Page 79
Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 70 °F (21 °C) Gauge
1/2 °F (.28 °C) Error
1/4 °F (.14 °C) Error
1/10 °F (.06 °C) Error
#14 2.5 mm2
26,700 ft. 8150 m
13,300 ft. 4000 m
5,300 ft. 1600 m
#16 1.5 mm2
16,700 ft. 5120 m
8,300 ft. 2500 m
3,300 ft. 1000 m
#18 1.0 mm2
10,500 ft. 3200 m
5,200 ft. 1600 m
2,100 ft. 640 m
#20 0.5 mm2
6600 ft. 2000 m
3,300 ft. 1000 m
1,300 ft. 400 m
#22 0.35 mm2
4,100 ft. 1250 m
2,000 ft. 600 m
800 ft. 250 m
Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 100 °F (38 °C) Gauge
1/2 °F (.28 °C) Error
1/4 °F (.14 °C) Error
1/10 °F (.06 °C) Error
#14 2.5 mm2
12,600 ft. 3800 m
6,300 ft. 1900 m
2,500 ft. 760 m
#16 1.5 mm2
7,900 ft. 2400 m
3,900 ft. 1200 m
1,500 ft. 450 m
#18 1.0 mm2
5,000 ft. 1500 m
2,500 ft. 760 m
1,000 ft. 300 m
#20 0.5 mm2
3,100 ft. 950 m
1,500 ft. 450 m
600 ft. 180 m
#22 0.35 mm2
1,900 ft. 580 m
900 ft. 275 m
300 ft. 90 m
Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 150 °F (65 °C) Gauge
1/2 °F (.28 °C) Error
1/4 °F (.14 °C) Error
1/10 °F (.06 °C) Error
#14 2.5 mm2
4,100 ft. 1250 m
2,000 ft. 600 m
800 ft. 240 m
#16 1.5 mm2
2,600 ft. 800 m
1,300 ft. 400 m
500 ft. 150 m
#18 1.0 mm2
1,600 ft. 500 m
800 ft. 240 m
300 ft. 90 m
#20 0.5 mm2
1,000 ft. 300 m
500 ft. 150 m
200 ft. 60 m
#22 0.35 mm2
600 ft. 180 m
300 ft. 90 m
100 ft. 30 m i2 Controller Technical Reference
73
Page 80
Measuring DC Voltages All Universal inputs can be configured to sense DC voltage by setting the Electrical Type to Voltage and connecting the input terminals to a DC voltage source within the range of the module’s input specifications. The following is a schematic representation of the connection:
IN x
+ V -
RET
The plus lead connects to the numbered input terminal, the other to a return terminal. To measure voltage, the pull-up resistor switch associated with this input is usually disabled (OFF). i2885, i2885-V, and i2887(L) Pull-up Resistor Interference When interfacing the i2885, i2885-V and i2887 to a voltage output device, specific information on the transducer may be required. The pull-up resistor of the input circuit will affect the output of the transducer. It is necessary to know the source resistance (Rs) of the transducer and to use the following conversion equation: (ElecValue - (Vref * Rs / (Rs + Rref)) / (Rref / (Rs + Rref))) Example To solve for a voltage input with a transducer having a source resistance of 100 ohms: Vref = 5.12 V Rref = 10K ohms (pull-up built into the i2885, i2885-V) Rs = 100 ohms (ElecValue - (5.12*100 / (100+10000))/(10000/(100+10000))) Thus: (ElecValue - 0.051)/0.990 This conversion adjusts for the correct reading from the transducer. It does not convert to your engineering type.
74
Schneider Electric n
Page 81
2-Wire Voltage Interface The following figure illustrates a 2-wire, current measuring transducer with 0 to 5 volts DC output:
Many voltage output transducers do not operate correctly with a pull-up resistor in the circuit due to their high source resistance. When connected to the input of the controller, there will be a "dead band" at the low end. The input at the controller will always read at least 0.7 Volts. Therefore, the pull-up resistor switch associated with this input is set to disabled (OFF).
i2 Controller Technical Reference
75
Page 82
Sensing Contact Closures (Digital) Digital input points are designed to allow the monitoring of contact closures across an input (contact wired between the input and return). All i2 series inputs and the Smart Sensor input (if applicable) can be configured as Digital Inputs.
IN x Contact Closure RET
To sense a digital input or contact closure, configure an input point with an Electrical Type of Digital. To sense contact closures, the pull-up resistor switch associated with this input must be enabled.
Note: When configuring a Digital point, there is a “Polarity” attribute. If this attribute is enabled, readings are reversed: “On” will occur when the contact is open, and “Off” occurs when the contact is closed.
76
Schneider Electric n
Page 83
Counting Pulsing Signals or Contact Closures Counter inputs are designed to allow the monitoring of digital pulse trains or contact closures across an input just like digital inputs, but they accumulate a total of those closures and act like a counter. All i2 series inputs, except Smart Sensor inputs, can be configured as Counter Inputs. Interfacing is similar to a digital input, however, you set the Electrical Type attribute to Counter instead. To count signals or contact closures, the pull-up resistor switch associated with this input must be enabled. When using an input as a counter, you must take into account the frequency of the input signal being counted. Universal inputs do not allow for very high speed contact counting. These inputs allow counting up to a maximum of 4 Hz or 4 contact closures per second. Minimum Pulse Width The high period of the signal must be at least 125 milliseconds. The low period of the signal must be at least 125 milliseconds.
i2 Controller Technical Reference
77
Page 84
Supervised Inputs All i2 series inputs, except i2885, i2885-V, and i2887(L) and Smart Sensor inputs, can be Supervised inputs. The following drawings depict the three types of supervised inputs that we recommend:
Normally Closed Supervised Inputs (Series) NC Series With this type of input wiring, a resistor is placed in series with the input. When the input contact switch is closed (normal position) the input contact is assumed to be closed. The circuit presents a reading of 10 K ohms at the input.
Circuit Action
Input Senses
Condition
Switch Closed Switch Opened Wire Cut Input Shorted
External Resistance Infinite Resistance Infinite Resistance Zero Ohms
Input contact Closed Input contact Open Input contact Open ‘Violation’ Violation or error
When the input contact is opened the switch opens and an infinite resistance is measured. If the wires to the input contact are cut it also appears as an “input contact open” condition. In this case there would be a input contact open without a valid card swipe or valid keypad entry resulting in an “input contact violation”. Shorting the input causes a zero ohm resistance, which also results in an input contact violation. When configuring for this type of contact select: ElecType: Resistor Type:
78
Supervised NCSeries
Schneider Electric n
Page 85
Normally Closed Supervised Inputs (Series Parallel) NC Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is closed (normal position) the input contact is assumed to be closed. The circuit presents a reading composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ).
Circuit Action
Input Senses
Condition
Switch Closed Switch Opened Wire Cut Input Shorted
External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ohms
Input contact Closed Input contact Open Violation or error Violation or error
When the input contact is opened the switch opens and the value of the parallel resistor is measured. If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero ohm resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:
Supervised NCSerPar i2 Controller Technical Reference
79
Page 86
Normally Open Supervised Inputs NO Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is open (normal position) the input contact is assumed to be closed. The circuit reads the value of the parallel resistor.
Circuit Action
Input Senses
Condition
Switch Closed Switch Opened Wire Cut Input Shorted
External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ohms
Input contact Open Input contact Closed Violation or error Violation or error
When the input contact is opened the switch closes and a reading results that is composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:
80
Supervised NOSeriPar