Andover Infinet i2 Controller Technical Reference: Power Connections

Pages 43 to 56 of 190, from Andover Infinet i2 Controller Technical Reference

The original document is the PDF (8.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls i2850 and Schneider i2850

Page 43

3 . . . . Power Connections i2 Controller Technical Reference

37

Page 44

38

Schneider Electric n

Page 45

Power Connections The i2 series controllers are operated via an external power source. An internal power converter creates the necessary DC voltages to supply the microprocessor circuitry. The following lists indicate the primary power sources for each controller. As indicated, some of the controllers listed include multiple power source choices.

Controller Power Options Controller i2600 Series i2800 Series i2810 Series i2850 Series i2865/866 i2865/866-V i2867 i2885 i2885-V i2887 i2887-L i2920

24VAC X X X X X X X X X X

12-28VDC X X X

115-230AC

X (separate models for each) X

Detailed connection diagrams may be found on the next few pages.

i2 Controller Technical Reference

39

Page 46

24VAC Connections When using a 24V AC source, this power supply is connected via three terminals located on the power connector. The unit should receive power from its own independent, un-switched circuit. The power connector is always located on the left side of the module case (as viewed from the front) and consists of three screw terminals. The 24 VAC connection consists of both terminals from the secondary of a power-line to 24 VAC transformer. Connection to the controller is via a screw type connector. The ground wire to the controller should not exceed 12” in length and it must be connected to a good earth ground.

Powering Multiple i2 Series Controllers Unless all the i2 Series controllers you intend to power are resident in the same cabinet, it is imperative that you use a separate transformer for each controller. When you attempt to power multiple remotely located controllers from a single power source the voltage drop caused by the current draw per controller (realize that the actuator may be using power from the controller as well) results in marginal operation and in most cases prevents proper communications between controllers. UL-864 Notes: All controllers used for UL864 Smoke Control applications must be powered by separate transformers. The optional varistors shown on the primary side of each 24VAC connection drawing are not to be used for Smoke Control applications.

CAUTION: Make sure that 24 VAC is not connected to the power cable while you are wiring the controller, or you could receive an electrical shock that is life-threatening.

40

Schneider Electric n

Page 47

The 24VAC connections are as follows: i2600 Series i2800 Series i2810 Series i2850 Series i2865/866 24VAC Connection i2 Controller Technical Reference

41

Page 48

i2865-V/866-V 24VAC Connection 24 VAC Step-Down Transformer

X1 10 24VAC

AC Line Power

11 X2

Optional Varistor (Choose a voltage rating appropriate to the input voltage applied. For example, 130V or 250V)

i2867 24VAC Connection

42

Schneider Electric n

Page 49

i2885 24VAC Connection i2885-V 24VAC Connection

24 VAC Step-Down Transformer

X1 10 24VAC

AC Line Power

11 X2

Optional Varistor (Choose a voltage rating appropriate to the input voltage applied. For example, 130V or 250V)

i2 Controller Technical Reference

43

Page 50 read from a scan by OCR; it may hold reading errors

i2887 24VAC Connection

CAUTION. DISCONNECT SWITCH ‘e Yy (Da

1b VOVAIE

I [« O Ke @ © ©

>

FT a = ‘OUTS é

|] tos Bee Gere SsbB RBE EN IP RS-485 UNIVERSAL INPUTS: TRIAC OUTPUTS 2TTVAC, 3A

24 VAC Step-Down Transformer x1 = v AC Line . tT Power

Optional Varistor choose a voltage rating appropriate to the input voltage applied. i.e 130V or 250V

44 Schneider Electric

Page 51

12 - 28 VDC Connection Some i2 series controllers can be powered by an external 12-28 VDC source. This power supply is connected via terminals located on the Power connector.

The DC connections are as follows: i2600 Series i2800 Series i2810 Series i2 Controller Technical Reference

45

Page 52

115 - 230 VAC Connection The i2887-L and the i2920 controller are the only controllers powered by an external AC mains source. MODEL i2887-L-115 i2887-L-230 i2920 i2920 AC Connection i2887-L AC Connection

46

Schneider Electric n

POWER 115 VAC , 50 or 60 Hz 230 VAC , 50 or 60 Hz 115-230 VAC , 50 or 60 Hz

Page 53

CAUTION: The AC power wiring should be connected by a qualified technician per applicable electrical codes. In the United States, wiring must conform to the National Electrical Code NFPA 70. Do not connect the power wiring with power applied.

i2 Controller Technical Reference

47

Page 54

Battery Backup Connection & Replacement If the power source is interrupted during operation, backup power for the internal controller state memory is provided by a coin-style 3 Volt Lithium battery. This battery can maintain backup status for typically 5-years. To access the battery holder, the module cover must be removed. The cover is secured via two force fitting plastic tabs. To remove the cover, gently depress the two cover latches simultaneously while lifting the cover. A typical controller cover is shown below:

Once the access cover is removed, the printed circuit board is accessible. The following illustrates the location of the battery holder on the i2850 in relation to the board. Each controller uses a similar holder:

48

Schneider Electric n

Page 55

During shipment, an insulating plastic tab is inserted under the clip on the battery to prevent it from draining prior to installation. To activate the battery, this tab must be removed. Should it become necessary to replace the battery, the battery is placed in a coin-style holder. The battery used in the i2 series varies per controller. The following table indicates the replacement battery type:

Controller Battery Types Controller

Battery

Controller

Battery

Controller

Battery i2600 Series

CR 1225 i2865/866

CR 1225 i2885-V none i2800 Series

CR 1225 i2865-V/866-V

CR 1225 i2920

BR 2325 i2810 Series

CR1225 i2867

CR 1225 i2850 Series

CR1225 i2885 none

CAUTION: There is danger of explosion if the battery is incorrectly replaced. Replace only with the same or equivalent type recommended above. Replacement of batteries is to be performed by a trained technician. Dispose of used batteries according to manufacturer’s instructions.

i2 Controller Technical Reference

49

Page 56

Building Ground Requirements Be sure that all equipment from Schneider Electric is grounded to true Earth ground. True Earth ground protects the equipment from transients and other power surges in the area. We cannot guarantee that the controller system will operate as documented without a properly grounded installation. An example of a sub-standard ground is a galvanized steel cold water pipe. As the pipe corrodes, it does not act as a true ground. The corrosion acts as an insulator, raising the potential of the pipe with respect to the ground. When lightning strikes in the area of the installation, it drastically changes the potential of the Earth. Since properly grounded Andover Continuum units respond to changes in potential more rapidly than poorly grounded electrical systems, a poorly grounded building tries to reach ground through the Andover Control system. The surge of current can destroy electronic components on the controller board. Surges of much lower potential than lightning also impact the reliability of the equipment.

Inspecting the Ground Be sure to have your grounds inspected before you begin the installation process to be sure your municipality follows the National Electrical Code. Many municipalities do not follow the code and often have substandard electrical grounds. Check your ground as follows: Inspect the building power distribution panel for Earth-ground termination. If the ground termination is any of the following, it is not adequate and must be corrected: Does not exist. Is connected to a corroded or galvanized pipe. Is connected using a small gauge wire (less than 14 AWG). Be sure your Andover Continuum cabinet is connected to the ground with a copper conductor that terminates at the distribution panel.

Lightning Protection Although metal oxide varistors are built into the board to protect against power line transients, this protection is not sufficient to protect against lightning. Lightning arresters are required at each point where Infinet cables enter or exit a building. The following lightning arrester is recommended: Schneider Electric # 01-2100-299, Two pair gas tube lightning arrester UL-864 Note: For Smoke Control applications, connections between buildings are to be handled using the i2210 Fiber Optic repeater. The use of lightning arrestors are not allowed.

50

Schneider Electric n