Andover Infinet i2 Controller Technical Reference: RS-485 Infinet

Pages 57 to 70 of 190, from Andover Infinet i2 Controller Technical Reference

The original document is the PDF (8.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls i2850 and Schneider i2850

Page 57

4 . . . . . . RS-485 Infinet i2 Controller Technical Reference

51

Page 58

52

Schneider Electric n

Page 59

Introducing Infinet Infinet is a high-performance, token-passing local area network (LAN) field bus that is built into all i2 controllers. The protocol supports a combination of shared resource and peer-to-peer communications, where more than one controller can be the network master at any given time. Electrically similar to standard RS-485, Infinet is physically wired using two-conductor shielded twisted pair cable that transmits data at a rate of up to 19.2 Kb/sec. Although Infinet utilizes a token-passing data access system, it allows for a combination of daisychained bus and star topologies to be implemented. Infinet II networks support a mix of i2 and older Infinet I devices. Infinet networks only support Andover Continuum Infinet controllers. You cannot mix Infinet and other RS-485 type controllers (i.e., BACnet or LONMark) on the Infinet network wiring. UL-864 Note: The Infinet meets NFPA Style 3.5 supervision requirements.

Infinet Cable Specifications Cables used to form the Infinet should conform to the following specifications: Wire Size: Cable Type: Shield: Nominal Impedance: Velocity of propagation: Capacitance:

24 AWG Twisted-pair, copper wire, tinned Braid 120 Ω 78% <12.5 pF/ft between conductors and < 22 pF/ft between the conductor connected to ground and the next conductor.

Maximum Cable Length Cable lengths of up to 4,000-ft (1,220 m) daisy chained from Infinet controller to Infinet controller on one arm of a star are supported. After 4,000 ft (1,220 m), a signal repeater (i2200) is required to add more nodes to the network or further extend the cabling. Using an i2210 repeater allows you to extend the length of Infinet with fiber optic cable, recommended for running cable between buildings and through noisy environments.

i2 Controller Technical Reference

53

Page 60

Maximum Number of Devices The Infinet supports a maximum of 127 nodes overall. Each controller represents a single node on the network. Display devices such as Infinet I DCX250 devices represent a node as well.

Infinet Network Configurations Infinet allows for both daisy-chained and star network topologies to co-exist. In all Infinet configurations, a network controller or gateway can be used to initiate the Infinet. Note: In this section’s network illustrations, the parent network controller can be a suitably equipped CX controller, a Continuum NetController, or a bCX1 9640.

54

Schneider Electric n

Page 61

Daisy Chain Configuration Daisy chained configurations consist of a single cable that is routed to the first controller then to the next, and so on. A simple daisy chain Infinet is illustrated below:

In this configuration you can have as many as 127 controllers or “nodes” on the network. There is a limitation, however, of 4000 feet (1200 m) before some sort of repeater is needed. Unlike other RS-485 networks, no terminators are required for the standard Infinet.

i2 Controller Technical Reference

55

Page 62

Daisy Chain Configuration with i2200 Repeater Daisy chained configurations that extend beyond the maximum cable length must include an Infinet Repeater.

In this configuration, only one port of the four-port repeater is connected. The i2200 acts as a simple signal booster-repeater to allow distances of greater than the maximum cable length.

56

Schneider Electric n

Page 63

Star Configuration with i2200 Repeater The i2200 repeater allows you to connect up to four additional Infinet network spurs to a single Infinet source. In this way, a star network configuration is supported. A simple twospur star configuration is illustrated below:

1

ACPOWER

1

2 N

115-230VAC 45VA 50/60 HZ

ACPOWER 2 N

115-230VAC 45VA 50/60 HZ

3 L

3 L

SERVICE PORT SERVICE PORT

RD

INFINET 4 +

RD

INFINET 4 +

TD

5 6 SHLD

TD

5 6 SHLD

+

UNIVERSAL INPUTS

+

UNIVERSAL INPUTS

-

-

7 RET 8 IN 1

7 RET

OFF ON

9 IN 2

8 IN 1

11 IN 3

1 2 3 4 5 6 7 8

10 RET 11 IN 3 12 IN 4 13 RET

1 2 3 4 5 6 7 8

10 RET

OFF ON

9 IN 2

12 IN 4 13 RET

*

14 IN 5

*

14 IN 5 15 IN 6

.

-

15 IN 6

#

.

-

#

16 RET 17 IN 7

16 RET

18 IN 8

17 IN 7 18 IN 8

19 RET 20 IN 9

19 RET

21 IN 10

20 IN 9

OFF ON

22 RET

21 IN 10

OFF ON

22 RET

9 10 11 12 13 14 15 16

23 IN 11 9 10 11 12 13 14 15 16

23 IN 11 24 IN 12 25 RET 26 IN 13

24 IN 12 25 RET 26 IN 13 27 IN 14 28 RET

27 IN 14

29 IN 15

28 RET

30 IN 16

29 IN 15 30 IN 16

31SPWR

CPU

32 RET 31SPWR

33 IN 17

CPU

32 RET

SMART SENSOR

33 IN 17

RESTART

SMART SENSOR RESTART

AC POWER 24 VAC 25 VA 50/60 HZ

AC POWER 24 VAC 25 VA 50/60 HZ

1

3 L

-

3 L

-

2 N

1 2 N

+ DC POWER 12 - 28 VDC 15 W

+ DC POWER 12 - 28 VDC 15 W

4SPWR 5 RET

1 2 3 4 5 6 7 8

8 IN 1 9 IN 2

1 2 3 4 5 6 7 8

1

OFF ON

7 RET

7 RET

2

45

8 IN 1

1

44

9 IN 2

43

10 RET

42

11 IN 3

2

41

12 IN 4

10 RET 11 IN 3

3

40

12 IN 4 13 RET 3

14 IN 5 4

15 IN 6 16 RET

4

17 IN 7

45 2

14 IN 5 15 IN 6 16 RET

36

17 IN 7

35

18 IN 8

44

41

42

40 39 3 4

38 37 36

4

35 34

UNIVERSAL INPUTS RESTART

UNIVERSAL INPUTS RESTART

1

2

43

3

13 RET

39 38 37

34

18 IN 8

1

OFF ON

6 IN 9

5 RET 6 IN 9

DIGITAL OUTPUTS CONTAC T RATING 24VAC , 3A 30V DC , 3A

SMART SENSOR DIGITAL OUTPUTS CONTAC T RATING 24VAC , 3A 30V DC , 3A

SMART SENSOR 4SPWR

5

5

CPU 33

CPU

6

33 6

5

32

5

30

30 6 7

RD

7

INFINET 19 +

26 25

8

24

20 -

8

29

7

26

28

SERVICE PORT

27

27

21SHLD

6 7

RD

29 28

SERVICE PORT

32 31

TD

31

TD

INFINET 19 +

25

8

24

20 -

8

21SHLD

23 22

23 22

+

+

-

G H I)(

G N D O U T6 R E T O U T7 R E T

G N D

ANALOG OUTPUTS

01 -0V,05 -mA

R E T

O U T6 R E T

U S

O U T7 R E T W PR NI5

G N Y R E N O P E G M T N A E E Q P U M IE N T

NI2

OUT

O W L)(

DIGITAL OUTPUTS

ANALOG OUTPUTS

C

U S

G N Y R E N O P E G M T N A E E Q P U M IE N T

58B2

MODEL S/N DATE DAMPERCONTROL

NI3

OUT1/OUT2

NI4

OUT1/OUT2

Thsi equpimentcompeilswh ti part15ofh teFCCruels. Operato i nsi sube j ct to the foo l wn i g two condtions: (1) Thsi devciemaynotcauseharmfuln iterference. tre frencerecevied, (2) Thsi devciemustacceptanynie nucin d lg in eftirncehtatmaycauseundersdi opo ea n irt.

SMART SENSOR

UNIVERSAL INPUTS

R E T

S/N DATE DAMPERCONTROL

NI4

01 -0V,05 -mA

R E T NI1

58B2

R E T

UNIVERSAL INPUTS

R E T NI3

24VAC,0 5.Amp

G N D

C

MODEL

NI1 NI2

Thsi equpimentcompeilswh ti part15ofh teFCCruels. Operato i nsi sube j ct to the foo l wn i g two condtions: (1) Thsi devciemaynotcauseharmfuln iterference. (2) Thsi devciemustacceptanynie tre frencerecevied, nucin d lg in eftirncehtatmaycauseundersdi opo ea n irt.

SMART SENSOR

R E T

AR I FLOW INPUT

10VA,506/0HZ

O U T3 O U T5

DIGITAL OUTPUTS

24VAC,0 5.Amp

G N D

N I

24V

O W L)(

AR I FLOW INPUT

O U T4

O U T5

G H I)(

CPU

OUT

N I

CPU 24V

10VA,506/0HZ

O U T3 O U T4

W PR NI5

INFINET PORT

D L EH S I

INFINET PORT

D L EH S I

DAMPER RESET

DAMPER RESET

Although this configuration provides a multiple-leg star with greater distances, you can still have only as many as 127 controllers or “nodes” on the network.

i2 Controller Technical Reference

57

Page 64

Infinet Between Buildings Using the i2210 The i2210 repeater allows you to convert the Infinet RS-485 signal into light waves using fiber optics. Two i2210 repeaters used together provide a noise-immune, lightningprotected method of extending the Infinet between buildings. A simple fiber optic buildingto-building Infinet configuration is illustrated below:

AC POWER 24 VAC 25 VA 50/60 HZ 1 -

2 N 3 L

+ DC POWER 12 - 28 VDC 15 W DIGITAL OUTPUTS CONTAC T RATING 24VAC , 3A 30V DC , 3A

SMART SENSOR 4SPWR 5 RET

1

OFF ON

6 IN 9

1 2 3 4 5 6 7 8

7 RET 8 IN 1 9 IN 2

45 2

1

44

2

41

43 42

10 RET 11 IN 3

3

40

12 IN 4

39

13 RET 3

14 IN 5 4

15 IN 6

38 37 36

16 RET 4

17 IN 7

35 34

18 IN 8 UNIVERSAL INPUTS RESTART

5

CPU 33 6

5

32 31

TD

30 6

29

7

26

7

RD

28

SERVICE PORT

27

INFINET 19 +

25

8

24

20 -

8

21SHLD

23 22

1

ACPOWER 2 N

115-230VAC 45VA 50/60 HZ

3 L

SERVICE PORT

RD

INFINET 4 +

TD

5 6 SHLD

+

UNIVERSAL INPUTS

-

7 RET 8 IN 1 OFF ON

9 IN 2

1 2 3 4 5 6 7 8

10 RET 11 IN 3 12 IN 4 13 RET 14 IN 5 15 IN 6

*

.

-

#

16 RET 17 IN 7 18 IN 8

+

19 RET

INFINET PORT

G H I)(

D L EH S I

22 RET

9 10 11 12 13 14 15 16

23 IN 11 24 IN 12 25 RET

O U T3 O U T4 O U T5 G N D

DIGITAL OUTPUTS

24VAC,0 5.Amp

G N D O U T6 R E T

27 IN 14

O U T7

28 RET

R E T W PR

29 IN 15

NI5

ANALOG OUTPUTS

01 -0V,05 -mA

R E T

C

G N Y R E N O P E M G T N E A E Q P U M IE N T

U S

58B2

MODEL

NI1 NI2

CPU

32 RET

Thsi equpimentcomp eilswh ti part15ofh teFCCruels. Operato i nsi sube j ct to the foo l wn i g two condtions: (1) Thsi devciemaynotcauseharmfuln iterference. tre frencerecevied, (2) Thsi devciemustacceptanynie nucin d lg in eftirncehtatmaycauseundersdi opo ea n irt.

SMART SENSOR

R E T

30 IN 16 31SPWR

O W L)(

AR I FLOW INPUT

24V

10VA,506/0HZ

OFF ON

26 IN 13

OUT

N I

CPU

20 IN 9 21 IN 10

UNIVERSAL INPUTS

S/N DATE

R E T

DAMPERCONTROL

NI3

OUT1/OUT2

NI4

33 IN 17

DAMPER RESET

SMART SENSOR RESTART

AC POWER 24 VAC 25 VA 50/60 HZ 1 -

2 N 3 L

+ DC POWER 12 - 28 VDC 15 W DIGITAL OUTPUTS CONTAC T RATING 24VAC , 3A 30V DC , 3A

SMART SENSOR 4SPWR 5 RET

1

OFF ON

6 IN 9

1 2 3 4 5 6 7 8

7 RET 8 IN 1 9 IN 2

45 2

1

44

2

41

43 42

10 RET 11 IN 3

3

40

12 IN 4

39

13 RET 3

14 IN 5 4

15 IN 6

38 37 36

16 RET 4

17 IN 7

35 34

18 IN 8 UNIVERSAL INPUTS RESTART

5

CPU 33 6

5

TD

+

32

-

31

D L EH S I

29

7

26

7

28

SERVICE PORT

INFINET 19 + 20 21SHLD

27

25

8

24 8

23 22

INFINET PORT

G H I)(

OUT

N I

CPU

O W L)(

AR I FLOW INPUT

24V

30

RD

6

10VA,506/0HZ

O U T3 O U T4 O U T5 G N D

DIGITAL OUTPUTS

24VAC,0 5.Amp

G N D O U T6 R E T O U T7 R E T W PR NI5

ANALOG OUTPUTS

01 -0V,05 -mA

R E T

Thsi equpimentcomp eilswh ti part15ofh teFCCruels. Operato i nsi sube j ct to the foo l wn i g two condtions: (1) Thsi devciemaynotcauseharmfuln iterference. tre frencerecevied, (2) Thsi devciemustacceptanynie nucin d lg in eftirncehtatmaycauseundersdi opo ea n irt.

SMART SENSOR

R E T

C

U S

G N Y R E N O P E M G T N E A E Q P U M IE N T

58B2

MODEL

NI1 NI2

UNIVERSAL INPUTS

R E T

S/N DATE DAMPERCONTROL

NI3

OUT1/OUT2

NI4

DAMPER RESET

Although this configuration provides noise immunity with greater distances, you can still have only as many as 127 controllers or “nodes” on the network.

58

Schneider Electric n

Page 65

Infinet Network Shielding The shield within the Infinet cable is essential to protect the network from electromagnetic interference and harmful transient voltage spikes. A properly applied shielding strategy is required for reliable communications. Each device on the Infinet network must be connected to the shield. To facilitate this, each controller is provided with a three position connector that includes a single connection for the shield. +

Shield Infinet Cable

- SHLD

Shield

White White Black

Infinet Cable

Black

To work properly, the shield must be connected to Earth ground. This connection must occur at only one point along the entire Infinet network. The shield connection within an i2 Series controller is not tied directly to ground. It is capacitively coupled to ground. The shield connection from the Infinet source controller (CX, NetController, or bCX1 9640) is internally directly connected to ground. The CX, NetController, or bCX1 9640 must then be properly connected to Earth ground to provide this reference point. Refer to the discussion of what a good Earth ground is on page 40 of this manual.

Shield Issues with Repeaters Infinet shielding is connected to both types of repeaters. The i2200 repeater shield (Input port #1) is connected the same as any other i2 controller node on the network. Its shield connection is not directly connected to ground. All shield connections for the four additional ports (port #2-5) the repeater provides are electrically connected together and to the Earth ground connection of the unit. A different issue occurs with the i2210. The i2210 fiber repeater allows a noise-free (electrically isolated) optical connection between two points. It therefore breaks the shield connection by providing no electrical signal to a companion i2210. The i2210 that is electrically wired to the Infinet is connected to the shield like any i2 controller. To provide a ground point for remote Infinet through the use of a fourth terminal labeled GND. Connecting the shield wire of the remote Infinet spur to this GND pin provides the Earth ground point. The diagrams on the following page illustrate the proper way to connect the shield for both sides of a two-building fiber isolated Infinet.

i2 Controller Technical Reference

59

Page 66

The shield of the source Infinet (the one electrically connected to the CX, NetController, or bCX1 9640) is tied to Earth ground at the CX, NetController, or bCX1 9640. Connect the shield to the shield pin of the i2210:

The shield of the extension Infinet (the one in the remote building that is isolated via fiber connection) is tied to Earth ground at the i2210 via the GND connection:

60

Schneider Electric n

Page 67

Controller Infinet Connections The Infinet port is typically found on the left hand side of the controller. On the i2865/866, i2865-V/866-V, i2867 and the i2887 it is found elsewhere. It may be labeled “Infinet” or simply “RS-485”. Refer to the overview diagrams found in the Introduction section of this manual for the exact location of the connector. The pin connections are shown below:

Connection to the cable is done by inserting a stripped conductor into the opening on a screw terminal position and tightening the associated screw to secure it in place. When the network is connected to more than one device, it is done so in a daisy chain manner as shown below: +

Shield Infinet Cable

- SHLD

Shield

White White Black

Infinet Cable

Black

* Wire colors are included for clarity. The colors of your cable may vary. However, make sure that all Infinet connections are consistent on their connections.

i2 Controller Technical Reference

61

Page 68

Infinet Repeater Connections The physical length of the Infinet wiring may be extended by utilizing either the i2200 or i2210 repeaters.

i2200 Connections The i2200 is a five-port RS-485 repeater/hub that includes a fifth port that is an RS-485to-RS-232 converter for use with short haul modems or other RS-232 communications devices. The multiple ports allow you to construct a star network configuration.

Baud Rate The communications Baud Rate is determined by the small 8-position switch on the front panel. Typically, for Infinet use, this is set to 19200. All ports (input RS-485, four output RS-485, and the RS-232 ports) communicate at the switch setting.

RS-232 The RS-485 to RS-232 conversion port is provided in order to facilitate extending the Infinet using an RS-232 device such as a short-haul modem. A typical modem configuration is illustrated below: UL-864 Note: RS-232 connection is not intended for use in UL-864 Smoke Control applications.

62

Schneider Electric n

Page 69

i2210 Connections The i2210 is a three-port hub that can connect up to 127 Infinet controllers. You can set up i2210s in two possible configurations: Point-to-point configuration Daisy chain configuration Fiber Cable Recommendations: 62.5/125 Duplex Glass Fiber with ST-style connector max. attenuation allowable: 13.5dB Note: When using repeaters. Make sure that the communication Baud Rate is set to the same speed as the network. For standard Infinet this will typically be 19200.

i2 Controller Technical Reference

63

Page 70

When you use the daisy chain configuration, you can have an Infinet on the Infinet port of each i2210 which allows you to expand the Infinet.

64

Schneider Electric n