Spec sheet · Schneider
Andover Continuum Infinet II i2850 Series Terminal Controllers
Spec sheet6 pagesPDF 563 KB
Specification sheet for the Andover Continuum Infinet II i2850, i2851 and i2853 terminal controllers for VAV and other terminal units.
Covers · 2 models
The models it covers
Summary
What is in it
Schneider Electric's specification sheet for the Andover Continuum Infinet II i2850 Series terminal controllers (i2850, i2851 and i2853), DDC controllers for terminal units such as VAV boxes, unit ventilators and heat pumps. It describes features, inputs and outputs, flash memory, I/O expansion, Plain English programming, the Smart Sensor and local display, optional wireless Infinet, dimensional drawings and full electrical, communications, mechanical and model specifications.
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
This is the Schneider Electric specification sheet for the Andover Continuum Infinet II i2850 Series Terminal Controllers, covering the i2850, i2851 and i2853. It describes the inputs, outputs, communications, expansion and programming of these controllers for VAV boxes and other terminal units. It also lists their electrical and mechanical specifications and the model variants.
- Device
- Infinet II terminal controller for DDC control of terminal units such as VAV boxes, unit ventilators and heat pumps p. 1
- Inputs
- i2850: four full range universal inputs, one on-board airflow sensor and a room sensor input for the Smart Sensor or a standard room temperature sensor p. 2, 3
- Outputs
- Three Form A relays and one Form K Tri-state relay output, each rated 24 VAC/VDC, 3 amp p. 3
- Power
- 24 VAC, +10% -15%, 50/60 Hz; 20 VA; fused with 2 amp fuse, MOV protected p. 5
- Network
- Andover Continuum Infinet RS-485 field bus to a network controller, 1200 to 19.2K baud; up to 254 Infinet devices per network controller p. 2, 5
- Memory, processor
- 128K SRAM, 1MB FLASH; Motorola 32-bit Coldfire processor p. 6
- Battery
- Replaceable, non-rechargeable lithium battery; 5 years typical accumulated power failure backup of RAM p. 5
- Size, weight
- 5.47 in H x 8.16 in W x 2.44 in D (139 x 207 x 62 mm); 1.08 lbs. (.50 kg); panel mount p. 5
- Operating environment
- 32 to 120 °F (0 to 49 °C), 10 to 95% RH non-condensing p. 5
- Input types
- Voltage 0-5.115 VDC, temperature -30°F to 230°F, digital, counter up to 4Hz, supervised alarm; 0 - 20 mA with an external 250 ohm resistor p. 5
- I/O expansion
- Up to two xP modules on the bottom of the controller: xPDI8, xPUI4, xPDO2, xPDO4, xPAO2, xPAO4; the bus also supports the xP Display Module p. 3
- Bus length
- 4,000 ft. (1,220m) standard; an i2 Infilink module extends it and is required after every group of 32 units p. 5
- Model variants
- i2850-S with Smoke-Control option; i2850-WL wireless; also i2851 and i2853 with -S and -WL versions p. 6
- Programming
- Plain English language, entered from CyberStation, Infinity SX 8000 Workstation or a local user terminal p. 4
What this sheet walks you through
- Choosing between the i2850, i2851 and i2853 by inputs p. 2
- Adding xP I/O expansion modules p. 3
- Programming the controllers in Plain English p. 4
- Connecting an Andover Continuum Smart Sensor p. 4
- Mounting the xP-Display local display p. 4
- Setting up wireless Infinet communication p. 4
Good to know
- Wireless Infinet needs controllers with wireless compatible firmware. p. 4
- The xP-Display must be mounted within 10 feet (3 meters) of the controller. p. 4
- Any two consecutive Form A outputs can be set up as an additional Form K output. p. 3
- The spec sheet states the enclosure type as UL Open class, IP 10. p. 5
Questions this sheet answers
What is the difference between the i2850, i2851 and i2853?
The i2850 has one on-board airflow sensor, the i2851 has none, and the i2853 has two for dual-duct VAV; all have four universal inputs. p. 2
What power does the i2850 need?
24 VAC, +10% -15%, 50/60 Hz, with a power consumption of 20 VA. p. 5
How many expansion modules can an i2850 take?
Up to two xP expansion modules, mounted on the bottom of the controller. p. 3
What are the i2850 relay output ratings?
Each relay is rated 24 VAC/VDC, 3 amp. p. 3
Does the i2850 keep its program after a power loss?
Yes: Flash memory stores the operating system and programs, and an on-board battery protects point and log data. p. 3