Page 1 of Andover Infinet i2 Controller Technical Reference

Manual · Schneider

Andover Infinet i2 Controller Technical Reference

Manual190 pagesPDF 8.4 MB

Technical reference for the Andover Infinet i2 building controllers from Schneider Electric, including the i2850: installation, wiring and programming.

Download the PDF8.4 MB

Covers · 2 models

The models it covers

Summary

What is in it

Schneider Electric's technical reference for the whole Andover Infinet i2 family of programmable stand-alone controllers (i2600, 800, 810, 850, 865, 867, 885, 887 and 920 series), which give direct digital control of terminal units such as VAV boxes and heat pumps. It covers mechanical installation and dimensions, power connections, the RS-485 Infinet network, universal and supervised inputs, airflow measurement, digital, tri-state and analog outputs, expansion modules, operation and programming, and troubleshooting.

Its parts

  1. Introduction
  2. Mechanical Installation
  3. Power Connections
  4. RS-485 Infinet
  5. Controller Inputs
  6. Controller Outputs
  7. Expansion Interface
  8. Operation/Programming
  9. Troubleshooting

From the manual

Key facts from this manual

Each line names its page in the PDF.

This is the Schneider Electric Andover Infinet i2 Controller Technical Reference (revision E, May 2010), for installing and using all Infinet II (i2) controllers: the i2850 Series (i2850, i2851, i2853) along with the i2600, i2800 and i2810 Series, i2865/866, i2867, i2885, i2887 and i2920. It covers mounting, power, Infinet networking, inputs, outputs, expansion modules, programming and troubleshooting.

Read for this summary: pages 2 to 3, 9 to 12, 16, 45 to 46, 54 to 55, 59 to 60, 73, 89 to 90, 97, 101, 115 to 118, 162 and 165 to 168 of 190.

i2850 I/O
i2850: 4 universal inputs plus Smart Sensor, 3 Form A outputs and 1 Tri-state output, 1 airflow sensor, Expansion Interface p. 9, 73, 97
Universal inputs
Software configurable as thermistor, voltage, counter, supervised or digital; 0-5VDC on most i2 models; max. line resistance 4700 ohms p. 73
Airflow sensor
i2850: 1 sensor, 0-2 in W.C. (0-500Pa), resolution 0.005 in W.C. (1.25Pa) at 23°C (73°F) p. 89
Tri-state output
i2850 Series: Form K Tri-state relay on OUT4; OUT1/OUT2 or OUT2/OUT3 can be combined as another Tri-state output p. 101
Battery
i2850 Series: CR1225 coin-style 3 Volt lithium battery, typically 5 years of backup p. 54, 55
Power fuse
i2850 Series: 2A @ 125VAC, NANO, part 01-2180-006 p. 167
Infinet network
Token-passing field bus, electrically similar to RS-485, on shielded twisted pair at up to 19.2 Kb/sec; max. 127 nodes; up to 254 i2 controllers (127 per Infinet port) p. 9, 59, 60
Cable length
Up to 4,000 ft (1,220 m) daisy chained on one arm; beyond that an i2200 repeater; an i2210 repeater extends Infinet over fiber optic cable p. 59
Expansion
i2850 Series: expansion connector on the bottom; two modules plus the xPDisplay, within 180mA @ 24 VDC from the controller p. 115, 118
Module current draw
xPAO2 80mA, xPAO4 120mA, xPDO2 60mA, xPDO4 100mA, xPDI8 25mA, xPUI4 50mA, xPBA4 60mA, xPBD4 125mA, xPDisplay 70mA (at 24VDC) p. 118
CPU indicator
2.5 times/second, equal on and off: boot mode (application being uprevved, missing or corrupt); 2.5 times/second, short on, long off: normal operation with entries in the error log p. 168
Wireless
A Wireless Adapter on each controller's COMM2 port, via the service port, joins a wireless mesh with a bCX1 9640 parent p. 10
Smoke control
The manual states the i2850-S is listed with UL for Smoke Control applications (UL 864) p. 12
Document
Schneider Electric part number 30-3001-861, revision E, May 2010, for i2 controller firmware version 3.5 p. 2

What this manual walks you through

  • Wiring 24 VAC power and powering several controllers p. 46
  • Activating and replacing the backup battery p. 54, 55
  • Infinet cabling, lengths and device limits p. 59, 60
  • Connecting the airflow sensor to a VAV box p. 89, 90
  • Configuring the Tri-state output and combining Form A outputs p. 101
  • Choosing expansion module combinations within the power limit p. 116, 117, 118
  • Pre-operation checks and first power-up p. 162
  • Checking and replacing the main power fuse p. 165, 167
  • Reading abnormal CPU blink patterns p. 168
  • Replacing older Infinet I controllers with i2 models p. 10, 11

Good to know

  • Unless the controllers share one cabinet, each needs its own transformer. p. 46
  • The insulating tab under the battery clip must be removed to activate the battery. p. 55
  • Airflow sensor tubing is kept to 15 inches (380.99 mm) at most. p. 90
  • Infinet wiring cannot be shared with other RS-485 controllers such as BACnet or LONMark. p. 59
  • Tri-state outputs fail in the OFF state if there is no power. p. 101

Questions this manual answers

What battery does the i2850 use?

A CR1225 coin-style 3 Volt lithium battery, which typically keeps backup for 5 years. p. 54, 55

What fuse does the i2850 take?

The i2850 Series main power fuse is 2A @ 125VAC, NANO, part 01-2180-006. p. 167

How many expansion modules can an i2850 have?

Two modules plus the xPDisplay, as long as they draw no more than the 180mA @ 24 VDC the controller supplies. p. 118

How long can an Infinet cable run be?

Up to 4,000 ft (1,220 m) daisy chained on one arm; beyond that an i2200 repeater is needed. p. 59

What does the i2850 CPU light blink rate mean?

A blink of 2.5 times/second with equal on and off time means boot mode: the application is being uprevved, is missing or is corrupt. p. 168

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Front Cover1
  2. Regulatory Notices3
  3. Introduction7
    1. i2 Controller Overview9
    2. Wireless Support10
    3. i2 vs Infinet I Controller Compatibility Issues10
    4. Special System Characteristics12
    5. i2 600 Series13
    6. i2 800 Series14
    7. i2 810 Series15
    8. i2 850 Series16
    9. i2 865/i2 86617
    10. i2 865-V/i2866-V/i2885-V18
    11. i2 86719
    12. i2 88520
    13. i2 88721
    14. i2 887-L22
    15. i2 92023
  4. Mechanical Installation25
    1. Dimension Drawings27
    2. Actuator Installation38
  5. Power Connections43
    1. Controller Power Options45
    2. 24VAC Connections46
    3. 12-28 VDC Connection51
    4. 115-230 VAC Connection52
    5. Battery Backup Connection and Replacemenet54
    6. Building Ground Requirements56
  6. RS-485 Infinet57
    1. Infinet Cable Specifictions59
    2. Maximum Cable Length59
    3. Maximum Number of Devices60
    4. Infinet Network Configurations60
    5. DaisyChain Configuration61
    6. Daisy Chain Configuration with i2 200 Repeater62
    7. Star Configuration with i2 200 Repeater63
    8. Infinet Between Buildings Using the i2 21064
    9. Infinet Network Shielding65
    10. Controller Infinet Connections67
44 more lines, from page 68 on
  1. Infinet Repeater Connections68
  2. Controller Inputs71
    1. Input Connections73
    2. Universal Inputs73
    3. Supervised Inputs84
    4. Measuring Airflow89
    5. Smart Sensor Bus Interface92
  3. Controller Outputs95
    1. Output Connections97
    2. Output Specifications97
    3. i2887-L Output Power Supply97
    4. Number of Outputs97
    5. Output Wiring98
    6. Digital Outputs100
    7. Tri-State Outputs101
    8. Analog Outputs109
    9. Voltage Output111
  4. Expansion Interface113
    1. Overview of expansion modules115
    2. Possible Expansion I/O Module Combinations116
    3. Power Consumption of Expansion Modules118
    4. Expansion Cable Connections119
    5. Basic Expansion (no Display)120
    6. Remote Expansion (no Display)120
    7. Basic Expansion (with External Display)121
    8. Remoe Expansion (with External Display)122
    9. Basic Expansion (i2920 with Internal Display)123
    10. Expansion Input/Output Wiring124
  5. Operation/Programming125
    1. Operation/Pgramming - All Controllers except i2885, i2885-V, 887-L127
    2. Operation/Programming - i2885, i2885-V, and i2887-L139
    3. I/O Point Assignments147
    4. Expansion Point Assignments156
    5. Actuator Programming and Use156
    6. Plain English Function Changes161
    7. Pre-Operation Checks162
    8. Initial Power-Up162
    9. CPU Indicators162
  6. Troubleshooting163
    1. General Troubleshooting165
    2. Infinet Troubleshooting170
    3. Troubleshooting the i2200 Repeater183
    4. Troubleshooting the i2210 Repeater185
    5. Attaching the Infinet (RoamIO2) Service Tool186

From the PDF’s own bookmarks.

The whole text · 20 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 41-4
  2. Pages 5 to 145-14
  3. Pages 15 to 2415-24
  4. Mechanical Installation, pages 25 to 3325-33
  5. Mechanical Installation, pages 34 to 4234-42
  6. Power Connections43-56
  7. RS-485 Infinet57-70
  8. Controller Inputs, pages 71 to 7871-78
  9. Controller Inputs, pages 79 to 8679-86
  10. Controller Inputs, pages 87 to 9487-94
  11. Controller Outputs, pages 95 to 10395-103
  12. Controller Outputs, pages 104 to 112104-112
  13. Expansion Interface113-124
  14. Operation/Programming, pages 125 to 134125-134
  15. Operation/Programming, pages 135 to 144135-144
  16. Operation/Programming, pages 145 to 154145-154
  17. Operation/Programming, pages 155 to 162155-162
  18. Troubleshooting, pages 163 to 172163-172
  19. Troubleshooting, pages 173 to 182173-182
  20. Troubleshooting, pages 183 to 190183-190

The file

Revision and size

RevisionRev. E, May 2010, part number 30-3001-861
PublisherSchneider Electric
Pages190
PDF8.4 MB
TextText from the PDF itself; 7 pages are scans, read by OCR, which may hold reading errors.

The first pages · 3 of 190

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 190
Page 2
Page 2of 190
Page 3
Page 3of 190

More documents · 1

For the same models