The text of a manual · part 5 of 20
Andover Infinet i2 Controller Technical Reference: Mechanical Installation, pages 34 to 42
Pages 34 to 42 of 190, from Andover Infinet i2 Controller Technical Reference
The original document is the PDF (8.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Andover Controls i2850 and Schneider i2850
Page 34
28 i2887 Mechanical Dimensions
The overall dimensions of the unit are:
f
1.15
[ 29.3 | !
Raf.f.f.f. ff f fh fi fiiififl fl fl oo
I
ITT en
HE
HH
| CAUTION \6/ | MAY BE REQUIRED TO DE-ENERGIZE THIS ® toad ‘a : | 4 | el | 4.40 5 | [111.8 | 4.00. | [ 101.6 | ! 1® DICE : g N= ORC IOMOROROROROIC | ORORORORORG) == 42 | 201556) [Sooooo eee F=f Berbera seisse Bim \ -O RS-485 UNIVERSAL INPUTS TRAC OUTPUTS 2TIVAC, 3A | ox _.20 J , 20 3x 0-180 [ 5.1 | [5.1 | [ 4.6 | 287 MTG HOLES | 60.1 | ~ 4.73 _ | 120.1 | eg 5 | 130.3 | Schneider Electric
Page 35
i2887-L (open class) Mechanical Dimensions
The overall dimensions of the unit are:
i2 Controller Technical Reference
29
Page 36
i2200, i2210 Repeater Mechanical Dimensions i2200 i2210
UL-864 Note: i2200 must be surface mounted when used in UL-864 Smoke Control applications.
30
Schneider Electric n
Page 37
XP Module Mechanical Dimensions
All /O Modules | 7.10 (180) | oe Lg 678 (172)
- ST yf oe eee eG S| 3.21 (82)
2.55
(65)
(0 | 0 Ulm |
0.33 ol
4X @.187 (5) THRU
External Display Module
0 = 5.00
TA Senin nae, *. 120.1
4.73
[299] [60.4 J aoe _ @& (©) & - [178.1 | D) [184.2 |
O@® @ ||] 7.25 DOOLNY oO op Wo) 'e® “Te
L [126 | [4.6 | 50 .180 (4) MTG HOLES i2 Controller Technical Reference
31
Page 38
Actuator Installation i2865/866/885 Installation Attach the controller to the VAV box using the following procedure: 1.
Loosen the nuts that attach the mounting U-bolt to the actuator motor.
U-bolt clamp with nuts
Manual override button 2.
Manually, position the damper blade at its fully closed position.
3.
With the manual override button depressed, rotate the actuator clamp of the controller motor to approximately 1/16 - 1/8” between the actuator stop and clamp, depending on seal design. The rotation direction to turn depends on Stop the setting of the rotation direction switch on the controller. The default direction to position the clamp would be counter-clockwise (full ‘-‘ position). See the other side of this sheet for details on the rotation direction switch.
4.
Position the unit at the proper perspective on the VAV box. Carefully insert the shaft of the VAV unit into the opening of the actuator motor through the U-bolt. Make sure the controller is flush with the VAV housing. Finger-tighten the nuts to secure the shaft to the actuator.
5.
Insert a #8 self-tapping screw through the mounting slot to secure the controller to the housing. Position the screw in the center of the slot. Do not over-tighten. The controller should move freely on this screw.
865/866
885
#8 Self-tapping screw secures the unit to the housing
6.
Tighten the U-Bolt to the shaft using an 8 mm wrench.
Note: For information about Programming the Actuator, see “Actuator Programming and Use” in Section 8. 32
Schneider Electric n
Page 39
Actuator Installation i2865-V/866-V/885-V Installation Attach the controller to the VAV box using the following procedure: Refer to the following illustration to install the actuator.
i2 Controller Technical Reference
33
Page 40
Procedure Attach the controller to the VAV box using the following procedure: 1. Check the mounting location for the Andover Continuum i2 865-V/866-V/885-V controller. The unit is typically mounted with the controller extending down or to the right from the damper shaft. However, the controller can be operated in any position within the vertical plane. Note: Installing the controller to the right (with the barbed fittings pointing down) will help to prevent condensate from migrating into the on-board velocity sensor. With a downward extension, the available area around the damper shaft must measure 6” (160mm) down from the lower edge of the shaft, 4.5” (120mm) to the right, 1.5” (40mm) to the left and 1.75” (45mm)above the shaft. Ensure the location allows enough clearance for servicing. The actuator is designed to mount over a ½“ (12.7 mm) diameter shaft with a minimum of 2.5” (63.5mm) of exposed shaft. If the damper shaft is less than ½” (12.7mm) an adapter, which can be purchased from Schneider Electric, may be required. The 865/866/885-V controller will not work with larger damper shafts. 2. If the exposed damper shaft is less than 2” (51mm) but at least 1” (25.4mm) long, move the two damper shaft mounting screws to the alternate lower damper shaft positions (see illustration on previous page). 3. Select the mounting bracket location that will provide the most stability for the operation of the actuator. Position the mounting clip in the desired mounting bracket. Do not insert the clip more than half-way into the bracket. This will allow the clip and back of the actuator to properly align with the VAV box. 4. Rotate the VAV damper shaft by hand to the fully closed position. Note whether the damper is rotated clockwise (CW) or counter-clockwise (CCW) to close.
5. Slip the controller over the damper shaft. Position the actuator and, using a selftapping sheet metal screw, secure the mounting clip to the VAV box. 6. Press the actuator toward the box until the actuator comes in contact with the VAV box, or the mounting clip snaps into the bracket, or the back of the actuator comes into contact with the VAV box. 7. Press and hold the red actuator clutch release and rotate the actuator to a nearly closed position, the 5° index mark if the damper shaft was rotated CCW to close (step 5). Rotate the actuator collar to the 85° index mark if the damper shaft was rotated CW to close (step 5).
34
Schneider Electric n
Page 41
8. Tighten the two damper Allen screws using the supplied hex wrench. The minimum torque required to secure the controller to the damper shaft depends on the shaft material. The maximum torque for the socket screws at 30 inch-pounds (3.4 Nm). Note: The damper shaft should rotate freely when the clutch is released. If it does not, the actuator may not be properly aligned with the damper shaft – it may be necessary to repeat steps 4 though 9 using a new orientation.
9.
If the damper does not provide a mechanical stop in the open direction, or it is not desirable to use the damper’s open stop, set the adjustable stops on the i2865-V /866V/885-V controller to the desired position. Use a ¼” hex driver to adjust the screw stop on the controller.
Note: For the 866-V model only, the damper position feedback reporting option can be enabled by setting the Andover Continuum attribute, LCDState, to ENABLED. The attribute, Override Value, indicates the damper position as a fractional value from 0 (at the closed stop) to 1 (at the open stop). Note: For information about programming the actuator, see “Actuator Programming and Use” in Section 8.
Refer to the i2/b3 865/866/885-V Controller Installation Instructions, 30-3001-985, for additional information regarding the installation of your new “-V” controller.
i2 Controller Technical Reference
35
Page 42
36
Schneider Electric n