Page 104

Form A Triac Outputs i2865/866, i2867, i2885 & i2887(L) The following is a functional schematic representation of the proper way to use the Form A Triac output:

When the output is activated, the connection between the “OUTx” and “GND” terminals becomes a virtual short circuit. Using the Form A connection you can control anything that would normally be controlled (within specifications) via a switch or relay contact closure. Switching Loads with Triacs Although the Triac-based outputs provided with this unit appear as relay contacts in the schematics provided, they are actually solid-state switches that have limitations on the loads they can switch. AC vs. DC The first limitation is that they cannot be used with DC loads. A Triac switches AC only. Minimum Load Current The second limitation involves the minimum load current. In order for the Triac to switch it must have at least 30 ma of holding current from the load. If your load is less than 30 ma you can increase it by connecting a resistor across the load (not directly at the Triac!). Check the current draw specification on your field device, and if it does not meet this minimum, add a resistor in parallel with the device being driven sized to achieve the minimum loading. Use the following formulas to determine resistance and wattage: Resistance (ohms)

=

Voltage Current

Maximum Current and Voltage 0.5A @ 24 VAC i2867 0.3A @ 24 VAC i2887, i2887-L

98

Schneider Electric n

Power (watts)

=

(Voltage)2 Resistance

Page 105

Form A Triac Outputs i2865-V/2866-V & i2885-V The i2 865/866-V controllers use three Form A triac output terminals with a single triac reference. This configuration gives you the flexibility to wire the single triac reference as either a hot or ground connection. On these new controllers, all three outputs must be wired the same, as either hot or ground switch applications. To make a hot switch connection, connect one of the output terminals (OUTX, where X= 3, 4, or 5) to a load, and connect the Triac Reference to the incoming 24 VAC power. Switching Option - Triac Form A Hot Connection i2/b3 865/866 -V Controller

24 VAC Step-Down Transformer

75, $ & 5 ( )

X1 24 VAC

AC Line Power

GND

' ,* ,7$ / 2 8 73 87 6 9$ & $

287 287 287

X2

Note: i2/b3 885-V Controller only has two digital outputs i2 Controller Technical Reference

99

Page 106

To make a ground switch connection, connect one of the output terminals (OUTX, where X= 3, 4, or 5) to a load in series with the 24 VAC incoming power, and connect the Triac Reference to ground. Switching Option - Triac Form A Ground Connection i2/b3 865/866 -V Controller

24 VAC Step-Down Transformer

75 ,$ & 5 ( )

X1 24 VAC

AC Line Power

GND

', * ,7$ / 2 8 7387 6 9$ & $

287 287 287

X2

Note: i2/b3 885-V Controller only has two digital outputs

The new b3 885-V controller, which has only two output terminal connections, works the same, allowing for either two hot or ground switch applications.

100

Schneider Electric n

Page 107

Form K Triac Outputs i2865-V/866-V & i2885-V To create a Form K triac connection on the new i2865 /866-V controllers, make the individual connections from the terminals 12 and 13 (OUT3 and OUT4), or use terminals 13 and 14 (OUT4 and OUT5), with a common ground reference to terminal 15 (TRIAC REF). Switching Option - Triac Form K Ground Connection i2/b3 865/866 -V Controller

OUT4 Load

OUT3 Load 24 VAC Step-Down Transformer

75, $ & 5 ( )

X1 24 VAC

AC Line Power

GND

' ,* ,7$ / 2 8 73 87 6 9$ & $

287 287 287

X2

Note: i2/b3 885-V Controller only has two digital outputs

To maintain Form K triac connections on the new i2885-V controller, make the individual connections from terminal 6 and 7 (OUT3 and OUT4) with a common ground reference to terminal 9 (TRIAC REF). Terminal 8 is not used on the i2885-V controller.

i2 Controller Technical Reference

101

Page 108

Internally Powered Triac Outputs i2887-L The i2887-L includes an internal 24VAC power source that can be used to power external loads thus eliminating the need for an external transformer. The following is a functional schematic representation of the proper way to use the Internal- powered Triac output:

All other limitations that normally apply to Triac outputs exist in this configuration as well. Note: The total allowable current sourced by the internal 24VAC power source for all external loads is 750mA .

102

Schneider Electric n

Page 109

Analog Outputs (i2804, i2814, i2920) The i2804, i2814 and i2920 include Analog outputs that may be configured to provide either voltage or current. Each output presents two ways of connecting, resulting in a current output between the terminal labeled ‘I’ and ‘GND’, and a voltage output between the terminal labeled ‘V’ and the terminal labeled ‘GND’. The diagram screen printed on the module indicates where each input number is located on the terminal block. The following is a schematic representation of the connection:

i2 Controller Technical Reference

103

Page 110

Analog Output Override Controls UL-864 Note: The use of output overrides is prohibited in UL-864 Smoke Control Applications.

The i2804, i2814 and the i2920 controller include an output override switch and manual variable control for each output.

The following describes the actions associated with each position of the override controls:

104

OFF

The output is set to zero volts, zero mA. Programs and the setting on the ADJUST potentiometer have no effect on the output Device when the switch is in this position.

AUTO

The analog signal is generated as a direct result of program control. The setting on the ADJUST potentiometer has no effect on the output Device when the switch is in this position.

MANUAL

The analog signal generated by the module is controlled manually by adjusting the ADJUST potentiometer. Programs have no effect on the output when the switch is in this position.

ADJUST

This is a variable control that allows you to manually adjust the output of the analog signal when the override switch is in the MANUAL position. Insert the tip of a small screwdriver to use this control. Turning to the right (clockwise) increases the output. Turning left (counterclockwise) decreases the output.

Schneider Electric n

Page 111

Voltage Output (i2804, i2866, i2866-V, & i2867) The i2804, i2866, i2866-V and i2867 controllers provide a voltage output that is a groundreferenced signal with a range of 0–10 VDC. The maximum output current is 5 mA (2,000 ohms minimum resistance). Ensure that the device being connected is either floating or at the same ground potential as the controller. Configure the output point with an Electrical Type of Voltage. Connect the device across the following terminals: i2804 i2866, i2867

OUTx i2866-V

AOx

AOx

Note: The load resistance (of the external device) must be greater than or equal to 2KΩ.

i2 Controller Technical Reference

105

Page 112