Page 1

Andover Continuum Infinet II i2850 Series

The i2850, i2851, and i2853 controllers provide cost-effective DDC control of individual terminal units (e.g. VAV boxes, fan-powered induction units, unit ventilators, heat pumps).

TM

Page 2

02

Andover Continuum Infinet II i2850 Series Terminal Controllers Features

The i2850 Series is a perfect fit for your VAV applications where external damper actuators are used. And because all i2850 Series controllers feature a built-in expansion port for additional I/O, these controllers are perfect for your more demanding control applications. Choose the i2850 Series controller with the input configuration that matches your application:

PRODUCT AT A GLANCE • Compact Terminal Controllers Provide VAV Control for a Broad Range of Applications • Compatible with Both Andover Continuum and Infinity Systems • Expandable I/O Meets Additional Point Count Needs • Universal Inputs with Form A and Form K Outputs for Flexible Control Options • Non-Volatile Flash Memory Provides Utmost Reliability, Stores Both Application Program and Operating System • Flash Memory Allows Easy On-Line Software Updates • On-Board Airflow Sensor • Optional Display/Keypad Provides Easy Operator Interface (Mounted Separately) • View and Modify Information with Optional Andover Continuum Smart Sensor Display • Local On-Board Service Port

• The i2850 has four full range universal inputs plus a fifth input for an on-board air flow sensor for VAV airflow measurement. • The i2851 contains four universal inputs as well, but does not have the on-board air flow sensor and is perfect for applications not requiring airflow measurement, such as heat pumps and fan coils. • The i2853 is for dual-duct VAV applications. It contains two onboard airflow sensors and four universal inputs. All three models feature an additional room sensor input, which supports Andover Continuum Smart Sensor, or any standard room temperature sensor; plus three Form A relays and one Form K Tri-state relay output. Similar to all i2 controllers, the i2850 Series features Flash memory, increased user memory, and a fast (32-bit) processor for faster scan times, with plenty of additional memory available for data logging of your critical data. The i2850 Series communicates with the entire Andover Continuum Infinet RS-485 field bus (i.e. both Andover Continuum Infinet and Andover Continuum Infinet II controllers) and is compatible with both the Andover Continuum CyberStation and Infinity SX 8000 front-ends. Up to 254 Andover Continuum Infinet devices can be networked to any Andover Continuum network controller.

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-I2850-A4.BU.N.EN.11.2007.0.01.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 3

03

Andover Continuum Infinet II i2850 Series Terminal Controllers Features (continued)

Increased Reliability with Flash Memory

Dimensional Drawings

The i2850’s non-volatile Flash memory stores your operating system and application programs, so that in the event of a power loss, your application will be restored when power is returned. In addition, the Flash memory allows for easy upgrades of your operating system via software downloads, eliminating the need to swap out proms. The i2850 controllers include an on-board battery to safeguard your runtime data, protecting all point data and log data from being lost if power is removed.

Inputs The input configuration on the i2850 Series consists of four full range universal inputs that accept voltage (0-5VDC), digital (on/off), counter signals (up to 4Hz), or temperature signals. The i2850 features one on-board air flow sensor; the i2853 provides two. All models offer an additional input to support the Andover Continuum Smart Sensor, or any standard room temperature sensor.

2

1

4

Outputs

3

The i2850 Series contains three Form A relay outputs and one Form K Tri-state output. Each relay is rated for 24 VAC/VDC, 3 amp. These outputs can be used separately for on/off or pulsed control of lighting, heat, and fan units. The preconfigured Form K Tri-state output can be used for bi-directional control of dampers and valves. (Note: Any two consecutive Form A outputs can be configured to form an additional Form K output.)

I/O Expansion The i2850 Series contains an I/O expansion port for the addition of up to two xP expansion modules directly on the bottom of the controller. The i2 family of modules includes the xPDI8, xPUI4, xPDO2, xPDO4, xPAO2, and xPAO4. In addition, the I/O bus supports the xP Display Module, which allows the user to view and change point values.

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-I2850-A4.BU.N.EN.11.2007.0.01.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 4

04

Andover Continuum Infinet II i2850 Series Terminal Controllers Features (continued)

Software Capabilities

Dimensional Drawings

The dynamic memory of the i2850 Series can be allocated for any combination of programs, scheduling, alarming, and data logging using the powerful Andover Continuum Plain EnglishTM programming language. Our object-oriented Plain English language with intuitive keywords provides an easy method to tailor the controller to meet your exact requirements. Programs are entered into the i2850 Series using the Andover Continuum CyberStation, Infinity SX 8000 Workstation, or local user terminal. Programs are then stored in, and executed by, the i2850 Series controllers. Programming multiple i2850 Series controllers is inherently easy with Plain English. A complete copy of one i2850 controller’s programs can be loaded directly into other i2850 controllers without changing any point names or programs.

1

Power Drawing

2

Communication Drawing

Smart Sensor Interface The i2850 Series provides a built-in connection for Andover Continuum Smart Sensor. The Smart Sensor provides a 2-character LED display and a 6-button programmable keypad that enables operators and occupants to change setpoints, balance VAV boxes, monitor occupancy status, and turn equipment on and off. An enhanced version of the Smart Sensor is also available with a 4-digit custom LCD that provides the following icons: PM, %, °, Setpoint, Cool, Heat, CFM, Fan, OA, and SP.

Local Display The local display with keypad (xP-Display) allows for the addition of a fully programmable local display module that can be mounted within 10 feet (3 meters) of the controller. Connected via a ribbon cable, the xP-Display easily allows the Operator Interface to be mounted on the door of an enclosure or on a wall below or next to the controller.

3 Smart Sensor and Inputs Drawing

4 Outputs Drawing

Optional Wireless Andover Continuum Infinet The i2850 Series Andover Continuum Infinet controllers can also communicate using a wireless mesh network. Simply plug Andover Continuum Wireless Adapters into the service ports of these controllers with wireless compatible firmware to create a wireless mesh network that sends and receives Andover Continuum Infinet messages.

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-I2850-A4.BU.N.EN.11.2007.0.01.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 5

05

Andover Continuum Infinet II i2850 Series Terminal Controllers Specifications

05 i2850 Series Terminal Controllers Electrical

Communications

Inputs

Power

Communications Interface

4 Universal inputs: Voltage (0-5.115 VDC);

24 VAC, +10% -15%, 50/60 Hz

Through Andover Continuum Infinet

Temperature -30°F to 230°F

Power Consumption

RS-485 field bus to network controller

(-34°C to 110°C), Digital (on/off), Counter

20 VA

Communications Speed

(up to 4Hz at 50% duty cycle, 125 ms min.

Overload Protection

1200 to 19.2K baud pulse width). Supervised Alarm (single or

Fused with 2 amp fuse. MOV protected.

Bus Length double resistor). Current input (0 - 20 mA)

Software Real-Time Clock

4,000 ft. (1,220m) standard for using external 250 ohm resistor

Synchronized through Andover Continuum

Andover Continuum Infinet, i2 Infilink

1 Smart Sensor Temperature Input

Infinet by network controller module allows extension to longer

(32°F to 105°F) (0°C to 41°C)

distances and is required after every

Airflow sensor (0 to 2” W.C.)

Mechanical group of 32 units on the network.

(i2850- qty 1; i2853-qty 2)

Operating Environment

Bus Media

Input Voltage Range

32°–120°F (0–49°C),

Andover Continuum Infinet: twisted,

0-5.115 volts DC

10–95% RH (non-condensing)

shielded pair, low capacitance cable

Input Impedance

Size

RS-485 port for implementing Wireless

10K ohm to 5.120V or 5M ohm

5.47˝ H x 8.16˝ W x 2.44˝ D

Infinet II connection, including:

with pull-up resistor disabled

(139H x 207W x 62) mm

Standard service port, four-position

Input Protection

Weight shrouded connector

24 VAC or 24 VDC temporarily

1.08 lbs. (.50 kg)

Comm. Error Checking on any single channel, ±1000V transients

Enclosure Type

International Standard CRC 16

(Tested according to EN61000-4-4)

UL Open class, IP 10.

Compatibility

Input Resolution

Flammability rating of UL94-5V

Andover Continuum Cyberstation and

5.0 mV

Mounting

Infinity SX 8000 systems

Input Accuracy ±15mV (±0.56°C from -23°C to +66°C or

Panel mount

±1°F from -10°F to +150°F)

Battery

Airflow Input

Battery Backup

Range:

0 to 2” W.C. (0-500 Pa)

Replaceable, non-rechargeable,

Resolution:

0.005” W.C. (1.25 Pa) @ 23° C (73° F)

lithium battery. Provides 5 years Accuracy:

typical accumulated power failure

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-I2850-A4.BU.N.EN.11.2007.0.01.CC

±0.05” W.C. (6.25 Pa) @23°C (73°F)

backup of RAM memory

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 6

06

Andover Continuum Infinet II i2850 Series Terminal Controllers Specifications (continued)

i2850 Series Terminal Controllers Outputs

User LEDs/Switches

Models

3 single pole single throw (SPST)

Status Indicator LEDs:

i2850

Form A relays

CPU

CPU Active

Infinet II i2850 Terminal Controller

1 Form K Tri-state relay output

TD

Transmit Data i2850-S

(Any two consecutive Form A outputs

RD

Receive Data

Infinet II i2850 Terminal Controller can be configured as one Form K Tri-state)

Output

Output Status (per with Smoke-Control option output) (Digital only)

i2850-WL

Output Rating Maximum 3A, 24VAC/VDC,

EXPANSION

±1500V transients

PORT PWR

Wireless Infinet II i2850 Terminal Controller

(Tested according to EN61000-4-4)

Switches

Infinet II i2851 Terminal Controller

Output Accuracy

RESET i2851-S

0.1 sec. for pulse width modulation

Input Pull-up Resistor Switch (per input)

Infinet II i2851 Terminal Controller i2851

Power Status

Expansion Bus with Smoke-Control option

Interfaces to optional xP I/O

General i2851-WL

Expansion Modules

Memory

Wireless Infinet II i2851 Terminal Controller

128K SRAM, 1MB FLASH i2853

Connections

Processor

Infinet II i2853 Terminal Controller

Power

Motorola 32-bit Coldfire i2853-S

3-position fixed screw terminal connector

Infinet II i2853 Terminal Controller

Inputs

Agency Listings with Smoke-Control option

6-position fixed screw terminal connector

UL/CUL 916, FCC CFR 47 Part 15, i2853-WL

Outputs

ICES-003, EN55022, AS/NZS 3548,

Wireless Infinet II i2853 Terminal Controller

9-position fixed screw terminal connector

Class A, CE

Smart Sensor 3-position fixed screw terminal connector

Options

Communications

UL864, Smoke Control System Equipment,

3-position removable screw

UUKL (i2850-S, i2851-S, i2853-S)

terminal connector

Expansion Port 6-position shrouded connector

Service Port

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. Schneider Electric One High Street, North Andover, MA 01845 USA SDS-I2850-A4.BU.N.EN.11.2007.0.01.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings November 2007 pdw

© 2007-2009 Schneider Electric. All rights reserved.

4-position shrouded connector