6 . . . . . . Controller Outputs i2 Controller Technical Reference
89
Page 96
90
Schneider Electric n
Page 97
Output Connections All i2 series controllers, except the i2600 Series, include some form of output complement. Outputs come in relay and Triac versions in many contact configurations.
Output Specifications For specific output specifications, consult the datasheet or the installation sheet for the particular controller. Generally, the following specifications apply: Digital Relay Outputs: Triac Outputs:
3A @ 24VAC/30VDC 0.5A @ 24VAC (30mA minimum load) 0.3A @ 24VAC (i2887, i2887-L)
All digital output loads are resistive.
i2887-L Output Power Supply The i2887-L includes the ability to supply power to its output loads eliminating the necessity for an external transformer. The following limitations apply: The total allowable current sourced by the internal power source for all external loads is 750mA.
Number of Outputs The following table lists the output complement of each controller.
Controller
Outputs
Controller
Outputs i2608
0 i2865
3 Form A Triac, Actuator i2624
0 i2865-V
3 Form A Triac, Actuator i2800
8 Form C i2866
3 Form A Triac, 2 Analog, Actuator i2804
4 Form C, 4 Analog i2866-V
3 Form A Triac, 2 Analog, Actuator i2810
8 Form C i2867
5 Form A Triac, 2 Analog i2814
4 Form C, 4 Analog i2885
2 Form A Triac, Actuator i2850
3 Form A, 1 Tri-state i2885-V
2 Form A Triac, Actuator i2851
3 Form A, 1 Tri-state i2887(L)
4 Form A Triac, 1 Form A Relay i2853
3 Form A, 1 Tri-state i2920
8 Form C, 8 Analog i2 Controller Technical Reference
91
Page 98
Output Wiring Output terminations are typically located along the right side of the module. Connection is via screw terminal.
CAUTION: Do not connect outputs while the controller is running.
The following pages include diagrams detailing each module’s output connections:
92
Schneider Electric n
Page 99
-V
-V -V
-V
TRIAC 15 REF
18 A07
OUT3
14 13
OUT4
17
NOT USED
16 A06
TRIAC REF 9
15 TRIAC REF
12 14 13 12 i2 Controller Technical Reference
93
Page 100
Digital Outputs Form A Relays i2850 Series and i2887(L) The i2887(L) and the i2850 series include Form A relay outputs. The following is a functional schematic representation of the connection:
These output contacts operate as a single pole switch. When the output is set to an ‘ON’ state, the contacts close allowing current to flow between the output terminals. To use the Form A output in your system, configure an output point with an Electrical Type of Digital.
Form C Relays i2800 Series, i2810 Series, i2920 These outputs operate as either two-position (on/off) or pulse-width modulation (PWM) control. The PWM feature permits the modulation of valves and dampers to 0.1 second resolution. Two adjacent Form C relay outputs can be combined in software to provide a Tri-state output, for bi-directional control of valves and dampers and other end devices. The following is a functional schematic representation of the connection:
To use the Form C output in your system, configure an output point with an Electrical Type of Digital.
94
Schneider Electric n
Page 101
Tri-State Outputs The following sections describe various types of tri-state outputs. Form-K Tri-State Relay Output i2850 series controllers include a Tri-state Form K relay output designated as OUT4. The following is a schematic representation of a Tri-state output: C
+ ON
ON
Configure Output 4 with an Electrical Type of Tri-state. Note that Tri-state outputs fail in the OFF state if there is no power. Combining Form A Relay Outputs as a Tri-State Output Adjacent output pairs such as: OUT1 and OUT2 OUT2 and OUT3 can be combined to form a standard Tri-state output. The outputs are electrically connected as shown in the schematic for the built-in Tri-state output. Configure the output point of the first point of a pair (i.e., OUT1 of the pair OUT1 and OUT2) with an Electrical Type of Tri-state.
i2 Controller Technical Reference
95
Page 102
Combining Form C Relay Outputs as a Tri-State Output Adjacent output pairs such as: OUT1 and OUT2 OUT2 and OUT3 can be combined to form a standard Tri-state output. The outputs are electrically connected as shown in the schematic for the built-in Tri-state output. Configure the output point of the first point of a pair (i.e., OUT1 of the pair OUT1 and OUT2) with an Electrical Type of Tri-state.
96
Schneider Electric n
Page 103
Relay Output Override Controls UL-864 Note: The use of output overrides is prohibited in UL-864 Smoke Control Applications.
The i2810 series and the i2920 include output override switches for each relay output.
The output of the module can be directed from program control to manual control. The output can be disabled completely as well. The following describes the actions associated with each position of the override controls: OFF
The output relay is de-energized to an ‘OFF’ state manually by setting the switch to OFF. Programs have no effect on the output when the switch is in this position.
AUTO
The action of the output relay is determined as a direct result of program control.
ON
The output relay is energized to an ‘ON’ state manually by setting the switch to ON. Programs have no effect on the output when the switch is in this position.
i2 Controller Technical Reference
97