Page 87
Wiring Door Switches The maximum length wire you should use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). Some switches have built-in resistors that facilitate Series Parallel connections as shown below:
i2 Controller Technical Reference
81
Page 88
Wiring Motion Detectors Motion detectors are devices that close a switch contact when motion is detected. Wiring is similar to a normal input contact switch input, however, the motion sensor requires an external power supply of 12 VDC or 24 VDC (UL listed under Category Control #APHV). The maximum length wire you should use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). The following shown a typical motion detector circuit:
82
Schneider Electric n
Page 89
Measuring Airflow The following i2 controllers include an airflow sensor: Controller
Sensors
Range
Resolution i2850
1
0-2” W.C. (0-500Pa)
0.005” W.C. (1.25Pa) @23°C (73°F)
i2853
2
0-2” W.C. (0-500Pa)
0.005” W.C. (1.25Pa) @23°C (73°F)
i2865/866
1
0-2” W.C. (0-500Pa) 0.005” W.C. (1.25Pa) @23°C (73°F)
i2865/866-V 1
0-1” W.C. (0-250Pa)
0.0013” W.C. (1.25Pa) @23°C (73°F)
i2885
1
0-1” W.C. (0-250Pa)
0.0013” W.C. (1.25Pa) @23°C (73°F)
i2885-V
1
0-1” W.C. (0-250Pa)
0.0013” W.C. (1.25Pa) @23°C (73°F)
The airflow sensors on the various controllers are located as shown:
Filter
IN
OUT
(HIGH)
CPU
(LOW)
AIRFLOW INPUT
Side marked ‘IN’ Here i2850 Series Airflow Sensor i2 Controller Technical Reference
83
Page 90
i2885 Airflow Sensor
The following steps explain the connection of the airflow sensor: 1. Using a small piece of 1/4” (6.35 mm) I.D. pneumatic tubing, attach the ‘OUT’ side of a 5 micron filter to the input connection (the side marked ‘P1’) of the sensor as shown above. 2. Connect a 1/4” I.D. pneumatic tube from the other end of the filter (the side marked ‘IN’) to the ‘HI’ opening on a VAV box. 3. Connect a 1/4” I.D. pneumatic tube from the output connector (the side marked ‘OUT’) of the airflow sensor to the ‘LO’ opening on a VAV box. Note: Keep tubing to a maximum of 15 inches (380.99 mm) in length. To measure Air Flow, configure an input point with an Electrical Type of Voltage.
84
Schneider Electric n
Page 91
I2865-V/866-V and i2885-V Airflow Sensor
The following steps explain the connection of the airflow sensor: 1. Connect the low pressure side of the velocity sensor to the barbed fitting labeled P1 (LO) on the controller. 2. Connect the high pressure side of the velocity sensor to the barbed fitting labeled P2 (HI) on the controller. Note: Use a maximum length of 4’ (1.2m) FRPE polyethylene tubing or 0.25” (6.34 mm) O.D. and 0.125” (3.175 mm) I.D. Tygon tubing. Do not expose the velocity sensor to moisture. If moisture condensation is a potential problem, orient the tubing and controller so that the barbed fittings are above the lowest part of the tubing to create a moisture trap. To measure air flow, configure an input point with an Electrical Type of Voltage.
i2 Controller Technical Reference
85
Page 92
Smart Sensor Bus Interface The Smart Sensor is a room temperature sensor that includes an LCD or LED display and a 6-button programmable keypad. Several i2 Series Controllers include a special interface port designed for this device.
Note: The Smart Sensor Interface is not listed for UL-864 Smoke Control Operation.
The following controllers include a Smart Sensor interface: i2800 i2850
I2866 i2887 (L)
i2804 i2851 i2865-V i2920 i2810 i2853 i2866-V i2814 i2865 i2867
The interface between the controller and the Smart Sensor Bus consists of three wires connected to positions on the screw-terminal connector typically located on the left side of the Controller module: The controller communicates with the keypad and the display of the Smart Sensor device over a single wire (the PWR connection). The RET line is the return for both the communications line and the internal thermistor. The input signal is the active lead from the Smart Sensor thermistor. Its connection is labeled according to a controller-specific input assignment. This input must be configured as a general Temperature input. The following page illustrates the connections between the Smart Sensor and the controller:
86
Schneider Electric n
Page 93
Smart Sensor Wiring
The controller includes a single Smart Sensor three-pin connector. Each controller numbers the thermistor input differently. However, the input connection always connects to the Smart Sensor IN3 terminal (shown above on the left). Controller
Smart Sensor Thermistor
800 Series 810Series 850 Series 865/866 865/866-V 867 887(L) 920
IN9 IN9 IN5 IN5 IN5 IN5 IN4 IN17 i2 Controller Technical Reference
87