Page 71
5 . . . . . . Controller Inputs i2 Controller Technical Reference
65
Page 72
66
Schneider Electric n
Page 73
Input Connections Universal Inputs The i2 series controllers include Universal inputs that are unique in that they are software configurable to handle any one of the following five input types: Thermistor Voltage
Counter Supervised*
Digital
* Supervised inputs are not available on the i2885, i2885-V, and i2887(L). Supervised inputs are not to be used in UL864 Smoke Control Applications.
Number of Inputs The following table lists the input complement of each controller.
Controller
Inputs
Controller
Inputs i2608
8 i2865
4 + Smart Sensor i2624
24 i2865-V
4 + Smart Sensor i2800
8 + Smart Sensor i2866
4 + Smart Sensor i2804
8 + Smart Sensor i2866-V
4 + Smart Sensor i2810
8 + Smart Sensor i2867
4 + Smart Sensor i2814
8 + Smart Sensor i2885
2 i2850
4 + Smart Sensor i2885-V
2 i2851
4 + Smart Sensor i2887(L)
3 + Smart Sensor i2853
4 + Smart Sensor i2920
16 + Smart Sensor
Universal Input Specifications The Universal inputs for most i2 controllers accept 0-5VDC. The inputs for the 810 Series accept 0-10VDC. The maximum line resistance is 4700 ohms. The maximum short circuit current is 0.33mA for i2920 inputs and 0.512mA for all other inputs.
i2 Controller Technical Reference
67
Page 74
Input Wiring The input terminations are typically located on the left of the module, however, the i2624 includes inputs on both the left and right sides of the module. Connection is via screw terminal. The inputs are labeled IN1 through INx and are typically followed by a connection labeled RET for the input signal return. It is recommended that a separate return wire be used for each input. The following pages include diagrams detailing each module’s input connections:
68
Schneider Electric n
Page 75
865/866
18 RET 19 IN14 20 RET 21 IN2 22 RET 23 IN3 24 IN4 eeees9e9e9d
865/866-V
1 IN4 2 IN2 3 RET 4 IN3 5 IN4 6
SsSseeeg9
RET
867
IN1 IN2 IN3 IN4 RET
1° 23 4 5
Sseseese°9
885
IN1 9
RET 10 IN2 11
885-V
IN1 4 RET 5
920
7 RET 8 IN1 9 IN2 10 RET 11 IN3 12 IN4 13 RET 14 IN5 15 IN6 16 RET 17 IN7 18 IN8 alin
3
2| IN2 RI IN: IN4
19 RET 20 IN9 21 IN 10 22 RET 23 IN 11 24 IN 12 25 RET 26 IN 13 27 IN 14 28 RET 29 IN 15 30 IN 16
|sessesssessseq |sssesssssseq i2 Controller Technical Reference
69
Page 76
Wiring Concerns Do not remotely ground any part of the sensor wiring. Remote grounds connected to the return terminals could make the controller operate incorrectly or damage the equipment. The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly. For reliable input operation, follow these input wiring guidelines: ƒ
Never lay wires across the surface of the printed circuit board.
ƒ
Wires should never be within 1 in. or 25 mm of any component on the printed circuit board.
ƒ
Use shielded input wire. Do not use the shield as the signal return wire.
ƒ
Terminate the shield of the input wires at one end of the run only, preferably at the end where your controller is located.
ƒ
Be careful when stripping wire not to drop small pieces of wire inside the cabinet.
ƒ
Don’t run your input wiring in the same conduit with AC power.
ƒ
Don’t run your input wiring in the same conduit with your output wiring. CAUTION: Do not externally ground any input connected to the controller. This may damage the unit. Do not connect inputs while the controller is running.
70
Schneider Electric n
Page 77
Input Pull-up Resistor Selection The i2 series (except the i2885, i2885-V and i2887(L)) inputs can be configured to include internal pull-up resistors. In some measuring instances it is desirable that there be no pull-up resistor. Instead of physically removing or cutting the resistor off the printed circuit board, the input module includes a pull-up resistor selection switch. When the switch is placed in the enabled ON position, the pull-up resistor is connected to the input line. When the switch is moved to the disabled OFF position, the pull-up resistor is removed from the circuit. The i2885 and i2885-V have no selection switch. Their pull-up resistors are permanently enabled. The following is a schematic representation of the switch and its associated pull-up:
Input Pull-up Resistor Switch Location The i2 Series (except the i2885, i2885-V and i2887(L)) pull-up selection switches allow you to select whether or not you want a pull-up resistor in the circuit. The small multiposition resistor selection switch modules are located in different places depending on the particular model. Some are accessible through an access window on the module case beside the input screw terminals. Others are located on the PC board behind the cover (i2867) or close to the input terminals (i2885/886 and i2865-V/866-V). These switch modules are commonly called “DIP Switches” and require a small object such as the tip of a pen or a small screwdriver to operate them. Each switch position acts as a “slide switch”. Pressing the raised slide marker to the right side marked “on” closes or enables the switch. To open or disable the switch position, press the slide marker over to the left or “off” side.
i2 Controller Technical Reference
71
Page 78
Measuring Temperature All of the i2 series inputs may be configured to sense temperature by configuring one of the controller’s inputs appropriately. This is done by setting the Electrical Type to either ACC Temp (DEG F) or ACC Temp (DEG C). Connect a resistive thermistor sensor to that input terminal. The following is a schematic representation of the connection:
IN x Thermistor RET
One lead connects to a numbered input terminal, the other to a return terminal. To measure temperature, the pull-up resistor switch associated with this input must be enabled (ON). When the input point is configured as a temperature input, the controller utilizes a look-up table to convert from a voltage reading to a temperature reading in degrees Fahrenheit or Celsius.
CAUTION: Never apply a voltage to a thermistor - doing so alters the thermistor’s accuracy and reliability. We recommend replacing any thermistor that has had any sort of voltage applied to it.
Maximum Wire Runs for Thermistors To keep thermistor errors minimal, limit the length of wire runs to the maximum for the gauge wire you select. The following two pages include three tables that indicate the maximum length runs for wires of various gauges to keep errors within certain temperature limits when using thermistor elements.
72