Programmable controller Twido Catalog: Characteristics (continued)

Pages 15 to 19 of 76, from Programmable controller Twido Catalog

The original document is the PDF (3.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Schneider ABE 7E16EPN20, Schneider ABE 7E16SPN20, Schneider TWDALM3LT, Telemecanique ABE 7E16SPN22 and Telemecanique ABE 7E16SRM20

Page 15

Characteristics (continued)

0

Twido programmable controller

0

Modular base controllers c input characteristics Base controller type Number of input channels Rated input voltage Commons Input voltage range Rated input current Input impedance Filter time

TWD V V

At state 1 At state 0

Isolation

LMDA 20DTK LMDA 20DUK LMDA 20DRT LMDA 40DTK LMDA 40DUK 12 24 c 24 sink/source (positive or negative logic) 1 2 c 20.4...26.4 5 mA for I0.0 and 10.1, 10.6 and I0.7, 7 mA for other inputs I0.i 5.7 kΩ for I0.0 and I0.1, 10.6 and 10.7, 4.7 kΩ for other inputs I0.i 35 µs for I0.0 and I0.1, I0.6 and I0.7, 40 µs for other inputs I0.i 45 µs for I0.0 and I0.1, I0.6 and I0.7, 150 µs other inputs I0.i No isolation between channels, isolation with internal logic by photocouplers

Transistor output characteristics Number of output channels Output logic (1) Commons Nominal output values

Voltage Current Output voltage range Voltage Current per channel Current per common Response time At state 1 At state 0 Residual voltage (voltage at state 1) Maximum inrush current Leakage current Overvoltage protection Maximum power of filament lamp Isolation

V A V A A

V A mA V W

8 2 16 Source Sink Source Sink 1 2 24 0.3 20.4…28.8 0.36 1 5 µs for Q 0.0 and Q 0.1, 300 µs for other outputs Q 0.i 5 µs for Q 0.0 and Q 0.1, 300 µs for other outputs Q 0.i 1 max 1 0.1 39 8 No isolation between channels, isolation with internal logic by photocouplers

Relay output characteristics Number of output channels Output currents

A

– –

Minimum switching load mA

– – – –

Contact resistance (when new) Loads (resistive, inductive)

mΩ A

– – rms insulation voltage

V

– mA mA mA

– – – s/ month days

+ 30 at 25 °C

Commons

Consumption for all the outputs

Common 1 Common 2 Common 3

At state 1 At state 0 c5V c 24 V c5V

6 2 per channel, 8 per common 3 N/O contacts 2 N/O contacts 1 N/O contact 0.1/0.1 c V (reference value) 30 max 2/a 240 V, 2/c 30 V (2) a1 500 for 1 minute 30 40 5

– – – – – –

– – – – – –

Real-time clock cartridge (optional) Precision Autonomy Battery type Charging time Life h years

Approximately 30 at 25 °C with fully charged battery Lithium battery, not interchangeable Approximately 10 to charge from 0...90 % of the full charge 10

Memory cartridge (optional) Cartridge type Memory type Memory capacity Save/transfer program and internal words Program size increase

Ko

TWD XCP MFK32 EEPROM 32 All modular base controllers –

TWD XCP MFK64

64 Base controllers TWD LMDA 20DRT/40DpK 6000 instructions with base controllers TWD LMDA 20DRT/40DpK (1) Source output: positive logic, sink output: negative logic. (2) 2A/a 240 V or 2A/c 30 V (with 1800 operations/hour max): - electrical life: minimum 100 000 operations, - mechanical life: minimum 20 x 106 operations.

15

Page 16

References

0

Twido programmable controller

0

Modular base controllers

References Sink/source inputs

Outputs

No. of I/O expansion modules

Program memory

Reference

Weight kg

4 4 7

3000 instructions TWDLMDA20DTK (2) 3000 instructions TWDLMDA20DUK 3000 instructions (1) TWDLMDA20DRT

0.140 0.140 0.185

7 7

3000 instructions (1) TWDLMDA40DTK (2) 3000 instructions (1) TWDLMDA40DUK

0.180 0.180

Modular base controllers, 20 I/O 12 c 24 V I

TWD LMDA 20DTK/20DUK

TWD LMDA 40DTK/40DUK

8 O, source transistor 8 O, sink transistor 6 O, relay 2 O, source transistor

Modular base controllers, 40 I/O 24 c 24 V I

16 O, source transistor 16 O, sink transistor

Separate components Description

Application

32 Kb memory cartridge

TWDXCPMFK32

TWDXCPMFK64

0.005

Real-time clock cartridge Serial interface module Digital display module

For all base controllers EEPROM Application backup Program transfer For TWD LMDA 20DRT/40DpK EEPROM base controllers Memory extension Application backup Program transfer Date-stamping, RTC based programming – See page 46 – See page 46 –

Weight kg 0.005

TWDXCPRTC TWDNOZpppp TWDXCPODM

0.005 – –

Mounting kit (Sold in packs of 5)

For fitting modular base controllers or extensions on a mounting plate or panel

TWDXMT5

–

TWDFTB2T13 TWDFTB2T16 TWDXCA2A10M See page 58

– – – –

64 Kb memory cartridge (3)

TWD LMDA 20DRT

TWD XCP MFK pp

Type

Reference

–

Replacement parts Screw terminal blocks (Sold in packs of 2) Analog input cable Pre-formed cables

Controller TWD LMDA 20DRT, 13 contacts – Controller TWD LMDA 20DRT, 16 contacts – – For built-in analog input. Length 1 m – –

Magelis compact displays Description

Protocol

Compact display, 2 lines of Uni-Telway, 20 characters Modbus (alphanumeric display) Compact displays, 4 lines Uni-Telway, Modbus of 20 characters (matrix display) XBT N401 Display connection cable Uni-Telway, Modbus

Compatible with PLC types Twido, Nano, TSX Micro, Premium Twido, Nano, TSX Micro, Premium Twido (4), Nano, TSX Micro, Premium, TSX series 7, Momentum, Quantum Other Modbus slave modules Twido, Nano, TSX Micro, Premium

Supply Reference voltage c 5 V by XBTN200 terminal port on PLC XBTN400 c 5 V by terminal port on PLC c 24 V XBTN401 external source

Weight kg 0.360

0.360

0.360

–

XBTZ978

0.180

Weight

Phaseo regulated switch mode power supplies Description

Single-phase regulated switch mode power supplies (5) ABL 7CEMpppp

ASI ABLM3024

16

Input voltage 47…63 Hz V a 100…240 single-phase wide range c 110…220 (6) a 100…240 single-phase wide range

Output voltage cV 24

24

Rated power W 15

Rated current A 0.6

Auto-protect reset

Reference

Auto

ABL7CEM24006 kg 0.180

30

1.2

Auto

ABL7CEM24012

0.220

48 72 120 2 x 72

2 3 5 2.4 + 3

Auto Auto Auto Auto

ABL7RE2402 ABL7RE2403 ABL7RE2405 ASIABLM3024

0.520 0.520 1.000 1.300

Regulated switch mode a 100…240 30 + 24 power supplies for the single-phase AS-Interface cabling wide range system (7) (1) 6000 instructions with memory extension cartridge TWD XCP MFK64 (2) Connection by HE 10 type connector, allowing use of the Telefast pre-wired system (see page 58). (3) Memory extension with base controllers TWD LMDA 20DRT/40DpK. (4) Connection via built-in port or via optional serial port on Twido programmable controllers. (5) These products do not conform to standard EN 61000-3-2. (6) Compatible input voltage, not indicated on the product. (7) Without ground fault detection.

Page 17

Twido programmable controller

Dimensions, connections

0

0

Modular base controllers

Dimensions TWD LMDA 20DpK/20DRT/40DpK b

Installation rules a 2.75" (70 mm)

0.78" (20 mm) 3.54" (90 mm)

3.14" (80 mm)

0.17" (4.5 mm) a

0.78" (20 mm)

3.14" (80 mm)

3.14" (80 mm)

0.78" (20 mm) 0.78" (20 mm) Dual Dimensions inches (mm)

b

TWD LMDA 20DTK/DUK 1.39" (35.4) 0 (excluding connector) TWD LMDA 20DRT 1.87" (47.5) 14.6 TWD LMDA 40DTK/DUK 1.87" (47.5) 0 (excluding connector)

Important: b Horizontal or flat mounting not permissible. b Avoid placing devices which generate heat (transformers, power supplies, power contactors...) beneath the controller.

Connections TWD LMDA 20DTK

(1) (2)

TWD LMDA 20DUK

TWD LMDA 20DRT

(2) (1) (1) (2)

v The COM (+) and COM (-) terminals are interconnected internally. v The COM and COM (+), COM and COM (-) terminals are independent. v The -V and +V terminals are interconnected internally. TWD LMDA 40DTK TWD LMDA 40DUK

(1) (2)

(2) (1)

(1) (2)

(2) (1)

v Connectors CN1 and CN2 are independent. v The COM (+) and COM (-) terminals are interconnected internally. v The COM and COM (+), COM and COM (-) terminals are independent. v The -V and +V terminals are interconnected internally.

v Output channels 0 and 1 are of the source transistor type. Output channels 2 to 7 are of the relay type. v The COM terminals are independent.

(1) Supply connection for sink inputs (positive logic). (2) Supply connection for source inputs (negative logic).

17

Page 18

Selection guide

0

Twido programmable controller Discrete I/O modules

Applications

Discrete Input modules

Type

8 c 24 V inputs (TWD DDI 8DT)

16 c 24 V inputs

32 c 24 V inputs

8 a 120 V inputs (TWD DAI 8DT) Connection

Inputs

By removable screw terminal block

Input current c 20.4...28.8 V (TWD DDI 8DT) a 85...132 V (TWD DAI 8DT) 15 mA per point 7 mA per point

Input logic

Sink (1)

Commons

1 common point (TWD DDI 8DT) 2 common points (TWD DAI 8DT)

Voltage ranges

Response time v Energization v De-energization

Outputs

By HE 10 type connector Allows use of the Telefast pre-wired system

5 mA per point

Sink/source (1) 2 common points

4 ms (TWD DDI 8DT), 25 ms (TWD DAI 8DT) 4 ms (TWD DDI 8DT), 30 ms (TWD DAI 8DT)

Output types Voltage range Commons Output current v Per output v Per group of channels

Isolation

Between channels: common point, Between bus and channels: by photocoupler

I/O module type

TWD DpI 8DT

Page

24 (1) Sink input: positive logic, source input: negative logic.

18

TWD DDI 16DT TWD DDI 16DK TWD DDI 32DK

0

Page 19

0

Discrete mixed I/O modules

0

Master module for AS-Interface cabling system

4 c 24 V inputs/4 relay outputs

16 c 24 V inputs/8 relay outputs

By removable screw terminal block

By non-removable spring terminal block b For controller versions ≥ 2.0 b Management of slave modules: v Discrete: maximum of 62 slaves arranged in 2 banks, A/B, of 31 addresses each v Analog: maximum of 7 slaves in bank A b The AS-Interface M3 profile supports analog profile 7.3 (7 slaves), but does not support analog profile S-7.4 c 20.4...28.8 V 7 mA per point Sink/source 1 common point

4 ms 4 ms

1 N/O contact a 240 V, c 30 V 1 common point

2 common points

2 A (Ith) 7 A (Ith)

Between input channels: common point, between output channels: common point Between bus and channels: by photocoupler

TWD DMM 8DRT

24

TWD DMM 24DRF

TWD NOI 10M3

39

19