The text of a manual · part 5 of 15
Programmable controller Twido Catalog: Selection guide (continued)
Pages 20 to 24 of 76, from Programmable controller Twido Catalog
The original document is the PDF (3.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Schneider ABE 7E16EPN20, Schneider ABE 7E16SPN20, Schneider TWDALM3LT, Telemecanique ABE 7E16SPN22 and Telemecanique ABE 7E16SRM20
Page 20
Selection guide (continued)
0
Twido programmable controller
0
Discrete I/O modules
Applications
8/16 output modules with removable screw terminal block
Type
8 c 24 V transistor outputs
Connection
By removable screw terminal block
Inputs
8 relay outputs
16 relay outputs
Voltage range Input current Input logic Commons Response time v Energization v De-energization
Outputs
Output types
Transistor
Relay with 1 N/O contact
Voltage range c 20.4...28.8 V a 240 V, c 30 V
Logic (1)
Sink
Commons
1 common point
2 common points
Output current v Per output v Per group of channels
0.3 A nominal 3 A at 28.8 V
2 A max. 7 A max.
Isolation
Between channels: common point Between bus and channels: by photocoupler.
Between channels: common point. Between bus and channels: a 1500 V for 1 minute.
Output module type
TWD DDO 8UT TWD DDO 8TT TWD DRA 8RT TWD DRA 16RT
Page
24 (1) Source output: positive logic, sink output: negative logic.
20
Source
–
8 A max.
Page 21
0
0
16/32 output modules with HE 10 type connectors
16 c 24 V transistor outputs
16 c 24 V transistor outputs
32 c 24 V transistor outputs
32 c 24 V transistor outputs
By HE 10 type connector
By HE 10 type connector Allows use of the Telefast pre-wired system
By HE 10 type connector
By HE 10 type connector Allows use of the Telefast pre-wired system
Source
Sink
Source
Transistor c 20.4...28.8 V Sink 1 common point
2 common points
0.1 A nominal 1 A at 28.8 V
Between channels: common point. Between bus and channels: by photocoupler.
TWD DDO 16UK
TWD DDO 16TK
TWD DDO 32UK
TWD DDO 32TK
24
21
Page 22
Presentation, description
Twido programmable controller 0
Discrete I/O modules
Presentation The range of Twido I/O modules includes input modules, output modules and mixed input/output modules. With the 15 I/O modules offered, in addition to the I/O integrated in 24 I/O compact base controllers and modular base controllers, configurations can be adapted to best suit application requirements, so optimizing costs. The following discrete I/O modules are available: b 1 a 120 V discrete input module, 8 channels, fitted with a removable screw terminal block b 4 c 24 V discrete input modules comprising an 8-channel module, two 16-channel modules and a 32-channel module, equipped with either removable screw terminal blocks or HE 10 type connector, depending on the model. These modules can be either “sink or source”. b 8 discrete output modules comprising two output modules with 8 and 16 relay outputs, three output modules with 8, 16 or 32-channel “sink” transistor outputs and three output modules with 8, 16 or 32-channel “source” transistor outputs, equipped with either removable screw terminal blocks or HE 10 type connector, depending on the model b 2 discrete mixed input and output modules, comprising one 4-channel input/ 4-channel relay output module with removable screw terminal block and one 16-channel input/8-channel relay output module with non-removable spring terminal block The narrow width of these I/O modules (17.5 mm, 23.5 mm, 29.7 mm or 39.1 mm) makes it possible to build Twido configurations of up to 264 I/O with a minimal overall size of L 10.0” (255.4 mm) x H 3.54” (90 mm) x D 3.2” (81.3 mm). All these discrete I/O modules and the analog I/O modules are connected to the base controller by stacking them on a 5 rail, starting from the right-hand side panel of the base controller, according to the following rules: b For 24 I/O compact base controllers TWD LCpA 24DRF: 4 modules max. (see characteristics page 6 b For 40 I/O compact base controllers TWD LCAp 40DRF: 7 modules max. (see characteristics page 6) b For 20 I/O modular base controllers TWD LMDA 20DpK: 4 modules max. (see characteristics page 15) b For 20 and 40 I/O base controllers TWD LMDA 20DRT/40DpK: 7 modules max. (see characteristics page 15) All the discrete I/O modules are electrically isolated with the use of a photocoupler between the internal electronic circuit and the input/output channels.
Description Twido discrete I/O modules comprise:
4 1
1 An extension connector for electrical connection to the previous module (1) 2 One or two blocks for displaying the channels and module diagnostics 3 One or two connection components of varying type, depending on the model: b removable screw terminal block (1 or 2) for modules whose reference ends in T b HE 10 type connector (1 or 2) for modules whose reference ends in K b non-removable spring terminal block for module TWD DMM 24DRF 4 Latching mechanism for attachment to the previous module
2
3
Module with removable screw terminal block
Module with HE 10 type connector
These modules are mounted on a symmetrical 5 rail. Mounting kit TWD XMT 5 (supplied in lots of 5) allows plate or panel mounting. For modules with removable screw terminal block, the terminal blocks are supplied with the module. (1) A connector on the right-hand side panel ensures continuity of the electrical link with the next I/O module.
22
0
Page 23
Characteristics
0
Twido programmable controller
0
Discrete I/O modules
General characteristics Temperature Relative humidity Degree of protection Altitude Vibration resistance
°C
Mounted on 5 rail Plate or panel mounted (using mounting kit TWD XMT 5)
Shock resistance m Hz m/s2 Hz m/s2 m/s2
Operation: 0…+ 55. Storage: - 25…+ 70. 30 to 95%, without condensation IP 20 Operation: 0…2000. Storage: 0…3000. 10…57, amplitude 0.075 mm, acceleration 57…150 Hz 9.8 (1 gn) 2…25, amplitude 1.6 mm, acceleration 25…100 Hz 39.2 (4 gn) 147 (15 gn) for 11 ms
Characteristics of c input channels Module type Number of input channels Rated input voltage Connection
TWD V
Commons Input voltage range
Rated input current Input impedance Filter time Isolation Internal consumption for all inputs
V mA kΩ ms ms
At state 1 At state 0 At state 1 At state 0 c5V c 24 V c5V mA mA mA
DAI 8DT DDI 8DT DDI 16DT DDI 16DK DDI 32DK DMM 8DRT DMM 24DRF 8 8 16 16 32 4 16 a 120 V c 24 sink/source Removable screw terminal block HE 10 type connector Removable Spring screw terminal terminal block block 2 1 2 1 a c 20.4...28.8 85…132 V 7.5 7 5 7 11 3.4 4.4 3.4 25 8 30 8 No isolation between channels, isolation with internal logic by photocouplers 55 25 40 35 65 25 (1) 65 (1) 0 20 (1) 45 (1) 25 5 10 5 (1) 10 (1)
Characteristics of transistor output modules Module type Number of output channels Output logic (2) Connection
TWD
Commons Nominal output values
Voltage Current Output voltage range Voltage Current per channel Current per common Response time At state 1 At state 0 Residual voltage (voltage at state 1) Maximum inrush current Leakage current Overvoltage protection Maximum power of filament lamp Isolation Consumption At state 1 c5V for all the outputs c 24 V At state 0 c5V
V A V A A µs µs V A mA V W mA mA mA
DDO 8UT DDO 8TT DDO 16UK DDO 16TK DDO 32UK DDO 32TK 8 16 32 Sink Source Sink Source Sink Source Removable screw terminal HE 10 type connector block 1 2 24 0.3 0.1 20.4…28.8 0.36 0.12 3 1 300 300 1 max 1 0.1 39 8 No isolation between channels, isolation with internal logic by photocouplers 10 10 20 20 40 70 5 5 10
Characteristics of relay output channels Module type Number of output channels Output currents
TWD Current per channel Current per common
Minimum switching load Contact resistance (when new) Loads (resistive, inductive)
rms insulation voltage Consumption for all the outputs
At state 1 At state 0 c5V c 24 V c5V
A A mA mΩ A
V mA mA mA
DRA 8RT DRA 16RT DMM 8DRT DMM 24DRF 8 N/O contacts 16 N/O contacts 4 N/O contacts 8 N/O contacts 2 7 8 7 0.1/0.1 c V (reference value) 30 max 2A/a 240 V or 2A/c 30 V (with 1800 operations/hour max): - electrical life: minimum 100 000 operations - mechanical life: minimum 20 x 106 operations a1 500 for 1 minute 30 45 See values above (input channels) 40 75 See values above (input channels) 5 5 See values above (input channels) (1) Consumption values are indicated for all inputs/outputs at state 0 or at state 1. (2) Source output: positive logic, sink output: negative logic.
23
Page 24
Twido programmable controller
References 0
0
Discrete I/O modules
References These discrete I/O modules are mounted on symmetrical 5 rails to the right of the Twido base controller. The maximum number of discrete and/or analog I/O modules which may be mounted depends on the type of base controller: Type of TWD base Number of modules
LCpA 10DRF 0
LCpA 16DRF 0
LCpA 24DRF 4
LCAp 40DRF 7
LMDA 20DpK 4
LMDA 20DRT 7
LMDA 40DpK 7
Discrete input modules
TWD DDI 8DT
Input voltage
No. of channels c 24 V sink/source
8
No. of common point 1
16
1
TWD DDI 32DK a 120 V
32
2
8
2
Connection
Reference
Removable TWDDDI8DT screw terminal block (supplied) Removable TWDDDI16DT screw terminal block (supplied) HE 10 type TWDDDI16DK (1) connector HE 10 type TWDDDI32DK (1) connector Removable TWDDAI8DT screw terminal block (supplied)
Weight kg 0.085
0.100
0.065 0.100 0.081
Discrete output modules
TWD DDO 8pT/DRA 8RT
Type of output
No. of channels
Transistor c 24 V/0.3 A
8, sink
No. of common point 1
8, source
1
16, sink
1
16, source
1
32, sink
2
32, source
2
8 (N/O contact)
2
16 (N/O contact)
2
TWD DDO 16pK Transistor c 24 V/0.1 A
TWD DDO 32pK
TWD DRA 16RT
Relay 2 A (Ith) a 230 V/c 30 V
Connection
Reference
Removable TWDDDO8UT screw terminal block (supplied) TWDDDO8TT Removable screw terminal block (supplied) HE 10 type connector HE 10 type connector HE 10 type connector HE 10 type connector
Weight kg 0.085
0.085
TWDDDO16UK
0.070
TWDDDO16TK (1)
0.070
TWDDDO32UK
0.105
TWDDDO32TK (1)
0.105
Removable TWDDRA8RT screw terminal block (supplied) Removable TWDDRA16RT screw terminal block (supplied)
0.110
0.145
Discrete mixed input/output modules No. of No. and I/O type of inputs 8 4 I, c 24 V sink/source TWD DDM 8DRT
No. and type of outputs 4 O, relay (N/O contact) 2 A (Ith)
No. of common point Inputs: 1 common Outputs: 1 common
16 I, 8 O, relay c 24 V (N/O sink/source contact) 2 A (Ith)
Inputs: 1 common Outputs: 2 commons
Connection
Weight kg
Removable TWDDMM8DRT screw terminal block (supplied)
0.095
Non-removable TWDDMM24DRF spring terminal block
0.140
TWD DDM 24DRF 24
(1) Module allowing use of the Telefast pre-wired system.
24
Reference