Page 113
7 . . . . . . Expansion Interface i2 Controller Technical Reference
107
Page 114
108
Schneider Electricn
Page 115
Controller Expansion Interface UL-864 Note: The use of the Expansion Interface is not listed for UL-864 Smoke Control Applications.
The following controllers include an expansion connector that allows you to add to the number of inputs or outputs via an external expansion module: i2810 Series i2850 Series i2920 (not expandable when used in an SX8000-based Infinity System) Modules include various input, output and display/keypad models: The INPUT modules are: ƒ xPDI8; 8-Channel Digital Input Module
ƒ xPUI4; 4-Channel Universal Input Module
The OUTPUT modules are: ƒ xPAO2; 2-Channel Analog Output Module
ƒ xPAO4; 4-Channel Analog Output Module
ƒ
DO2; 2-Channel Relay Output Module
ƒ
DO4; 4-Channel Relay Output Module
The BI-DIRECTIONAL (contain both inputs and outputs) modules are: ƒ xPBA4; 4 Universal Inputs, 4 Analog Outputs Module
ƒ xPBD4; 4 Universal Inputs, 4 Digital Outputs Module
The DISPLAY modules are: ƒ xPDisplay; Internal Mounted Keypad/Display Module (i2920 only)
ƒ xPRemote Display; Externally Mounted Keypad/Display Module
Expansion modules are connected to the controller via the expansion connector located on the bottom of the unit. Modules can be directly connected to the controller or be interfaced using a cable.
The Expansion Connector is located on the bottom of the controller i2 Controller Technical Reference
109
Page 116
Possible Expansion I/O Module Combinations These combinations are based on current draw and programming limitations. The following tables describe the Andover Continuum Point Count and the modules necessary to make the combination. Analog Output Only Expansion: Point Count
Modules Necessary
2 Analog Outputs xPAO2
2 Analog Outputs xPAO2 + xPAO2
4 Analog Outputs xPAO4
Digital Output Only Expansion: Point Count
Modules Necessary
2 Digital Outputs xPDO2
4 Digital Outputs xPDO2 + xPDO2
4 Digital Outputs xPDO4
6 Digital Outputs xPDO4 + xPDO2
Digital Input Only Expansion:
110
Point Count
Modules Necessary
8 Digital Inputs xPDI8
16 Digital Inputs xPDI8 + xPDI8
Schneider Electricn
Page 117
Universal Input Only Expansion: Point Count
Modules Necessary
4 Universal Inputs xPUI4
8 Universal Inputs xPUI4 + xPUI4
Keypad/Display Only Expansion * Point Count 16 button, 2 x 16 char display
Modules Necessary xPDISPLAY
I/O Combination Expansion: Point Count
Modules Necessary
2 Analog, 2 Digital Outputs xPAO2 + xPD02
2 Analog, 4 Digital Outputs xPAO2 + xPDO4
2 Analog Outputs, 8 Digital Inputs xPAO2 + xPDI8
2 Digital Outputs, 8 Digital Inputs xPDO2 + xPDI8
4 Universal Inputs, 4 Digital Outputs xPUI4 + xPDO4
4 Universal Inputs, 8 Digital Inputs xPUI4 + xPDI8
Combination Display Expansion*: Point Count
Modules Necessary
2 Analog Outputs, Display xPAO2 + xPDISPLAY
2 Digital Outputs, Display xPDO2 + xPDISPLAY
4 Digital Outputs, Display xPDO4 + xPDISPLAY
4 Universal Inputs, Display xPUI4 + xDISPLAY i2 Controller Technical Reference
111
Page 118
8 Digital Inputs, Display xPDI8 + xPDISPLAY
16 Digital Inputs, Display xPDI8 + xPDI8 + xPDISPLAY
2 Digital Outputs, 8 Digital Inputs, Display xPDO2 + xPDI8 + xPDISPLAY
2 Analog Outputs, 8 Digital Inputs, Display xPDAO2 + xPDI8, + xPDISPLAY
4 Universal Inputs, 2 Digital Outputs, Display xPUI4 + xPDO2 + xPDISPLAY
4 Universal Inputs, 8 Digital Inputs, Display xPUI4 + xPDI8 + xPDISPLAY
*Expansion Power Limitation The Expansion Interface allows for two modules plus the xPDisplay as long as the combination does not draw more current than the Controller can supply. Controllers can supply a maximum of 180mA @ 24 VDC. Refer to the individual power requirements for each module listed below.
Power Consumption of Expansion Modules The number of Expansion Modules is limited by the capacity of the power supply current available from the controller. The maximum current available is 180 mA.
The table below lists the current draw for each Expansion Module.
112
Module
# Channels xPAO2; Analog Output Module
2
80mA xPAO4; Analog Output Module
4
120mA xPDO2; Digital Output Module
2
60mA xPDO4; Digital Output Module
4
100mA xPDI8; Digital Input Module
8
25mA xPUI4; Universal Input Module
4
50mA xPBA4; Bi-directional Module
8 (4 UI, 4 AO)
60mA xPBD4; Bi-directional Module
8 (4 UI, 4 DO)
125mA xPDisplay; Keypad/Display Module
N/A
70mA
Schneider Electricn
Current draw @ 24VDC
Page 119
Expansion Cable Connections Expansion modules are connected to the controller and each other via the expansion connector or by using a cable. There are two types of cables available and two lengths of each type. The following table outlines the types, their use and the Schneider Electric part numbers for each.
Type
Usage
Length
Part #
Female-Male
Controller-Module Module-Module
3 Feet (914 mm)
XP-MOD-CABLE-3
Female-Male
Controller-Module Module-Module
10 Feet (3 M)
XP-MOD-CABLE-10
Female-Female
Controller-Display Module-Display
3 Feet (914 mm)
01-0100-484
Female-Female
Controller-Display Module-Display
10 Feet (3 M)
XP-DISP-CABLE-10
The following pages detail possible expansion module connections and illustrate the use of the expansion cables. Note: The total length of all cables cannot exceed 10 Feet (3M)
i2 Controller Technical Reference
113
Page 120
Basic Expansion (no Display) Adding expansion modules to a supported controller is a simple task of plugging the two together. The supported configurations for simple local expansion are illustrated below. The modules used must conform to the supported combinations list shown on the first page of this section.
Remote Expansion (no Display) The system allows modules to be located up to 10’ (3M) from the main controller. Expansion cables are available in 3’ (914mm) and 10’ (3M) lengths. The supported basic remote expansion configurations are illustrated below:
114
Schneider Electricn
Page 121
Basic Expansion (with External Display) The remote xP Display may be added to any supported controller as well as in addition to up to two expansion modules. The supported configurations for simple local expansion are illustrated below. As before, the modules used must conform to the supported combinations list shown on the first page of this section.
+
-
*
.
-
#
+
-
*
.
-
#
+
-
*
.
-
# i2 Controller Technical Reference
115
Page 122
Remote Expansion (with External Display) The system allows modules display modules to be added to remote expansion modules as well. The supported basic remote expansion configurations are illustrated below:
+
-
*
.
-
#
+
-
*
116
Schneider Electricn
.
-
#
Page 123
Basic Expansion (i2920 with Internal Display) The xP Display may be added internally to any i2920 controller as well as in addition to up to two expansion modules. The supported configurations for simple local expansion are illustrated below. As before, the modules used must conform to the supported combinations list shown on the first page of this section.
+
-
*
+
-
.
-
*
#
.
#
-
Remote Expansion (i2920 with Internal Display)
+
-
+
-
+
-
+
+
*
.
-
#
*
.
-
#
*
.
-
#
*
.
-
#
-
*
.
-
# i2 Controller Technical Reference
117
Page 124
Expansion Input/Output Wiring Terminations are typically located along the right and left side of the expansion module. Connection is via screw terminal. The following diagram details each module’s connections:
xPUI4
V
1
1
2
V GND
GND
C
NC
1
NO
I
I V
V GND
GND
2
NC
I
I
1
NC
2
C
NC
2
NO
V
NC
3
GND V GND
118
Schneider Electricn
C NO
I
4
C NO
I
3
C NO
NC
4
C NO