The text of a manual · part 7 of 15
Programmable controller Twido Catalog, pages 28 to 33
Pages 28 to 33 of 76: Connections (continued); Connections (continued)
The original document is the PDF (3.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Schneider ABE 7E16EPN20, Schneider ABE 7E16SPN20, Schneider TWDALM3LT, Telemecanique ABE 7E16SPN22 and Telemecanique ABE 7E16SRM20
Page 28
Connections (continued)
0
Twido programmable controller Discrete I/O modules
Transistor output modules TWD DDO 8UT
TWD DDO 8TT Fu
Fu
TWD DDO 16UK Fu
TWD DDO 16TK Fu
TWD DDO 32UK Fu
Fu
Fu
28
Fu
TWD DDO 32TK
Fu
Terminals: v COM (-) are linked internally. v COM0 (-) are linked internally. v COM1 (-) are linked internally. v + V are linked internally. v + V0 are linked internally. v + V1 are linked internally.
Fu
Fu
Fu
Fu
Fu
Terminals: v COM (+) are linked internally. v COM0 (+) are linked internally. v COM1 (+) are linked internally. v - V are linked internally. v - V0 are linked internally. v - V1 are linked internally.
0
Page 29
Connections (continued)
0
Twido programmable controller
0
Discrete I/O modules
Relay output modules TWD DRA 8RT
TWD DRA 16RT Fu
Fu
(1)
(2)
(1)
(2)
(1)
(2)
(1)
(2)
(3)
(4)
(3)
(4)
Terminals: v COM0 are linked internally. v COM1 are linked internally. v COM0 and COM1 are independent (1) Sink output (negative logic) (2) Source output (positive logic)
Mixed input/output modules TWD DMM 8DRT
TWD DMM 24DRT Fu
(1) (2)
Fu
(3)
v The COM (+) terminals are linked internally
(4)
(1) (2)
v Terminals COM0, COM1 and COM2 are independent v Terminals - V are linked internally.
(1) Source input (negative logic) (2) Sink input (positive logic) (3) Sink output (negative logic) (4) Source output (positive logic)
29
Page 30
Selection guide
0
Twido programmable controller Analog I/O modules
Applications
Analog input modules
Number of I/O
2 inputs
4 inputs
8 inputs
8 inputs
Type
Voltage/current
Voltage/current Temperature
Voltage/current
PTC/NTC
Connection
Removable screw terminal block
0...10 V (non differential) 0...20 mA (differential)
–
Inputs
Outputs
Range
0...10 V (non differential) 4...20 mA (differential)
Resolution
10 bits (1024 points)
Acquisition period
32 ms + 1 controller cycle time
0...10 V (non differential) 0...20 mA (differential) Pt 100/1000 NI 100/1000 12 bits (4096 points)
10 bits (1024 points)
160 ms
Range
Resolution
Transfer time
External supply c 24 V external power supply to sensors/pre-actuators (voltage range 20.4…28.8 V)
Isolation
Isolation between channels and ground: by photocoupler
Analog I/O module type
TWD AMI 2HT TWD AMI 4LT
Pages
35
30
TWD AMI 8HT TWD ARI 8HT
0
Page 31
0
Analog output modules
0
Analog mixed I/O modules
Master module for AS-Interface cabling system b For controller versions ≥ 2.0 b Management of slave modules: v Discrete: maximum of 62 slaves arranged in 2 banks, A/B, of 31 addresses each v Analog: maximum of 7 slaves in bank A b The AS-Interface M3 profile supports analog profile 7.3 (7 slaves), but does not support analog profile S-7.4.
1 output
2 outputs
2 inputs/1 output
Voltage/current
Voltage
Voltage/current
Thermocouple/temperature probe inputs Voltage/current output
0...10 V (non differential) 4...20 mA (differential)
Thermocouple type K, J and T Pt100 3-wire temperature probe
Removable screw terminal block
12 bits (4096 points)
32 ms + 1 controller cycle time
0...10 V 4...20 mA
± 10 V
0...10 V 4...20 mA
12 bits (4096 points)
11 bits + sign (2048 points)
12 bits (4096 points)
20 ms + 1 controller cycle time
0.3 ms + 1 controller cycle time
20 ms + 1 controller cycle time
TWD AMO 1HT
TWD AVO 2HT
TWD AMM 3HT
35
100 ms + 1 controller cycle time
TWD ALM 3LT
TWD NOI 10M3
39
31
Page 32
Twido programmable controller
Presentation, description
Analog I/O modules
Presentation Twido analog I/O expansion modules enable the acquisition of various analog values encountered in industrial applications. Analog output modules are used to control the pre-actuators in devices such as variable speed drives, valves and applications that require process control. The output current or voltage is proportional to the numerical value defined by the user program. When the Twido controller stops, the outputs can be configured with fallback (reset to the lowest scale value or hold the last value received). This function, when set to 'hold', is useful when debugging the application or when a fault occurs, in order not to disturb the process being controlled. The 8 following analog I/O modules are available: b One module with 2 inputs: 0…10 V, 4…20 mA b One module with 4 inputs: 0…10 V, 0…20 mA, Pt 100/1000, Ni100/1000 range 122 ... 302 °F (50...150 °C) b One module with 8 inputs: 0…10 V, 0…20 mA b One module with 8 inputs: PTC/NTC b One module with 1 output: 0…10 V, 4…20 mA b One module with 2 outputs: ± 10 V b One mixed module with 2 inputs: 0…10 V, 4…20 mA and 1 output: 0…10 V, 4…20 mA b One mixed module with 2 thermocouple or temperature probe inputs and one 0…10 V, 4…20 mA output Twido analog extension modules offer a resolution of 10 bits, 11 bits + sign and 12 bits, with connection by removable screw terminal block. An external c 24 V power supply is required for each analog module. Like discrete I/O modules, analog I/O modules are connected to the base controller by stacking them on a 7 rail, starting from the right-hand side panel of the base controller, according to the following rules: b For 24 I/O compact base controllers TWD LCpA 24DRF: 4 modules max. (see characteristics page 8) b For 40 I/O compact base controllers TWD LCpA 40DRF: 7 modules max. (see characteristics page 8) b For 20 I/O modular base controllers TWD LMDA 20DpK: 4 modules max. (see characteristics page 15) b For 40 I/O modular base controllers TWD LMDA 20DRT/40DpK: 7 modules max. (see characteristics page 15) All analog I/O modules are electrically isolated with the use of a photocoupler between the internal electronic circuit and the input/output channels
Description 4 1 2
3
Twido analog I/O modules comprise: 1 An extension connector for electrical connection to the previous module (1) 2 A block for displaying the channel and module diagnostics 3 A removable screw terminal block for connection of the c 24 V external power supply, the sensors and the pre-actuators 4 A latching mechanism for attachment to the previous module These modules are mounted on a symmetrical 7 rail. Mounting kit TWD XMT 5 (supplied in lots of 5) allows plate or panel mounting. (1) A connector on the right-hand side panel ensures continuity of the electrical link with the next I/O module.
32
0
Page 33
Characteristics
Twido programmable controller
0
Analog I/O modules
General characteristics Temperature
°C
Operation: 0…+ 55. Storage: - 25…+ 70.
Relative humidity
30 to 95 %, without condensation
Degree of protection
IP 20
Altitude Vibration resistance
Mounted on rail m
Operation: 0…2000. Storage: 0…3000.
Hz m/s2
10…57, amplitude 0.075 mm, acceleration 57…150 Hz 9.8 (1 gn)
Plate or panel mounted Hz (using mounting kit TWD XMT 5) m/s2 m/s2
Shock resistance
2…25, amplitude 1.6 mm, acceleration 25…100 Hz 39.2 (4 gn) 147 (15 gn) for 11 ms
Analog input characteristics Module type Number of channels Range
TWD AMI 2HT/AMM 3HT 2 high-level inputs Voltage Current 0…10 V 4…20 mA
Type
Non differential
Resolution
4096 points (12 bits)
LSB value
2.5 mV
Connection
Removable screw terminal block
Permissible continuous overload c 13 V
External supply
V
Input impedance
TWD ALM 3LT 2 low-level inputs Thermocouple Temperature probe Type K (0…1300° C) Pt probe, Type J (0…1200° C) 3-wire type Type T (0…400° C) (- 100…500° C)
Differential
4 µA
40 mA
0.325° C (type K) 0.3° C (type J) 0.1° C (type T)
0.15° C
–
Rated voltage: c 24. Voltage range: c 20.4…28.8 1 MΩ min
10 Ω
250 Ω max
5 Ω max
Maximum sampling duration ms
16
50
Sampling repetition time ms
16
50
Acquisition period ms
32 + 1 controller cycle time
100 + 1 controller cycle time
Maximum error at 25° C
% PE
± 0.2
0.2 + precision of cold junction compensation (± 4° C max)
Temperature coefficient Repeat accuracy after stabilization time Non linearity Total error
% PE/°C ± 0,006 % PE ± 0.5
Measuring precision
% PE % PE
± 0.2 ±1
Common mode rejection
- 50 dB
Cross talk
2 low significance bits max.
Cabling
Twisted shielded pair recommended
Dielectric strength
V rms
Type of protection Consumption
± 0.2
– a 500 between the input and the supply circuit Photocoupler between the input and the internal circuit
Internal supply c 5 V External supply c 24 V mA mA
50 60
33