Page 28

Connections (continued)

0

Twido programmable controller Discrete I/O modules

Transistor output modules TWD DDO 8UT

TWD DDO 8TT Fu

Fu

TWD DDO 16UK Fu

TWD DDO 16TK Fu

TWD DDO 32UK Fu

Fu

Fu

28

Fu

TWD DDO 32TK

Fu

Terminals: v COM (-) are linked internally. v COM0 (-) are linked internally. v COM1 (-) are linked internally. v + V are linked internally. v + V0 are linked internally. v + V1 are linked internally.

Fu

Fu

Fu

Fu

Fu

Terminals: v COM (+) are linked internally. v COM0 (+) are linked internally. v COM1 (+) are linked internally. v - V are linked internally. v - V0 are linked internally. v - V1 are linked internally.

0

Page 29

Connections (continued)

0

Twido programmable controller

0

Discrete I/O modules

Relay output modules TWD DRA 8RT

TWD DRA 16RT Fu

Fu

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(3)

(4)

(3)

(4)

Terminals: v COM0 are linked internally. v COM1 are linked internally. v COM0 and COM1 are independent (1) Sink output (negative logic) (2) Source output (positive logic)

Mixed input/output modules TWD DMM 8DRT

TWD DMM 24DRT Fu

(1) (2)

Fu

(3)

v The COM (+) terminals are linked internally

(4)

(1) (2)

v Terminals COM0, COM1 and COM2 are independent v Terminals - V are linked internally.

(1) Source input (negative logic) (2) Sink input (positive logic) (3) Sink output (negative logic) (4) Source output (positive logic)

29

Page 30

Selection guide

0

Twido programmable controller Analog I/O modules

Applications

Analog input modules

Number of I/O

2 inputs

4 inputs

8 inputs

8 inputs

Type

Voltage/current

Voltage/current Temperature

Voltage/current

PTC/NTC

Connection

Removable screw terminal block

0...10 V (non differential) 0...20 mA (differential)

–

Inputs

Outputs

Range

0...10 V (non differential) 4...20 mA (differential)

Resolution

10 bits (1024 points)

Acquisition period

32 ms + 1 controller cycle time

0...10 V (non differential) 0...20 mA (differential) Pt 100/1000 NI 100/1000 12 bits (4096 points)

10 bits (1024 points)

160 ms

Range

Resolution

Transfer time

External supply c 24 V external power supply to sensors/pre-actuators (voltage range 20.4…28.8 V)

Isolation

Isolation between channels and ground: by photocoupler

Analog I/O module type

TWD AMI 2HT TWD AMI 4LT

Pages

35

30

TWD AMI 8HT TWD ARI 8HT

0

Page 31

0

Analog output modules

0

Analog mixed I/O modules

Master module for AS-Interface cabling system b For controller versions ≥ 2.0 b Management of slave modules: v Discrete: maximum of 62 slaves arranged in 2 banks, A/B, of 31 addresses each v Analog: maximum of 7 slaves in bank A b The AS-Interface M3 profile supports analog profile 7.3 (7 slaves), but does not support analog profile S-7.4.

1 output

2 outputs

2 inputs/1 output

Voltage/current

Voltage

Voltage/current

Thermocouple/temperature probe inputs Voltage/current output

0...10 V (non differential) 4...20 mA (differential)

Thermocouple type K, J and T Pt100 3-wire temperature probe

Removable screw terminal block

12 bits (4096 points)

32 ms + 1 controller cycle time

0...10 V 4...20 mA

± 10 V

0...10 V 4...20 mA

12 bits (4096 points)

11 bits + sign (2048 points)

12 bits (4096 points)

20 ms + 1 controller cycle time

0.3 ms + 1 controller cycle time

20 ms + 1 controller cycle time

TWD AMO 1HT

TWD AVO 2HT

TWD AMM 3HT

35

100 ms + 1 controller cycle time

TWD ALM 3LT

TWD NOI 10M3

39

31

Page 32

Twido programmable controller

Presentation, description

Analog I/O modules

Presentation Twido analog I/O expansion modules enable the acquisition of various analog values encountered in industrial applications. Analog output modules are used to control the pre-actuators in devices such as variable speed drives, valves and applications that require process control. The output current or voltage is proportional to the numerical value defined by the user program. When the Twido controller stops, the outputs can be configured with fallback (reset to the lowest scale value or hold the last value received). This function, when set to 'hold', is useful when debugging the application or when a fault occurs, in order not to disturb the process being controlled. The 8 following analog I/O modules are available: b One module with 2 inputs: 0…10 V, 4…20 mA b One module with 4 inputs: 0…10 V, 0…20 mA, Pt 100/1000, Ni100/1000 range 122 ... 302 °F (50...150 °C) b One module with 8 inputs: 0…10 V, 0…20 mA b One module with 8 inputs: PTC/NTC b One module with 1 output: 0…10 V, 4…20 mA b One module with 2 outputs: ± 10 V b One mixed module with 2 inputs: 0…10 V, 4…20 mA and 1 output: 0…10 V, 4…20 mA b One mixed module with 2 thermocouple or temperature probe inputs and one 0…10 V, 4…20 mA output Twido analog extension modules offer a resolution of 10 bits, 11 bits + sign and 12 bits, with connection by removable screw terminal block. An external c 24 V power supply is required for each analog module. Like discrete I/O modules, analog I/O modules are connected to the base controller by stacking them on a 7 rail, starting from the right-hand side panel of the base controller, according to the following rules: b For 24 I/O compact base controllers TWD LCpA 24DRF: 4 modules max. (see characteristics page 8) b For 40 I/O compact base controllers TWD LCpA 40DRF: 7 modules max. (see characteristics page 8) b For 20 I/O modular base controllers TWD LMDA 20DpK: 4 modules max. (see characteristics page 15) b For 40 I/O modular base controllers TWD LMDA 20DRT/40DpK: 7 modules max. (see characteristics page 15) All analog I/O modules are electrically isolated with the use of a photocoupler between the internal electronic circuit and the input/output channels

Description 4 1 2

3

Twido analog I/O modules comprise: 1 An extension connector for electrical connection to the previous module (1) 2 A block for displaying the channel and module diagnostics 3 A removable screw terminal block for connection of the c 24 V external power supply, the sensors and the pre-actuators 4 A latching mechanism for attachment to the previous module These modules are mounted on a symmetrical 7 rail. Mounting kit TWD XMT 5 (supplied in lots of 5) allows plate or panel mounting. (1) A connector on the right-hand side panel ensures continuity of the electrical link with the next I/O module.

32

0

Page 33

Characteristics

Twido programmable controller

0

Analog I/O modules

General characteristics Temperature

°C

Operation: 0…+ 55. Storage: - 25…+ 70.

Relative humidity

30 to 95 %, without condensation

Degree of protection

IP 20

Altitude Vibration resistance

Mounted on rail m

Operation: 0…2000. Storage: 0…3000.

Hz m/s2

10…57, amplitude 0.075 mm, acceleration 57…150 Hz 9.8 (1 gn)

Plate or panel mounted Hz (using mounting kit TWD XMT 5) m/s2 m/s2

Shock resistance

2…25, amplitude 1.6 mm, acceleration 25…100 Hz 39.2 (4 gn) 147 (15 gn) for 11 ms

Analog input characteristics Module type Number of channels Range

TWD AMI 2HT/AMM 3HT 2 high-level inputs Voltage Current 0…10 V 4…20 mA

Type

Non differential

Resolution

4096 points (12 bits)

LSB value

2.5 mV

Connection

Removable screw terminal block

Permissible continuous overload c 13 V

External supply

V

Input impedance

TWD ALM 3LT 2 low-level inputs Thermocouple Temperature probe Type K (0…1300° C) Pt probe, Type J (0…1200° C) 3-wire type Type T (0…400° C) (- 100…500° C)

Differential

4 µA

40 mA

0.325° C (type K) 0.3° C (type J) 0.1° C (type T)

0.15° C

–

Rated voltage: c 24. Voltage range: c 20.4…28.8 1 MΩ min

10 Ω

250 Ω max

5 Ω max

Maximum sampling duration ms

16

50

Sampling repetition time ms

16

50

Acquisition period ms

32 + 1 controller cycle time

100 + 1 controller cycle time

Maximum error at 25° C

% PE

± 0.2

0.2 + precision of cold junction compensation (± 4° C max)

Temperature coefficient Repeat accuracy after stabilization time Non linearity Total error

% PE/°C ± 0,006 % PE ± 0.5

Measuring precision

% PE % PE

± 0.2 ±1

Common mode rejection

- 50 dB

Cross talk

2 low significance bits max.

Cabling

Twisted shielded pair recommended

Dielectric strength

V rms

Type of protection Consumption

± 0.2

– a 500 between the input and the supply circuit Photocoupler between the input and the internal circuit

Internal supply c 5 V External supply c 24 V mA mA

50 60