twido I/O connection sub-bases
Presentation Relay and connection functions, with or without polarity distribution, significantly reduce wiring time and eliminate the risk of error. The Advantys Telefast pre-wired system allows fast, reliable and economical remote connection of I/O modules (c 24 V discrete) to operative parts, partly eliminating the single-wire connection and intermediate terminal blocks. The Telefast system can only be connected to Twido modules equipped with HE 10 type connectors. It consists of connecting cables and interface sub-bases. The Telefast range is suitable for all types of connection found in control system devices: v I/O located in the PLC cabinet v I/O located directly on the machine or in auxiliary enclosures All the I/O connection sub-bases comprise output terminals on 2 rows : b 1st row: connection of the signal b 2nd row: connection of its common v c 24 V for the inputs v 0 V for the outputs A 3rd row of optional terminals ABE 7BVpp may be added for connection of another common. These I/O sub-bases are available in different configurations: Sub-bases for Twido modular base controllers b ABE 7B20MPN20: sub-base with 12 inputs + 8 passive outputs b ABE 7B20MPN22: sub-base with 12 inputs + 8 passive outputs v individual fuse protection for each output (0.315 A) v LED indication v blade disconnector for the 0 V common b ABE 7B20MRM20: sub-base with 12 inputs + 8 outputs with soldered relays v 2 A solid state relay (1 x 4 A common/2 channels) on 2 outputs v electromechanical relays (1N/O c 24 V/a 250 V, 3 A) on 6 outputs for adaptation of the current or voltage signal (1 x 10 A common/6 channels) Sub-bases for Twido extension modules b ABE 7E16EPN20: sub-base with 16 passive inputs b ABE 7E16SPN20: sub-base with 16 passive outputs b ABE 7E16SPN22: sub-base with 16 passive outputs v individual fuse protection for each output (0.315 A) v LED indication v blade disconnector for breaking the 0 V common b ABE 7E16SRM20: sub-base with 16 soldered relay outputs v electromechanical relays (1N/O c 24 V/a 250 V, 3 A) on 16 outputs for adapting the current or voltage signal (1 x 5 A common/4 channels) Optional terminal blocks b ABE 7BV20TB v 12 shunted screw terminals for the input common v 8 shunted screw terminals for the output common b ABE 7BV20 v 20 shunted screw terminals for connection of a single common
Compatibility: page 53
50
Characteristics: pages 54 and 55
References, dimensions: pages 58 and 59
Curves: pages 56 and 57
Schemes: pages 60 to 63
Page 51
Connection interfaces
Description
0
Advantys, Telefast® pre-wired system for Twido I/O connection sub-bases
Description 2
4 5
6
Connection sub-bases ABE 7B20Mpppp, ABE 7E16SRM20 and ABE 7E16SPN22
1
1 HE 10 connector (20-way for ABE 7E16ppppp, 26-way for ABE 7B20ppppp) 2 Fuse for the c 24 V supply circuit 3 Rail mounting 4 LED for channel indication (only on ABE 7B20MPN22 and ABE 7E16SPN22) 5 c 24 V power supply terminal block 7 6 Blade disconnector on c 0 V (only on ABE 7B20MPN22 and ABE 7E16SPN22) 7 Legend holder cover: customer marking on outside and sub-base wiring scheme on inside, providing access to fuses per channel (only on ABE 7B20MPN22 and ABE 7E16SPN22) 8 8 Test point for Ø 2.3 mm plug 9 Upper terminal block for connection of signals 10 Lower terminal block for connection of commons 11 Optional snap-on terminal block with 20 screw terminals
3
11
4
10
2
9
Connection sub-bases ABE 7E16EPN20 and ABE 7E16SPN20
1
5
3 8
Compatibility: page 53
7
1 HE 10 connector, 20-way 2 Fuse for the c 24 V supply circuit 3 Rail mounting 4 c 24 V power supply terminal block 5 Test point for Ø 2.3 mm plug 6 Upper terminal block for connection of signals 7 Lower terminal block for connection of commons 8 Optional snap-on terminal block with 20 screw terminals
6
Characteristics: pages 54 and 55
References, dimensions: pages 58 and 59
Curves: pages 56 and 57
Schemes: pages 60 to 63
51
Page 52
Connection interfaces
Presentation
0
Advantys, Telefast® pre-wired system for Twido Pre-wired solutions
1
2
3
5
4
4
7
6
Compatibility: page 53
52
Characteristics: pages 54 and 55
References, dimensions: pages 58 and 59
Curves: pages 56 and 57
Schemes: pages 60 to 63